TMR Circuit to Combine Three Analog Currents into a Single Output
The following figure displays 0-20 mA outputs combined through a 2/3 current sharing circuit that allows the three outputs to
be voted to one. Failure of a 0-20 mA output is sensed and a deactivating relay contact is opened.
TMR Circuits for Voted 0-20 mA Outputs
48
GEH-6721_Vol_I_BP
GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I