GE Mark VIe System Manual page 146

Hide thumbs Also See for Mark VIe:
Table of Contents

Advertisement

6.6.2.1 General Practices
The following general practices should be used for all levels of cabling:
All cables of like signal levels and power levels must be grouped together in like cableways.
In general, different levels must run in separate cableways, as defined in the different levels. Intermixing cannot be
allowed, except as noted by exception.
Interconnecting wire runs should carry a level designation.
If wires are the same level and same type signal, group those wires from one cabinet to any one specific location together
in multiconductor cables.
When unlike signals must cross in trays or conduit, cross them in 90° angles at maximum spacing. Where it is not
possible to maintain spacing, place a grounded steel barrier between unlike levels at the crossover point.
When entering terminal equipment where it is difficult to maintain the specific spacing guidelines displayed in the
following tables, keep parallel runs to a minimum, not to exceed 1.5 m (5 ft) in the overall run.
Where the tables display tray or conduit spacing as 0, the levels can be run together. Spacing for other levels must be
based on the worst condition.
Trays for all levels should be solidly grounded with good ground continuity. Conduit should provide shielding.
The following general practices should be used for specific levels of cabling:
When separate trays are impractical, levels L and M can be combined in a common tray if a grounded steel barrier
separates levels. This practice is not as effective as tray separation, and may require some rerouting at system startup. If
levels L and M are run side-by-side, a 50 mm (1.97 in) minimum spacing is recommended.
Locate levels L and M trays and conduit closest to the control cabinets.
Trays containing level L and level M wiring should have solid galvanized steel bottoms and sides and be covered to
provide complete shielding. There must be positive and continuous cover contact to side rails to avoid high-reluctance air
gaps, which impair shielding.
Trays containing levels other than L and M wiring can have ventilation slots or louvers.
Trays and conduit containing levels L, M, and H(S) should not be routed parallel to high power equipment enclosures of
100 kV and larger at a spacing of less than 1.5 m (5 ft) for trays, and 750 mm (2.5 ft) for conduit.
Level H and H(S) can be combined in the same tray or conduit but cannot be combined in the same cable.
Level H(S) is listed only for information since many customers want to isolate unfused high voltage potential wires.
Do not run levels H and H(S) in the same conduit as level P.
Where practical for level P and/or P(S) wiring, route the complete power circuit between equipment in the same tray or
conduit. This minimizes the possibility of power and control circuits encircling each other.
146
GEH-6721_Vol_I_BP
GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I
Public Information

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mark vies

Table of Contents