IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide

PowerBoost1 Information

LED Indicator
AC (green)
ACTIVE (green)
LOW BATT (yellow)
TROUBLE (yellow)
Notes:
If AC power is lost and the battery voltage falls below 10v, the PowerBoost1 output voltage will be turned
off. The output power is turned back on when AC power is restored.
You must use the DIP switch settings shown below.
STATUS
AC power available.
Cyclical flashing – normal communications.
Repetition of 3 flashes – loss of communications.
Missing or low battery.
One or more trouble conditions exist, such as; overload, output
supervision, ground fault, or charger failure.
PowerBoost1
LOW BATT LED
INDICATOR
ON
1
2 3 4
5
(Switch handle = white)
iPGSM-COM-003-V0
– 10 –
TROUBLE LED
INDICATOR
Configure DIP switch
as shown:
ON
1
2 3 4
5
AC LED
INDICATOR
ACTIVE LED
INDICATOR