2.4 Routine Maintenance for the Cooling System

Table 2-12
If the NetCol5000-C will be idle for a long time in the low temperature area, switch off the
chilled water stop valve and humidifier water inlet valve to prevent freezing.
Issue 01 (2019-03-05)
Mai
nten
ance
Peri
od
Quart
erly
Annu
ally
Annu
ally
describes the routine maintenance requirements for the NetCol5000-C.
The condensate pump, float, electric heater, and humidifier are optional components. If not configured,
ignore the maintenance for them.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Operation
Standard
Point
Operating
thermometer
temperatu
re: –10° C
and T/H sensor
to +55° C
Humidity
:
5%–95%
RH
Visual
The piece of
observation
white paper
that you use
to wipe the
cabinet panel
is clean.
Visual
No metal
observation
component
rusts.
2 Routine Maintenance
Troubleshooting
Check whether the air
conditioner and dehumidifier
in the equipment room
function properly.
If the piece of white paper
turns black, clean the new
main way.
If any metal component
experiences severe
oxidation, remove the
rust or replace the
component in a timely
manner.
If the component was
painted before, repaint it
after removing the rust.