Step 7 Pull the handle on the cover to remove the cover, as shown by (7) in
Step 8 Replace the faulty component in the electric control box.
Step 9 Install the electric control box by following steps from
Step 10 Close and lock the rear door.
----End

5.2.3 Replacing an Air Filter

Prerequisites
Context
Preparation: maintain from the rear door.
Procedure
Step 1 Open the rear door.
Step 2 Rotate the baffle plate and remove the air filter.
Step 3 Install the spare air filter.
Step 4 Close and lock the rear door.
Step 5 Tap Maint > Performance Maint on the home screen to enter the performance maintenance
screen and clear the runtime of the air filter.
----End

5.2.4 (Optional) Replacing a Condensate Pump

Prerequisites
Context
Recommended tool: Phillips screwdriver
Preparations: The device is only maintained from the rear door, and is powered off.
Procedure
Step 1 Turn off all AC input switches.
Step 2 Open the rear door.
Issue 01 (2019-03-05)
The air filter needs to be replaced.
A spare air filter of the same model is available and functional.
The condensate pump needs to be replaced.
A spare and functional condensate pump valve is available.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Parts Replacement
Figure
5-29.
Step 1
to
Step 7
in the reverse order.