Electrical Connections

You must connect the following cables to the RTU-A01P unit:
– 12V power cable.
– L
W
ON
ORKS
– I/O cables from the contacts/sensors.
Make sure that the 12V cable corresponds in size to the norms
indicated in the table below; the size of the 12V cable can be
calculated using the following table (maximum voltage drop on the
cable = 0.5V):
Cable length (m) = 0.5V / (I[A] load x 2 x (res [Ohm/km] /1000))
Type of cable
AWG
mm2
10
5,25
12
3,3
14
2
16
1,3
18
0,9
20
0,6
22
0,35
• The L
W
ON
ORKS
• In a free-topology configuration, the sum total of the sections must
not exceed 500m.
• In a bus configuration, the sum total of the sections must not
exceed 2700m.
• In a free-topology configuration, activate the 50ohm terminator by
placing the appropriate jumper on the FTT10A plug-in of the
TemaServer.
• In a bus configuration, place two terminators (with resistance
values of 100ohm 1% ½W) at the two ends of the bus.
• Check that the length of the L
to the norms indicated in Table 1.
1
L
W
®
is a trademark of the Echelon Corporation
ON
ORKS
Page 2
1
twisted-pair cable.
Ohm/Km 100 [mA] 200 [mA] 500 [mA]
3,41
733
5,7
439
8,8
284
14
179
21
119
34
74
52
48
1
data cable must be twisted-pair.
Length (m) in relation to base load
1 [A]
367
147
219
88
142
57
89
36
60
24
37
15
24
10
W
1
data cable corresponds
ON
ORKS
PRELIMINARY OPERATIONS
2 [A]
5 [A]
73
37
44
22
28
14
18
9
12
6
7
4
5
2
15
9
6
4
2
1
1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Temaline rtu a11Temaline tk c21sTemaline rtu a01p

Table of Contents