Honeywell temaline TK C21P Installation Manual page 10

Plc processor
Table of Contents

Advertisement

When the cables go outdoor is mandatory to use shielded cables. The
cables' shielding must be connected to the respective ground
connectors (-V).
For internal wiring without shielded cables is recommended an
electrical environment where the cables are well separated, even at
short runs, especially to the power cables or external cables which
can be essentially subjected to interference or lighting.
Use a twisted-pair cable for the contact cables. Make sure that the
cables correspond in size to the norms indicated in.
Max contact resistance = 25 Ohm
Page 6
Cable type
AWG
mm2
ohm/Km
12
3,3
14
2
16
1,3
18
0,9
20
0,6
22
0,35
24
0,2
Table 3. Length of Contact Cables
Lenght
[m]
5,7
2193
8,8
1420
14
21
34
52
85
893
595
368
240
147
INSTALLATION

Advertisement

Table of Contents
loading

This manual is also suitable for:

Temaline rtu a11Temaline tk c21sTemaline rtu a01p

Table of Contents