Thyristor unit from 125a to 500a

Advertisement

Quick Links

EN1I-6305
USER'S MANUAL
S
Rev. 12/2004
CD3000
-3PH
THYRISTOR UNIT
125A
500A
From
to

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell CD3000S-3PH

  • Page 1 EN1I-6305 USER’S MANUAL Rev. 12/2004 CD3000 -3PH THYRISTOR UNIT 125A 500A From...
  • Page 2 EN1I-6305...
  • Page 3 User’s Manual CD3000S-3PH from 125A to 500A Honeywell CD3000S-3PH Thyristor Unit from 125A to 500A Index: Glossary 1.1 Terminology 1.2 Input signal 1.3 Power feed back 1.4 What is a thyristor unit Technical specifications 2.1 General Features: 2.2 Input features 2.3 Output features...
  • Page 4 Honeywell CD3000S-3PH from 125A to 500A User’s Manual CAUTION Thyristor units are used in power industrial equipment. When the thyristor unit is working, there are on the unit the following voltages - Maximum main supply voltage on power terminals up to 600V.
  • Page 5 User’s Manual CD3000S-3PH from 125A to 500A Honeywell Protection(protection) CD3000 thyristor family has a polymeric plastic cover in compliance to International specification IP20. To understand if IP20 protection is sufficient should be evaluated the installation place where the units are installed.
  • Page 6: Input Signal

    Honeywell CD3000S-3PH from 125A to 500A User’s Manual 1. Glossary 1.1 Terminology voltage power supply. the full circulating current in thyristor unit. total load power. 1.2 Input signal SSR: This input type is a square waveform generated by a temperature controller.
  • Page 7: Technical Specifications

    User’s Manual CD3000S-3PH from 125A to 500A Honeywell 2. Technical specifications 2.1 General Features: Operating temperature 0÷45°C for higher temperature see derating curve Voltage power supply 24V minimum, 480V max and 600V on request Input signal Zero Crossing (ZC) Firing mode Auxiliary voltage supply 200÷230V ±15%;...
  • Page 8: Output Features

    Honeywell CD3000S-3PH from 125A to 500A User’s Manual 2.3 Output features Ripetitive peak Latching Max peak Leakage T value for Frequency Power Isolation Current Voltage range reverse voltage current one cycle current fusing range loss Voltage I=Inom (480V) (600V) (mAeff) (10msec.) (A) (mAeff) tp=10msec.
  • Page 9: Ordering Information

    User’s Manual CD3000S-3PH from 125A to 500A Honeywell 3. Ordering information Model CD3000S 3PH CD3000S-3PH Ex:CD3000S 3PH/ 150A/ 400V/ 480V/ 460V/ SSR/ 1 Nominal CURRENT of CD3000S 125A 300A 450A 150A 350A 500A 225A 400A 2 Operating Load Voltage (incoming voltage supply) Specify the value of the line supply.
  • Page 10: Installation And Wiring Information

    Honeywell CD3000S-3PH from 125A to 500A User’s Manual 4. Installation and wiring information 4.1 Identification of the unit Before to install the CD3000S unit examine for damages or deficiencies. If any is found, notify the carrier immediately. Check that the product features shown on CD3000S identification label corresponds to that ordered.
  • Page 11 User’s Manual CD3000S-3PH from 125A to 500A Honeywell 4.3 Dimensions Size W(mm) H(mm) D(mm) 125A (S11) 150A (S11) 225A (S13) 300A (S14) 350A (S14) 400A (S14) 450A (S14) 500A (S14) www.honeywell.com/imc...
  • Page 12: Fixing Holes

    Honeywell CD3000S-3PH from 125A to 500A User’s Manual 4.4 Fixing Holes Size A(mm) B(mm) C(mm) 125A (S11) 150A (S11) 225A (S13) 300A (S14) 350A (S14) 400A (S14) 450A (S14) 500A (S14) www.honeywell.com/imc...
  • Page 13: Wiring Instructions

    User’s Manual CD3000S-3PH from 125A to 500A Honeywell 5. Wiring instructions 5.1 Removing the cover To open the unit apply as follow. For S11 size you must open the cover to configure the unit and to view the fuses For S13 and S14 sizes, you must open the cover to cable, to configure the unit and to view the fuses Warning: this procedure can be done just by specialized personnel CD3000S unit has isolated heatsink.
  • Page 14: Auxiliary Terminals

    Honeywell CD3000S-3PH from 125A to 500A User’s Manual 5.1.1 Auxiliary Terminals Before connect or disconnect, make sure that the power, control cables and wires are insulated from the voltage Terminal Description Auxiliary supply voltage 230-460Vac (600V opt.) N.C. not connected Auxiliary supply voltage 230-460Vac (600V opt.)
  • Page 15 User’s Manual CD3000S-3PH from 125A to 500A Honeywell 5.1.2 Power Terminals Before connect or disconnect, make sure that the power, control cables and wires are insulated from the voltage Terminal Description Line Input Phase 1 Load Output Phase 1 Line Input Phase 2...
  • Page 16: Cabling Detail

    Honeywell CD3000S-3PH from 125A to 500A User’s Manual 5.2 Cabling detail Use 75°C copper (CU) conductor only, provided with the terminal type indicated below. Torque/couple Wire Wire Current/courant Lb-in (N-m) Range/cable Terminal/terminal 125A, 150A, Polymeric Terminal 310 (35.0) 225A Block M8...
  • Page 17 User’s Manual CD3000S-3PH from 125A to 500A Honeywell Power terminals: wire details: Current Supply Load L1, L2 and L3 T1, T2 and T3 Cable Screw Cable Screw 125A 150A 225A 300A 2 x 70 2 x 1/0 2 x 70...
  • Page 18: Wiring Connection

    Honeywell CD3000S-3PH from 125A to 500A User’s Manual 5.3 Wiring connection 5.3.1 CD3000S 3PH 125-500A 240/460V 1 240/460V 3 PE 4 FAN 5 FAN SUPPLY 230V Std FAN 6 RESET 7 RESET 8 INPUT + 9 INPUT SIGNAL INPUT - 10...
  • Page 19: Led Status Table

    User’s Manual CD3000S-3PH from 125A to 500A Honeywell 5.4 LED Status Table STATUS DESCRIPTION Auxiliary supply is not connect (green led) Auxiliary supply is connect OFF Condition (Load IS NOT Powered) (green led) ON Condition (Load IS Powered) = Light OFF = Light ON www.honeywell.com/imc...
  • Page 20 Honeywell CD3000S-3PH from 125A to 500A User’s Manual 6. Start up Before to supply the thyristor unit: • verify that load current equal or less than nominal; For resistive load (star or delta) For resistive load open delta • verify that there is no short circuit on load;...
  • Page 21: Auxiliary Supply

    User’s Manual CD3000S-3PH from 125A to 500A Honeywell 6.1 Auxiliary supply Warning: this procedure can be done just by specialized personnel. To change auxiliary supply voltage sold the correct link-jumper on main PCB. Auxiliary supply jumpers for S11, S13 and S14 sizes...
  • Page 22: Input Configuration

    Honeywell CD3000S-3PH from 125A to 500A User’s Manual 6.2 Input configuration Warning: this procedure can be done just by specialized personnel. Location of auxiliary supply jumpers for S11, S13 and S14 sizes Jumpers Configuration MAIN PCB Input A B C FITTED www.honeywell.com/imc...
  • Page 23: Thyristor Firing Mode

    User’s Manual CD3000S-3PH from 125A to 500A Honeywell 7. Thyristor firing mode 7.1 Zero Crossing(ZC) ZERO CROSSING ZC firing mode is used with Logic Output VOLTAGE SUPPLY (V) from temperature controllers Thyristor operate like a contactor. The Cycle time is performed by temperature controller.
  • Page 24: Fuses And Fuseholder

    Honeywell CD3000S-3PH from 125A to 500A User’s Manual 8. Fuses and fuseholder 8.1 Fuses and Fuse Code CD3000S unit must be protected by fuses against short circuit selecting the proper I²t that must be lower than thyristor one. The same caution must be taken if Circuit Breaker is used. Remember that is very difficult to protect the thyristor if this choice is done.
  • Page 25: Maintenance

    User’s Manual CD3000S-3PH from 125A to 500A Honeywell 9. Maintenance 9.1 Trouble Shooting Small problems sometimes can be solved locally with the help of the below tab of trouble shooting. If you don’t succeed, contact us or your nearest distributor.
  • Page 26: Repairing Procedure

    Honeywell CD3000S-3PH from 125A to 500A User’s Manual 9.2 Repairing procedure • Phone to us. • Explain to Service Engineer the problem because sometimes it can be solved with a phone call. • If this is not possible ship the unit to us or to your distributor.
  • Page 27 User’s Manual CD3000S-3PH from 125A to 500A Honeywell www.honeywell.com/imc...
  • Page 28 However, we assume no responsibility for its use. While we provide application assistance personally, through our literature and the Honeywell website, it is up to the customer to determine the suitability of the product in the application.