When the cables go outdoor is mandatory to use shielded cables. The
cables' shielding must be connected to the respective ground
connectors (-V).
For internal wiring without shielded cables is recommended an
electrical environment where the cables are well separated, even at
short runs, especially to the power cables or external cables which
can be essentially subjected to interference or lighting.
Use 4-wire (or 5-wire, if the sensor is provided with input disable)
cables for the connections to the sensors. Make sure that the cables
correspond in size to the norms indicated in Table 4 (maximum voltage
drop on the cable = 0.1V):
Cable length(m) = 0.1V / (I[A] load x 2 x (res [Ohm/km] /1000))
I load max for each sensor = 100mA (400mA overall)
Type of cable
AWG
12
14
16
18
20
22
24
Page 8
mm2
ohm/Km
20 [mA]
3,3
5,7
2
8,8
1,3
14
0,9
21
0,6
34
0,35
52
0,2
85
Table 4. Sensor Cable Length
in relation to current absorbed by sensor
50 [mA]
100 [mA] 200 [mA] 500 [mA]
439
175
284
114
179
71
119
48
74
29
48
19
29
12
Length (m)
88
44
57
28
36
18
24
12
15
7
10
5
6
3
INSTALLATION
18
11
7
5
3
2
1