10. Technical data

Type voltage
Mains frequency
Load description
Operating modes
Digital set point inputs (connection signals)
The Thyro-S has 2 set point inputs. The set point inputs are safely disconnected from
the mains (SELV, PELV).
Set point 1:
Set point 2:
Ambient temperature
35°C external cooling (F model with integrated ventilator)
45°C self air cooling
At higher temperatures it is possible to operate with reduced type current:
Temperature range up to 55°C: type current –2% / °C
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
230 Volt -57% +10%
400 Volt -57% +10%
500 Volt -57% +10%
all models 47Hz bis 63Hz; f=6Hz;
max. frequency change 5% per half wave
ohmic load
Name
Load signal, with digital set point = ON
1:1
all full wave (default setting)
1:2
every 2. mains full wave
1:3
every 3. mains half wave (d.c. free)
1:5
every 5. mains halve wave (d.c. free)
Logic input 0-24V
R
System interface, connection from superset automation
system via optional bus module.
Π3,3k
ON Π3V
i
51