Programming For Panel Linking; Programming For 4100Sm; Programming For Access Control - Honeywell VISTA-128BPEN Installation And Setup Manual

Commercial burglary partitioned security system with scheduling
Table of Contents

Advertisement

Vista-128BPEN Installation and Setup Guide

Programming for Panel Linking

Step
Action
1
Program the Panel Link Module (PLM) into
the system in Device Programming in the #93
Menu Mode with Device Type 10.
2
If you want to supervise the PLM, program
zone 8xx with response type 05, where "xx" =
the module's address. If you want the zone to
report to the central station, make sure the
report code for the zone is set with a non-zero
value.

Programming for 4100SM

✳05 Enter 1 to print all zone faults/restores; enter
0 to print only events enabled in field 1✳70
✳14 Enter 1 if using Home Automation (cannot use
both serial printer and Home Automation)

Programming for Access Control

VistaKey
See the VistaKey-SK Installation and Setup Guide for
the detailed programming instructions.
VistaKey Dialer Enables
When the VistaKey is installed with an alarm system,
the system defaults are set so that the system does not
send reports to the central station. The programming is
accomplished in field 1∗35 for the following events:
ACS Troubles - To enable or disable ACS trouble
reporting.
ACS Bypasses - To enable or disable ACS bypass
reporting.
ACS System - To enable or disable ACS system
reporting, (i.e., ACS module reset).
ACS Alarms - To enable or disable ACS alarm
reporting.
Dialer (Trace) - To enable or disable access
grant/denial events sent to the central station.
PassPoint
The PassPoint ACS can dedicate some of its inputs for
use as regular VISTA-128BPEN hardwired zones (the
zone response type is ACS). The PassPoint ACS can
also utilize the control panel dialer for reports to the
central station.
PassPoint Dialer Events
All PassPoint ACS events can be sent to the VISTA-
128BPEN dialer via the VGM. These events will also be
logged into the control's event log. This is enabled in
4-8
Step
Action
3
If you want to supervise the PLMs
connected to other controls, program those
modules in Zone Programming with response
type 12. Also, program the panel ID number.
The ID number must match the ID number
programmed in Device Programming of the
control panel the PLM is connected. If you
want the zone to report to the central station,
make sure the report code for the zone is set
with a non-zero value. Be sure to program
the input type with 00.
See Device Programming and Zone Programming in #93
Menu Mode Programming in the Programming Guide
for a detailed explanation of the programming
procedures.
1✳70 Event Log Types (1=enable; 0=disable
1✳71 12/24-Hour Time Stamp (0=12 hr; 1=24 hr)
1✳72 Printer On-line (0=disable; 1=enable)
1✳73 Enter 0 for 1200 Baud Rate
the PassPoint ACS. See the PassPoint ACS
documentation for a detailed explanation.
Programming the VISTA Gateway Module
See the PassPoint ACS instructions to program the
VISTA Gateway Module.
Using ACS Zone Inputs
If the PassPoint ACS has uncommitted zones, these
may be used by the VISTA-128BPEN as hardwired
zones. To program for ACS zone inputs, perform the
following steps:
Step
Action
1
Enter Zone Programming in the #93 Menu
Mode.
2
Program this zone as any other zone. Indicate
the input type as ACS (10).
3
Enter the PassPoint ACS's zone ID (00-31)
See Zone Programming in the Programming Guide for a
detailed explanation.
Access Control of an Entry/Exit Point
The control can send entry and exit requests to the
VistaKey or PassPoint ACS utilizing keypads and
button-type (BR) RF transmitters. A zone is
programmed with a response type 27 (Access Point) and
an appropriate input type (console, RF).