Figure 3-29: Wiring The Vistakey - Honeywell VISTA-128BPEN Installation And Setup Manual

Commercial burglary partitioned security system with scheduling
Table of Contents

Advertisement

Vista-128BPEN Installation and Setup Guide
To mount and wire the VistaKey module, perform the following steps:
Step
Action
1
Mount the VistaKey, door strike or mag lock, and card reader.
2
Mount the door status monitor (DSM) and/or request-to-exit (RTE) devices.
3
Using Figure 3-29 as a reference, connect the card reader interface cable to TB3, making the +5V or +12V
connection last.
4
Connect the leads to TB1 in the following order:
a. All ground leads to terminals 2, 5, and 9.
b. The DSM, (optional) RTE, and General Purpose leads to terminals 6, 7, and 8, respectively.
c. Door strike (or mag lock) lead to terminal 10.
d. Local +12V or +24V supply lead to terminal 1.
e. Local +12V or +24V supply lead to the N/C relay terminal 11 (if a mag lock is being used), OR to the N/O
relay terminal 10 (if a door strike is being used).
5
Connect the (–) polling loop and (+) polling loop leads (from the VISTA-128BPEN) to terminals 4 and 3,
respectively.
6
Set the Address Select switch to the desired access door number (1-8)
7
Repeat steps 1 through 6 for each VistaKey being installed.
Connecting the Card Reader
THIS DEVICE COMPLIES WITH PART 15 CLASS A
LIMITS OF FCC RULES. OPERATION IS SUBJECT
TO THE FOLLOWING TWO CONDITIONS:
(1) IT MAY NOT CAUSE HARMFUL INTERFERENCE.
(2) IT MUST ACCEPT ANY INTERFERENCE THAT
MAY CAUSE UNDESIRED OPERATION.
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION'S STANDARDS 70 &
74 (NATIONAL FIRE PROTECTION ASSOC.,
BATTERYMARCH PARK, QUINCY, MA. 02269).
PRINTED INFORMATION DESCRIBING PROPER
MAINTENANCE, EVACUATION PLANNING AND
REPAIR SERVICE IS TO BE PROVIDED WITH
THIS EQUIPMENT.
FOR ADDITIONAL RATINGS AND
SPECIFICATIONS, REFER TO
INSTALLATION INSTRUCTION
FOR THE VISTAKEY-SK.
WEEKLY TESTING IS REQUIRED
TO ENSURE PROPER OPERATION
OF THIS SYSTEM.
3-26
Lead from Reader
Lead Color
Green LED
Orange
Ground*
DATA 1 (Clock)
DATA 0 (Data)
+5VDC†
+12VDC†
*
TB-3 Terminal 5 is also a ground and may be used
instead of terminal 2. Terminals 2 and 5 are a common
† Connect to +5VDC OR +12VDC per reader
manufacturer's specification.
1
2 3 4 5 6 7 8 9 10
TB 1
VISTAKEY

Figure 3-29: Wiring the VistaKey

To VistaKey TB3
Terminal #
1
Black
2
White
3
Green
4
Red†
6
Red†
7
ground.
14V MAX (12V @ 85-160mA Nominal)
GND
POLLING LOOP +
POLLING LOOP -
GND
ZONE A (DSM)
ZONE B (RTE)
ZONE C (General)
GND
POLE Door Strike/Mag Coil
N/C MAG COIL POWER
N/O DOOR STRIKE POWER
RELAY CONTACT RATINGS:
11 12
3A @ 28VDC MAX. (RESISTIVE LOAD)
K1
DOOR
READER INTERFACE CABLE
CONTROL
RELAY
RDR LED
(ORANGE)
1
GND
(BLACK)
2
DATA 1
(WHITE)
3
DATA 0
(GREEN)
4
TB 3
GND
5
+5V
6
+12V
(RED)
7
8
TRIGGER (SEE NOTE 3)
+
NOTE 1: USE UL LISTED ENERGY CABLE FOR ALL CONNECTIONS.
NOTE 2: VISTAKEY TB3 TERMINAL 5 IS A GROUND AND MAY BE
USED INSTEAD OF TB3 TERMINAL 2. TB3 TERMINALS 2 AND 5 ARE
A COMMON GROUND.
NOTE 3: WHEN USING TRIGGER TO TURN ON AN LED OR BUZZER,
RETURN HIGH SIDE OF LED OR BUZZER TO TB3 TERMINAL 7.
TRIGGER RATING IS 15mA AT 12VDC.
TO ALARM SYSTEM
CONTROL PANEL
POLLING LOOP TERMINALS.
+ 12 VDC TO ONLY
ONE OF THESE INPUTS.
(FROM TB1-1)
NO
CONNECTION