To install the 5881ENHC RF receiver, perform the following steps:
Step
Action
1
Mount the receiver, following the advisories stated previously.
2
Set the DIP switches in the receiver for the address (01-07). See Figure 3-19.
Make sure the address setting is not being used by another device (keypad, relay module, etc.).
3
If installing a 5881ENHC, install a flat-head screw (supplied) in the case tamper tab as shown in Figure 3-18.
When the receiver is pried from the wall, the tamper tab will break off and remain on the wall. This will
activate a tamper switch in the receiver and cause generation of a tamper signal. Note that this signal will
also be generated when the receiver's front cover is removed.
4
Connect the receiver's wire harness to the keypad terminals (6, 7, 8, and 9). Plug the connector at the other
end of the harness into the receiver.
5
Refer to the Installation Instructions provided with the receiver for installations regarding antenna
mounting, etc.
MOUNTING
HOLES
Installing the 5800TM Module
Installation of this module is necessary only if you are using a 5827BD or 5804BD Bi-directional device.
The address for the 5800TM must be enabled in the control's Device Programming in the #93 Menu Mode as a
keypad and then assigned to a partition.
To install the 5800TM, perform the following steps:
Step
Action
1
Mount the unit using its accompanying mounting bracket near the RF receiver.
The 5800TM must not be installed within the control cabinet. It must be between one and two feet
from the receiver's antennas.
2
Set the module for the appropriate address. For Address Setting 28 cut the red jumper; for Address 29 cut the
white jumper; for Address 30 cut both jumpers.
Make sure the address setting is not being used by another device (keypad, relay module, etc.).
3
Connect the module's wire harness to the keypad terminals (6, 7, 8, and 9). Plug the connector at the other
end of the harness into the module.
ANTENNAS
INSERT IN
CIRCUIT
RIGHT-HAND
BOARD
TERMINALS
DIP SWITCH
INTERFERENCE
INDICATOR LED
DIP SWITCH #5 (PRESET ONLY ON 5881EH)
ON: SETS 5881EH FOR USE IN COMMERCIAL
FIRE APPLICATIONS (SEE THE RECEIVER'S
INSTRUCTIONS)*.
OFF: USE IN NON-COMMERCIAL FIRE
INSTALLATIONS.
* FOR COMMERCIAL FIRE APPLICATIONS
THE 5881EH PC BOARD MUST BE MOUNTED
IN A SEPARATE CABINET (SEE RECEIVER'S
INSTRUCTIONS FOR DETAILS).
Figure 3-19: 5881ENHC RF Receiver (cover removed)
TO CONTROL'S REMOTE KEYPAD
CONNECTION POINTS.
USE MAX. of 220 ft. [67m of #22 (0.64mm)
WIRE or 550 ft. (168m) of #18 (1mm) WIRE
FOR EACH RUN. OBSERVE 20 ft. MAX.
FOR COMMERCIAL FIRE INSTALLATIONS.
(SEE RECEIVER'S INSTRUCTIONS.)
YELLOW
DIP SWITCH WHITE AREAS = SWITCH
RED
HANDLES. POSITION 2-4 DETERMINE
BLACK
RECEIVER'S ADDRESS. CONSULT
CONTROL'S INSTRUCTIONS FOR
GREEN
ADDRESS TO USE. DIP SWITCH BELOW
SHOWN SET FOR ADDRESS "0."
WIRING
SWITCH
OPENING
POSITION
5
4
3
PLUG & SOCKET
2
1
Installing the Control
RECEIVER ADDRESS SETTINGS
(" - " MEANS OFF)
0
1
2
3
4
5
6
7
PRESENT ONLY ON 5881EH (SEE TEXT AT LEFT)
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
FOR FUTURE USE
3-15