Two Supplies Equally Likely To Drop Out; Supply Failure Detection Mode - Honeywell Ex-Or CDH4U5 Installation And Commissioning Instructions

4-channel programmable intelligent lighting control module
Table of Contents

Advertisement

c) Two Supplies Equally Likely to Drop Out
SUPPLY 1
L
N
N1
L1
N2 L2
Changeover
Contactor
N
L
As shown in the diagram above, two equal supplies may be connected from a single phase or different phases. In order to maintain constant supply to the unit an
external change-over contactor* is required. Line terminals from each of the supplies (N1, L1 and N2, L2) are connected via the change-over contactor. The
Live and Neutral outputs from the contactor are connected to the mains input of the unit. In the case of failure of one of the supplies, the change-over contactor
switches to the alternative supply to ensure continuous supply to the unit. As shown in the diagram above, one or more channels may be wired to run from either
supply.
* Such as Lovato BG series mini-contactor.
Note: Please refer to AN4027 for recommendations on wiring supplies to the change-over contactor and part number.

Supply Failure Detection Mode

MAINS INPUT
N
+ 1 -
+ 2 -
+ 3 -
+ 4 -
DIMMING CHANNELS
Channel 1 & Channel 4 are equipped with three-wire pluggable terminals with provision of connecting Neutral and Live from each supply. On detection of supply
failure on Channels 1 or 4, the unit enters into special operating mode. During this mode, the unit controls the output of luminares connected to the channel(s)
fed by the remaining supply according to the settings of Scene 5. During this special operating mode, the unit will continue to respond to switch inputs and
occupancy detection. The unit automatically reverts to normal behaviour once the failed supply has been restored.
Note: Please refer to the Commissioning section for programming the channel output settings of Scene 5.
CH1
E
L
Ballast
N
D
D
CH1
E
L
Ballast
N
D
D
MAINS INPUT
D
D
N
L
+ 1 -
+ 2 -
+ 3 -
+ 4 -
DIMMING CHANNELS
SELV SWITCH INPUTS
B COM A
B COM A
5
4
CH1
N1 L1
VOLT FREE CHANNELS
L
CH1
CH2
CH4
CH3
CH2
E
L
Ballast
N
D
D
N1 L1
VOLT FREE CHANNELS
ML
CH1
CH2
1 - 1
COMMS BUS
CH4
CH3
Dimming
CH2
5
B COM A
B COM A
B COM A
3
2
1
ML
VOLT FREE CHANNELS
CH3
1 - 1
2 - 2
COMMS BUS
-4-
SUPPLY 2
Earth not
L
shown for
clarity
N
CH3
CH4
VOLT FREE CHANNELS
N2 L2
CH3
CH4
2 - 2
DETECTOR PORTS
3
4
2
1
N2 L2
CH4
E
L
Ballast
N
D
D
E
L
Ballast
N
D
D
Can be
Maintained
derived
Live
from
Emergency
either
Luminaire
supply

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents