Product Applications; Connections; Technical Data; Dimensions - Honeywell Ex-Or CDH4U5 Installation And Commissioning Instructions

4-channel programmable intelligent lighting control module
Table of Contents

Advertisement

Product Applications

The CDH4U5 may be used in various different applications, e.g. warehouse, school, hospital etc having a single supply or two different supplies. For more
details on the differing applications, please refer to Application Note AN4027.

Connections

Comms
Bus (MLS)
Volt-free
Channels

Technical Data

Operational supply:
Power consumption:
Product rating & recommended circuit protection: 16A or 20A MCB
Maximum load (per channel):
Digital dimming ballasts per channel:
Digital dimming ballasts per LCM:
1-10V dimming ballasts per channel:
Maintained live output:
Mains supply terminal capacity:
Override switch input connector:
MLS bus connector:
MLS bus cable:
Case material:
Case finish:
IP rating:

Dimensions

Width (W) = 213 mm
Height(H) = 62 mm
Depth(D) = 91 mm
Weight
= 0.55kg approx
Enclosure
An enclosure (K5612S MAG) is available for this product. It provides integral connection bars fitted with link.
It features a robust base together with an all-over front cover and moulded lid in an impact-resistant, flame-retardant thermoplastic.
Cable entry points are located on top, bottom, side and rear surfaces.
Colour:
Dimensions:
Protection:
Dimming
Channels
Mains
Input
Maintained
Live VF Output
Volt-free
Channels
230VAC ~50Hz/60Hz
18W maximum
6A
10 maximum
40 maximum
20mA (sinking only). See manufacturer's specification: worst case 10 Ballasts but Philips HF-R, for example,
20 Ballasts.
6A
2x2.5mm≤ or 1x4mm≤
2.5mm≤
2.5mm≤
1.5mm≤ unscreened twisted pair: see Application Note AN4001
Self-extinguishing blend PC/ABS
Gray RAL 7035
20
Magnolia
306mm x 230mm x 110mm
BS EN 60529 to IP2XC
-7-
Detectors
Switches
Additional
Switches

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents