7 .16 Two-stage burner control with two
solenoid valves
The IFD is equipped with two signalling contacts for
operating and fault signals. For controlling two-stage
burners, a bridge must be installed in the lower section of the
housing between terminals 12 and 13. Valve V2 is connected
to terminal 14.
1 2 3 4 5 6 7 8 9 10 11 12 13 14

Z
I
Program sequence
04
01
t W t Z
t SA
During the waiting time t
W
made for flame simulation and fail-safe operation. If no flame
simulation is detected, the IFD 258 opens the
IFD 258 · Edition 03.12l
s2
v1
v2
c
max.
max. 2 A,
2 A,
253 V AC
253 V AC
L1 (L1)
N (L2)
PE
88
1
L1

3
10
11
V1
5
14
V2
8-9
t
after heat demand, checks are
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวี ว ั ฒ นา กทม. 10170.
website:
https://www.add-furnace.com/
Line ID: @add11 e-mail: add028883472@gmail.com
gas valve V1 and ignites the burner. The ignition time t
constant. The safety time t
tion time t
. If a flame is detected during the safety time, the
Z
operation signalling contact closes and valve 2 is opened once
the safety time t
has elapsed.
SA
If no flame is detected, the fault signalling contact clos- es
once the safety time t
has elapsed.
SA
Example of application
Control: ON/OFF or ON/HIGH/LOW/OFF
The burner BIO/BIC starts at low-fire rate. Once the normal
operating state is reached, the automatic burn- er control unit
IFD 258 opens the air valve. The burner switches to high-fire
operation.