Download Print this page

Honeywell Silent Knight WSK-RELAY Installation And Maintenance Instructions page 2

Wireless relay module

Advertisement

COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Silent Knight system control panel (list available from Silent Knight).
BATTERY REPLACEMENT
Low battery levels on the wireless devices are displayed as a trouble on an
annunciator. Therefore when the message "TROUBLE BATTERY LOW" is dis-
played, replace the battery in the device. This message is an indication that
approximately one week of battery life remains.
To replace the batteries in a wireless device use the following steps:
1. Have 4 CR123A (or DL123A) batteries available
2. Remove the faceplate from the module.
3. Open the battery compartment refer to Figure 3.
4. Remove the used batteries and replace with new batteries. The battery com-
partment is designed such that the batteries can only align in the appropri-
ate direction. Do not force the batteries into the openings.
5. Replace the battery compartment cover.
6. Replace the faceplate.
FIGURE 3. BATTERY COMPARTMENT:
BATTERY
COMPARTMENT
SPACING
Wireless technologies can exhibit communication disruption if devices are
spaced too close together. To avoid this form of disruption, SWIFT devices
should not be placed closer than 2 feet (60 cm) apart without an intervening
structure.
MOUNTING
The WSK-RELAY mounts directly to an SMB500 electrical box (see Figure 4).
To avoid interference with the wireless network metal electrical boxes are NOT
recommended. Non-metal surface mounted electrical boxes (SMB500) are
available from Silent Knight. If not using an SMB500, the minimum mounting
opening dimensions for the WSK-RELAY are 4in. X 3¾in. x 1½in. deep.
NOTE: Do not attach the module to temporary structures such that the place-
ment could be altered.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. For applications interfacing with Emergency Control Functions,
field wiring shall be limited to 3' or 20' in non-metallic conduit.
1.
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2.
Set the address on the module per job drawings.
3.
Secure module to electrical box (supplied by installer), as shown in
Figure 4.
Use of these products in combination with non-Honeywell products in a wireless mesh
network, or to access, monitor or control devices in a wireless mesh nework via the inter-
net or another external wide area network, may require a separate license from Sipco, LLC.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
WARNING: Do not make changes to the equipment. Changes or modifications not expressly approved by the manufacturer could void the user's authority to operate the equipment.
Silent Knight
®
and Honeywell
®
are registered trademarks of Honeywell International, Inc.
BATTERY
COMPARTMENT
DOOR
All relay switch contacts are shipped in the standby state (open) state, but may
have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to com-
municate with the panel before connecting circuits controlled by the module.
When interfacing with an emergency control function, that function must re-
spond in 1 second or less.
FIGURE 4. MODULE MOUNTING:
C2002-01
FIGURE 5. TYPICAL MONITORING CONFIGURATION:
T1: NOT USED
T2: NORMALLY OPEN
T3: COMMON
T4: NORMALLY CLOSED
NOTE: IN APPLICATIONS INTERFACING WITH EMERGENCY CONTROL FUNCTIONS,
FIELD WIRING SHALL BE LIMITED TO 3 FEET OR 20 FEET IN NON-METALLIC CONDUIT.
LICENSING STATEMENT
For more information, contact Sipco, LLC or Ipco, LLC at 8215 Roswell Rd., Building 900,
Suite 950, Atlanta, GA 303350, or at www.sipocollc.com or www.intusiq.com.
FCC STATEMENT
2
WARNING
MODULE DOES NOT SUPERVISE
CONTROLLED CIRCUITS
IF ANY WIRING TO TERMINALS 1-4 IS
NONPOWER LIMITED, A NONPOWER
LIMITED LABEL MUST BE PLACED
OVER THE POWER LIMITED TERMINAL
INFORMATION ON THE NAMEPLATE
LABEL. INSTALL CONTACT CLOSURE
DEVICES PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
©2017 Honeywell. 03-02
C1096B-01
C2019B-00
I56-4272-000

Advertisement

loading