CLIF-CBUSLC INTERFACE – INSTALLATION & COMMISSIONING INSTRUCTIONS

C-BUS CONNECTION

The CLIF-CBUSLC features an RS485 interfaces to which C-Bus devices can be connected: RS485-1 (consisting of push-in
terminals 24 [GND-1], 25, and 26).

C-Bus Topologies

Via the C-Bus, up to 30 C-Bus devices (e.g., controllers, etc.) can communicate with one another and a PC central. The C-Bus
must be connected via the individual controllers (open ring).
NOTE:
Star connection is not allowed, as this might cause uncontrollable line reflections.
Instead of CLIF-CBUSLC Interfaces, C-Bus controllers (e.g., the Excel 500, Excel 100, LION, PANTHER) can also be
connected.

C-Bus Cables

NOTE:
Observe national regulations for C-Bus cables!
For Europe; only shielded cable is permitted.
For the U.S., shielded or unshielded cable can be used.
Cable type
J-Y-(ST)Y 2 x 2 x 0.8
A-Y-(ST)Y 2 x 2 x 0.8
AK 3702
AK 3740A
Belden 9842
Belden 9841
AK 3702
AK 3740A
EN1Z-1026GE51 R0417
CLIF-
Excel 100
CBUSLC
Fig. 21. C-Bus topology Excel 5000
Description
shielded, twisted pair
shielded, twisted pair
unshielded, twisted pair
shielded
twisted pair
shielded
unshielded, twisted pair
shielded
Table 13. C-Bus cable types
Excel 500
PANTHER
Recommended for
Europe, inside cabinet
Europe, outside cabinet
US not approved for Europe
US (low-cost) not approved for Europe
Europe, US also possible
US
US not approved for Europe
US (low-cost) not approved for Europe
18