H1008 AUTOMATIC
HUMIDITY CONTROL
OUT
OUT
G
CG
CW
W
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
OPTIONAL SAIL SWITCH IS MONITORING THE OUTPUT AIR
OF THE BLOWER.
3
CURRENT SENSING RELAY IS MONITORING THE FURNACE
BLOWER MOTOR.
Fig. 10. Wiring for R7997, R8184,
RA116 and RA117 oil systems.
SETTINGS
Adjustment
The H1008A,D Automatic Humidity Control with
HumidiCalc+™ Software is designed to provide an optimal
50°F (10°C) dewpoint and automatically adjusts the
humidity level to prevent window frost or condensation.
The H1008D activates a ventilator or dehumidifier to lower
the indoor humidity level when the house dewpoint rises
above 58°F. Outdoor temperature is inferred (without the
need for an outdoor sensor), or measured (with optional
outdoor sensor) by the HumidiCalc+™ Software. Indoor
humidity and temperature information is measured by
sensors located on the back of the control. The frost
factor–set by using the frost factor dial–allows for variables
in furnace oversizing, window insulation and average daily
outdoor temperature. The Automatic Humidity Control with
HumidiCalc+ Software requires an initial adjustment
period. To adjust the frost factor, set the frost factor dial to
10 and use Table 1 to adjust the frost factor—only one
setting at a time—increasing the dial setting for more
humidity, or decreasing the setting if moisture starts to
build up on the inside of your windows. For more precise
humidity adjustments, set the frost factor between the dial
settings. Allow two days for the humidity level to subside
before making further adjustments. Once the frost factor
has been set, no further adjustment is needed.
Table 1. Recommended Frost Factor Adjustment.
Humidity Level
Condensation on
windows
Insufficient humidity Increase the frost factor dial by
SAIL SWITCH
(OPTIONAL)
BLOWER
CURRENT
SENSING
RELAY
EXTERNAL 24 VAC
TRANSFORMER
24 VAC
Recommended Adjustment
Decrease the frost factor dial by
one setting.
one setting.
H1008A,D AUTOMATIC HUMIDITY CONTROL

SYSTEM STATUS

The control has a green indicator light that flashes to
indicate system status. Flash frequency represents system
2
status. See Table 2 for status descriptions.
System Status
Error
3
Standby
Test
L1
(HOT)
Call for
L2
humidification/
1
dehumidification
Off

ERROR STATUS

M13306A
To troubleshoot the system where error status is indicated:
— If an outdoor temperature sensor is not used:
— First check to ensure that the OUT terminals are
properly shorted together.
— Then cycle power to the device. If the control
continues to flash in the error mode, replace the
humidity control.
— If an outdoor temperature sensor is used, disconnect
it, short the OUT terminals together and cycle power.
If the error status remains, replace the humidity
control. If the error status is eliminated, replace the
outdoor temperature sensor.
Control enters the error mode if any sensor reads out-of-
range. See Table 3.
Sensor
Indoor
temperature
RH sensor
Outdoor
temperature
OUT terminals At powerup, if sensor is present and
5
Table 2. System Status.
Flash Frequency
1/8 second on, 1/8 second off
1 second on, 1 second off
4 seconds on, 1 second off.
Steady on with call for heat or fan.
Steady on
Off
Table 3. Error Modes.
Error Indicated When...
Temperature reads below 45°F or
greater than 120°F.
RH reads 0 or 100%.
Temperature reads less than -40°F or
greater than 120°F.
later opens or shorts.
At powerup, if sensor terminals are
jumped and later are open.
69-1185EF—2