51 - Parameters (cont'd)
(2)
If there is no abort output allocated to the alarmed group:
a) The intruder condition is restored.
b) Intruder restore is signalled
The system requires a system reset. The panel cannot be set until this occurs.
NOTE: If reduced resets (51.55.3) is enabled, the alarm will be reset by the user code, if the alarm is
unconfirmed.
If the Abort time is programmed for 000 seconds, then there is no time restriction on when the entry
of a valid code will signal the Abort.
NOTE: 000 seconds equals infinite.
Star
Abort Operation
For entry route deviation, the signalling of an Intruder alarm is immediate, or
For entry timeout conditions, the signalling of an Intruder alarm is immediate:
(1)
The Abort timer starts on signalling of the Intruder.
(2)
If a valid code is entered within the programmed abort time:
a) The intruder condition is restored.
b) Intruder restore is signalled.
c) The system does not require a system reset.
(3)
If a valid code is not entered until the programmed abort time expires:
a) The Abort output/channel is not activated.
b) The Intruder condition is not restored.
c) Intruder restore is not signalled
d) The system does require a system reset.
(4)
If the abort time is programmed for *000 seconds, then there is no time restriction on when
the entry of a valid code will signal the abort.
04 = Exit Time
This parameter determines the time allowed to leave the premises via the exit route before the system sets.
The Exit Time is programmable within the range 0–300 seconds; the default is 120 seconds.
Infinite Exit Time
Assigning a value of 000 seconds sets the Exit Time to infinity; an Exit terminator activation (Final or Push-
set zone) is required to complete the setting of the system. The infinite Exit Time is normally used with a
Push-set zone to terminate the setting and an Entry zone to start the unsetting procedure.
NOTE:
If the system is programmed to Autoset, an Exit Time of 000 causes the system to instantly set
— there is no requirement for a Push-Set zone to be activated.
Setting Multiple Groups
This parameter can be assigned a different value for each group. If more than one is group is being set, the
longest exit time is adopted for all setting groups.
05 = Entry Time
This parameter determines the entry time allowed to users when unsetting the system. The Entry Time is
programmable within the range 0–300 seconds; the default is 120. Assigning a value of 000 seconds sets the
Entry Time to infinity.
This parameter can be assigned a different value for each group.
Galaxy Programming Manual
52