accepts the programming and returns to the previous level; exits from the option.
esc
The banner is displayed whenever any group on the system is unset.
13 = PA Delay
This parameter determines the delay between the activation of a PA Delay or PA Delay Silent zone and the
alarm sounding and signalling a PA via the communicator. The PA Delay is programmable within the range 1–
60 seconds; the default is 60.
This parameter can be assigned a different value for each group.
14 = Key/SW Level
This parameter assigns a code level to zones programmed as Keyswitch. The Keyswitch zone can be used
to reset system, tamper and PA alarms - depending on the reset level assigned to each of these parameters.
The default level is 6 - manager; the programmable range is:
0–7 for the engineer
0–8 for the remote code
15 = System Text
This parameter allows two text strings to be assigned to the system: press 1 to select the System ID or 2 to
select the Panel Location.
1.
System ID — 8 character identification of system;
2.
Panel Location — 16 character message of where control is fitted.
The text is written using the alpha-numeric assembly method:
erases characters;
#
selects upper case, lower case or library;
selects alphabet character/words;
A B
selects alphabet character or words;
000–538
positions selected characters/words;
ent
accepts the programming and returns to the previous level; exits from the option.
esc
16 = Soak Time
This parameter determines the number of days that zones can be soak tested for; the programmable range is 1
– 14 days; the default is 7.
NOTE:
Default settings must be changed before programming in Menu Option 55 – Soak.
51 - Parameters (cont'd)