CPU Fail Trigger Output
1*36
0 = disable
1 = enable
TLM Input on Zone 9
1*37
0 = disable
1 = enable
User Reset of Tamper Alarms Instead
1*38
of Installer Only Reset
0 = disable (ANPI requirement)
1 = enable
User Bypass of Tamper Faults
1*39
Instead of Installer Only Bypass
0 = disable (ANPI requirement)
1 = enable
Maximum Number of Zones that can
1*40
be Bypassed per Partition
Enter 01-15
Enter 00 for no restriction
Bypass/Unbypass Zones when
1*41
Armed
0 = disable
1 = enable
Call Waiting Defeat
1*42
0 = disable
1 = enable
Permanent Keypad Display
1*43
Backlighting (partition-specific)
0 = disable
1 = enable
Keypad Tamper Detect
1*44
0 = disable
1 = enable (ANPI requirement)
Exit Delay Sounding (partition-
1*45
specific)
0 = disable
1 = enable
Auxiliary Output Mode
1*46
0 = ground start output.
1 = smoke detector reset.
2 = keypad sounds at an auxiliary sounder.
3 = AAV module.
FIELD
TITLE and DATA ENTRIES
If enabled, output 2 on J7 to be CPU Fail output, overriding any other
selection for output 2 (CENELEC requirement).
If enabled, the telephone line fault monitor is to be fed into zone 9.
If enabled, allows the user to reset tamper alarms.
If enabled, allows the user to bypass tamper faults.
Select the maximum number of zones that can be bypassed for any armed
period. This cannot be 00 for ANPI compliance).
If enabled, zones can be bypassed and unbypassed while the system is
armed.
If enabled, the system defeats Call Waiting on the first outgoing call attempt to
both the primary and secondary numbers.
NOTE: After the panel's initial call to report the alarm, the panel may attempt
to make an additional call, perhaps for a cancel or a zone restoral. If Call
Waiting is not defeated, an operator at the central station attempting to
contact the premises (to verify whether the alarm is valid) hears the phone
ringing indefinitely and must to dispatch on the call.
DO NOT enable this feature unless Call Waiting is being used.
If enabled, backlighting for the keypad display remains on at all times.
Otherwise the backlighting comes on when a key is pressed.
NOTE: When a key is pressed, display backlighting turns on for all keypads in
that partition.
If enabled, when 21 key depressions are entered, without a valid sequence
(arm, disarm, etc.), the control panel disables all keypads in that partition.
This includes any wireless keypads. After 15 minutes the inhibit is
automatically removed .
If enabled, the system produces slow beeping from the keypads during exit
delay and reverts to rapid beeping during the last 10 seconds of the exit delay.
Select the mode for output 1 on the J7 triggers.
NOTES:
Only one of the options may be active within the system.
Option 2 applies only to the partition enabled in field *15.
EXPLANATION
Section 5 - Data Field Descriptions
5-11