Honeywell CNI4 Operating And Installation Manual page 55

Table of Contents

Advertisement

8 Troubleshooting
Error
Error Description
Codes
185
Server certificate expired
186
CA certificate expired
193
Modem not responding
195
Radio on Initialization Fail??
196
PPP connection fail
197
TCP/IP socket connection fail
200
Modem dial fail
201
BLE Abrupt Connection Failure
202
BLE pairing fail
203
User table checksum error
205
BLE out of bonds
208
SRAM configuration checksum
mismatch
Troubleshooting Recommendations
Send certificates for renewal
Send certificates for renewal
In case of multiple occurrences, replace the hardware.
In case of multiple occurrences, replace the hardware.
Check for correct APN, supercap voltage Item#3014(>3.2),
and Signal Strength
Check PowerSpring and port numbers
Check packet service command, supercap voltage
Item#3014(>3.2), and Signal Strength
Super capacitor voltage is low for bluetooth to connect.
Wait for 1-4hrs for the supercap to charge
Retry pairing from MasterLink app or Switch Off and
switch On Bluetooth on mobile.
In case of multiple occurrences, perform a reset. If problem
still persists, replace the hardware.
Write Item# 3082 = 1 to unpair bonds
In case of multiple occurrences, perform a reset. If problem
still persists, replace the hardware.