Honeywell SiX Series Installation Instructions Manual page 2

Wireless carbon monoxide (co) detector
Hide thumbs Also See for SiX Series:

Advertisement

If the detector is not successfully enrolled during the
6.
enrollment period, the LED turns off and the device
powers down. Pressing and holding the test button, while
powering the detector, will arm the detector to perform a
reset to factory defaults.
The device can also be manually enrolled. See the
Controller's Programming Guide for details.
24-Hour Enrollment Deletion and Default
If the device is enrolled in a panel different than the
intended panel, and you are unable to delete it from the
unintended panel, reset default the device to factory
default setting:
This procedure is available for 24 hours after enrollment
with a panel and the device remains powered (battery
installed).
Remove power from the detector. Press the CO Test
Button. While holding the test button, insert the
batteries. Continue holding the test button for 10
seconds and release. The status LED should start
blinking green rapidly to confirm its deleted enrollment.
4. L'enrôlement est confirmé lorsque la DEL verte est
allumée durant 3 secondes et que le dispositif émet
un pépiement .
5. Appuyez sur GARDER (Enregistrer).
6. Si le dispositif n'est pas enrôlé avec succès durant la
période d'enrôlement, la DEL s'éteint et le dispositif
se met hors tension.
button, while powering the detector, will arm the
detector to perform a reset to factory defaults.
Le dispositif peut également être enrôlé manuellement.
Pour les détails, reportez-vous au Guide de
programmation du contrôleur.
If the device is enrolled in a panel different than the
intended panel, and you are unable to delete it from the
unintended panel, reset default the device to factory
default setting:
This procedure is available for 24 hours after enrollment
with a panel and the device remains powered (battery
installed).
Remove power from the detector. Press the CO Test
Button. While holding the test button, insert the
batteries. Continue holding the test button for 10
seconds and release. The status LED should start
blinking green rapidly to confirm its deleted enrollment.