The unit is shipped in a calibrated and fully functional tested condition. Since the
unit is factory-calibrated using proprietary firmware algorithms, no internal unit
adjustments are necessary.
This unit contains no internal adjustments, so no preventative or scheduled
maintenance is required.
No cleaning or decontamination procedures are required for this instrument.

9.0 LITHIUM BATTERY REPLACEMENT

The E-Mon Class 3400 Meter has a Lithium Battery Cell, which is used to retain
the contents of SRAM and the RTC during power outages. The battery has a life
expectancy of greater than 5 years.
Nominal Working Voltage
Nominal Current Capacity
Cell Chemical
Operating Temperature Range -30 to +60 Degrees Celsius
Manufacturer
Manufacturer's Part Number
Fig. 20. Battery Specifications at 25 Degrees Celsius.
WARNING
Only replace battery with Panasonic part number CR2032 only. Use of
another battery may present a risk or explosion. See owners manual for
safety instructions. Internal circuit card components are extremely
sensitive to electrostatic discharge. Be careful not to touch internal
circuitry prior to discharging any static buildup on your person. To
discharge yourself, touch a grounded metal object such as conduit or a
metal enclosure exterior.
The battery cell is mounted in a coin cell on the upper right side of the
main power board. Replace the battery if the low battery warning is on
display.
3 Vdc Output
225 mAHr
Manganese Dioxide Lithium
Panasonic
CR2032
35