Installing the Profibus Cable

When laying the Profibus cable, note the following:
Do not lay signal and bus cables parallel to power cables or in bundles with
power cables.
Lay Profibus cables and cables with direct voltages > 60V and alternating
voltages > 25V in separate bundles or cable channels.
Always lay signal cables in one channel, following the shortest route.
Avoid extending the Profibus cables with connectors.
Do not lay Profibus cables in bundles with telephone lines and cables leading
to potentially explosive areas.
Avoid branch lines.
Refer to the following cable specifications, connector description, and instructions
for cable shielding and bus termination.

Profibus Cable Specifications

The proper cable for a Profibus network is a shielded twisted pair cable. Profibus
cable is available from Siemens parts distributors and sold as "Profibus Network
Cable". The twisted pair cable consists of a Green and a Red wire. Below are
some of the cable characteristics of Profibus cable.
For data rates up to 500 kbits/second, follow the stub recommendations in the
Profibus technical standard. At 1500 kbits/second the overall drop capacity should
be less than 0.2nF. Maximum length of the stub at 1500 kbits/second is 6.6
meters.
4-14
VersaPoint™ I/O System Profibus-DP NIU User's Manual – August 2005
Profibus Network Cable
Profibus 9-pin Connector
Impedance
Capacity
Resistance
Wire Gauge
Conductor Area
Siemens part # 6XV1-830
Siemens part # 6ES7972
135 to 165 Ohms (3 to 20 MHz)
< 30 pF per meter
< 110 Ohms per Kilometer
> 0.64 mm (0.025 inch)
> 0.34 mm2 (AWG 22)