GSD File for NIU Version IC220PBI001
Use this file for NIU version module IC220PBI001.
This file should also be used for module IC220PBI002 when DIP switch 8 is in
the Off position. See chapter 4 for more information about setting this switch.
;***************************************************
; GSD-File for VersaPoint PROFIBUS-DP NETWORK
INTERFACE UNIT
: GE Intelligent Platforms North America
; Manufacturer
; Article-No.
: IC220PBI001-AA
; Hardware-Release : 02
; Firmware-Release : A (41 hex)
; GSD-Revision
: 1.03
; Date
: 31.01.2003
;***************************************************
;****************** History **************************
; Revision
Change
; 1.00
-initial product release
; 1.01
-corrected entry for 2ch analog output module
; 1.02
-new modules added
; 1.03
-new modules added, module discription changed
;***************************************************
#Profibus_DP
GSD_REVISION = 2
format
Vendor_Name = "GE "
Model_Name = "VersaPoint Profibus NIU" ; device name
Revision = "V2.0"
Ident_Number = 0x05B9
Slave_Family = 3
Protocol_Ident = 0
Station_Type = 0
FMS_supp = 0
Hardware_Release = "V2.0"
Software_Release = "A"
Bitmap_Device = "GEF05B9N"
state
;Bitmap_DIAG = "GEF05B9D"
state
9.6_supp = 1
19.2_supp = 1
93.75_supp = 1
187.5_supp = 1
GFK-1911B
; version ID of the GSD file
; manufacturer name
; device revision
; product ID
; device family class
; protocol ID of the device
; device type
; no DP/FMS mixed device
; hardware revision
; software revision
; device bitmap - normal
; device bitmap - diagnostic
; supported baudrates
Appendix D The NIU GSD File
500_supp = 1
1.5M_supp = 1
3M_supp = 1
6M_supp = 1
12M_supp = 1
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 550
MaxTsdr_12M = 850
Redundancy = 0
; no redundancy
Repeater_Ctrl_Sig = 2
TTL level
;********************************************
;********* slavespecific data *****************
;********************************************
Freeze_Mode_supp = 1
mode
Sync_Mode_supp = 1
Auto_Baud_supp = 1
recognition
Min_Slave_Intervall = 1
User_Prm_Data_Len = 0
Max_Diag_Data_Len = 16
data
;************************************************
;********* modular device ************************
;************************************************
Modular_Station = 1
Max_Module = 64
D
; device response times
; connector signal CNTR-P:
; device supports freeze
; device supports sync mode
; automatic baud rate
; min cycle time 0.1ms
; length of User_Prm_Data
; max length of diagnostic
; modular device
; max 64 modules
D-21