Commissioning
6.7 Commissioning: Basic procedure
This dialog box provides the following setting options for STO (Basic Functions):
● "F-DI input filter"
This is where you set the debounce time for the fail-safe digital inputs used to control
STO/SBC/SS1 (p9651).
● "Monitoring for simultaneous operation"
This is where you set the tolerance time for the switchover of the safety-related inputs on
the Control Unit (p9650).
● "STOP F -> STOP A delay time"
This is where you set the transition time from STOP F to STOP A on the Control Unit
(p9658).
● "Forced dormant error detection (test stop) of the shutdown paths"
This is where you set the time interval for performing the forced dormant error detection
and test of the safety shutdown paths (p9659).
244
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Safety Integrated