B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 36 of 64)
ADDR
REGISTER NAME
81C1
Reserved Register T2
81C2
Reserved Register T3
81C4
Reserved Register T4
81C6
Reserved Register T5
B
81C8
Reserved Register T6
81CA
Reserved Register T7
81CC
Reserved Register T8
EGD Fast Production Status (Read Only Non-Volatile and Read Only)
83E0
EGD Fast Producer Exchange 1 Signature
83E1
EGD Fast Producer Exchange 1 Configuration
Time
83E3
EGD Fast Producer Exchange 1 Size
EGD Slow Production Status (Read Only Non-Volatile and Read Only) (2 modules)
83F0
EGD Slow Producer Exchange 1 Signature
83F1
EGD Slow Producer Exchange 1 Configuration
Time
83F3
EGD Slow Producer Exchange 1 Size
83F4
...Repeated for EGD Slow Producer Exchange 2
EGD Fast Production (Read/Write Setting)
8400
EGD Fast Producer Exchange 1 Function
8401
EGD Fast Producer Exchange 1 Destination
8403
EGD Fast Producer Exchange 1 Data Rate
8404
EGD Fast Producer Exchange 1 Data Item 1 (20
items)
8418
Reserved (80 items)
EGD Slow Production (Read/Write Setting) (2 modules)
8468
EGD Slow Producer Exchange 1 Function
8469
EGD Fast Producer Exchange 1 Destination
846B
EGD Slow Producer Exchange 1 Data Rate
846C
EGD Slow Producer Exchange 1 Data Item 1 (50
items)
849E
Reserved (50 items)
84D0
...Repeated for EGD Exchange 2
Breaker Failure (Read/Write Grouped Setting) (6 modules)
8600
Breaker Failure 1 Function
8601
Breaker Failure 1 Mode
8602
Breaker Failure 1 Source
8603
Breaker Failure 1 Amp Supervision
8604
Breaker Failure 1 Use Seal-In
8605
Breaker Failure 1 Three Pole Initiate
8607
Breaker Failure 1 Block
8609
Breaker Failure 1 Phase Amp Supv Pickup
860A
Breaker Failure 1 Neutral Amp Supv Pickup
860B
Breaker Failure 1 Use Timer 1
860C
Breaker Failure 1 Timer 1 Pickup
860D
Breaker Failure 1 Use Timer 2
860E
Breaker Failure 1 Timer 2 Pickup
860F
Breaker Failure 1 Use Timer 3
8610
Breaker Failure 1 Timer 3 Pickup
8611
Breaker Failure 1 Breaker Status 1 Phase A/3P
B-44
RANGE
-55 to 125
-2147483647 to
2147483647
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65535
0 to 4294967295
0 to 65535
0 to 65535
0 to 4294967295
0 to 65535
0 to 1
0 to 4294967295
50 to 1000
0 to 65535
---
0 to 1
0 to 4294967295
500 to 1000
0 to 65535
---
0 to 1
0 to 1
0 to 5
0 to 1
0 to 1
0 to 4294967295
0 to 4294967295
0.001 to 30
0.001 to 30
0 to 1
0 to 65.535
0 to 1
0 to 65.535
0 to 1
0 to 65.535
0 to 4294967295
B30 Bus Differential System
APPENDIX B
UNITS
STEP
FORMAT
C
1
F002
---
1
F004
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F001
---
---
F003
---
1
F001
---
1
F001
---
---
F003
---
1
F001
---
1
F102
---
1
F003
ms
50
F001
---
1
F001
---
---
F001
---
1
F102
---
1
F003
ms
50
F001
---
1
F001
---
---
F001
---
1
F102
---
1
F157
---
1
F167
---
1
F126
---
1
F126
---
1
F300
---
1
F300
pu
0.001
F001
pu
0.001
F001
---
1
F126
s
0.001
F001
---
1
F126
s
0.001
F001
---
1
F126
s
0.001
F001
---
1
F300
DEFAULT
125
0
0
0
0
0
0
0
0
0
0
0
0
0 (Disabled)
0
1000
0
0
0 (Disabled)
0
1000
0
0
0 (Disabled)
0 (3-Pole)
0 (SRC 1)
1 (Yes)
1 (Yes)
0
0
1050
1050
1 (Yes)
0
1 (Yes)
0
1 (Yes)
0
0
GE Multilin