GE B30 Instruction Manual page 471

Ur series bus differential system protection relay
Hide thumbs Also See for B30:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 23 of 64)
ADDR
REGISTER NAME
4163
MMS Available TCP/IP Connections
4164
PMU Available TCP/IP Connections
Simple Network Time Protocol (Read/Write Setting)
4168
Simple Network Time Protocol (SNTP) Function
4169
Simple Network Time Protocol (SNTP) Server IP
Address
416B
Simple Network Time Protocol (SNTP) UDP Port
Number
Clock (Read/Write Setting)
419F
Synchronizing Source
Clock (Read/Write Command)
41A0
Real Time Clock Set Time
Clock (Read/Write Setting)
41A2
SR Date Format
41A4
SR Time Format
41A6
IRIG-B Signal Type
41A7
Clock Events Enable / Disable
41A8
Time Zone Offset from UTC
41A9
Daylight Savings Time (DST) Function
41AA
Daylight Savings Time (DST) Start Month
41AB
Daylight Savings Time (DST) Start Day
41AC
Daylight Savings Time (DST) Start Day Instance
41AD
Daylight Savings Time (DST) Start Hour
41AE
Daylight Savings Time (DST) Stop Month
41AF
Daylight Savings Time (DST) Stop Day
41B0
Daylight Savings Time (DST) Stop Day Instance
41B1
Daylight Savings Time (DST) Stop Hour
Oscillography (Read/Write Setting)
41C0
Oscillography Number of Records
41C1
Oscillography Trigger Mode
41C2
Oscillography Trigger Position
41C3
Oscillography Trigger Source
41C5
Oscillography AC Input Waveforms
41D0
Oscillography Analog Channel
4200
Oscillography Digital Channel
Trip and Alarm LEDs (Read/Write Setting)
42B0
Trip LED Input FlexLogic Operand
42B2
Alarm LED Input FlexLogic Operand
User Programmable LEDs (Read/Write Setting) (48 modules)
42C0
FlexLogic Operand to Activate LED
42C2
User LED type (latched or self-resetting)
42C3
...Repeated for User-Programmable LED 2
42C6
...Repeated for User-Programmable LED 3
42C9
...Repeated for User-Programmable LED 4
42CC
...Repeated for User-Programmable LED 5
42CF
...Repeated for User-Programmable LED 6
42D2
...Repeated for User-Programmable LED 7
42D5
...Repeated for User-Programmable LED 8
GE Multilin
RANGE
0 to 5
0 to 4
0 to 1
0 to 4294967295
1 to 65535
0 to 3
0 to 235959
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
–24 to 24
0 to 1
0 to 11
0 to 6
0 to 4
0 to 23
0 to 11
0 to 6
0 to 4
0 to 23
3 to 64
0 to 1
0 to 100
0 to 4294967295
0 to 4
n
0 to 65535
(16 items)
n
0 to 4294967295
(63 items)
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
B30 Bus Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F001
---
1
F001
---
1
F102
---
1
F003
---
1
F001
---
1
F623
---
1
F050
---
1
F051
---
1
F052
---
1
F114
---
1
F102
hours
0.5
F002
---
1
F102
---
1
F237
---
1
F238
---
1
F239
---
1
F001
---
1
F237
---
1
F238
---
1
F239
---
1
F001
---
1
F001
---
1
F118
%
1
F001
---
1
F300
---
1
F183
---
1
F600
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F127
DEFAULT
5
4
0 (Disabled)
B
0
123
0 (None)
0
0
0
0 (None)
0 (Disabled)
0
0 (Disabled)
0 (January)
0 (Sunday)
0 (First)
2
0 (January)
0 (Sunday)
0 (First)
2
15
0 (Auto.
Overwrite)
50
0
2 (16
samples/
cycle)
0
0
0
0
0
1 (Self-Reset)
B-31

Advertisement

Table of Contents
loading

Table of Contents