7.1 COMMANDS
PATH: COMMANDS
COMMANDS
CLEAR RECORDS
This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a com-
mand setting to "Yes" and pressing the ENTER key. After clearing data, the command setting automatically reverts to "No".
PATH: COMMANDS
COMMANDS
SET DATE AND TIME
The date and time can be entered on the faceplate keypad. The time setting is based on the 24-hour clock. The complete
date, as a minimum, must be entered to allow execution of this command. The new time and date take effect when the
ENTER key is pressed.
When the relay is synchronizing to an external time source such as PTP, IRIG-B, or SNTP, the manually entered time is
over-written.
7
The timescale of the entered time is local time, including daylight savings time where and when applicable.
PATH: COMMANDS
COMMANDS
RELAY MAINTENANCE
7-2
CLEAR RECORDS
CLEAR USER FAULT
REPORTS? No
CLEAR EVENT RECORDS?
No
CLEAR OSCILLOGRAPHY?
No
CLEAR UNAUTHORIZED
ACCESS? No
CLEAR DIRECT I/O
COUNTERS? No
CLEAR TELEPROTECT
COUNTERS? No
CLEAR ALL RELAY
RECORDS? No
SET DATE AND TIME
SET DATE AND TIME:
2000/01/14 13:47:03
RELAY MAINTENANCE
PERFORM LAMPTEST?
No
UPDATE ORDER CODE?
No
REBOOT RELAY?
No
SERVICE COMMAND:
0
SAVE VOLATILE DATA?
No
B30 Bus Differential System
7 COMMANDS AND TARGETS
7.1.3 CLEAR RECORDS
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes. Valid only for units with Direct Input/
Output module.
Range: No, Yes
Range: No, Yes
7.1.4 SET DATE AND TIME
(YYYY/MM/DD HH:MM:SS)
7.1.5 RELAY MAINTENANCE
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: 0, 101
Range: No, Yes
GE Multilin