GE b30 Instruction Manual
GE b30 Instruction Manual

GE b30 Instruction Manual

Bus differential system
Hide thumbs Also See for b30:
Table of Contents

Advertisement

GE
Grid Solutions
B30
Bus Differential System
Instruction Manual
Product version: 7.41x
GE publication code: 1601-0109-AE1 (GEK-130972)
E83849
LISTED
IND.CONT. EQ.
52TL
1601-0109-AE1

Advertisement

Table of Contents
loading

Summary of Contents for GE b30

  • Page 1 Grid Solutions Bus Differential System Instruction Manual Product version: 7.41x GE publication code: 1601-0109-AE1 (GEK-130972) E83849 LISTED IND.CONT. EQ. 52TL 1601-0109-AE1...
  • Page 2 The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The content of this manual is for informational use only and is subject to change without notice.
  • Page 3: Table Of Contents

    Environmental........................2-31 2.5.12 Type tests ..........................2-32 2.5.13 Production tests ........................2-32 2.5.14 Approvals ..........................2-33 2.5.15 Maintenance.........................2-33 3 INSTALLATION Unpack and inspect..................3-1 Panel cutouts....................3-2 3.2.1 Horizontal units ........................3-2 3.2.2 Vertical units ........................... 3-3 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 4 3.7.5 Automatic discovery of UR devices................3-56 Connect to the B30 ..................3-57 3.8.1 Connect to the B30 in EnerVista ................. 3-57 3.8.2 Use Quick Connect via the front panel RS232 port..........3-58 3.8.3 Use Quick Connect via a rear Ethernet port............3-59 Set up CyberSentry and change default password .........3-59...
  • Page 5 System setup ....................5-126 5.5.1 AC inputs ..........................5-126 5.5.2 Power system........................5-127 5.5.3 Signal sources........................5-128 5.5.4 Breakers..........................5-130 5.5.5 Disconnect switches ......................5-135 5.5.6 FlexCurves...........................5-138 5.5.7 Bus............................5-145 FlexLogic......................5-146 5.6.1 FlexLogic operands ......................5-146 5.6.2 FlexLogic rules ........................5-156 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 6 6.3.3 RxGOOSE boolean inputs ....................6-4 6.3.4 RxGOOSE DPS inputs......................6-4 6.3.5 Teleprotection inputs ......................6-5 6.3.6 Contact outputs........................6-5 6.3.7 Virtual outputs........................6-5 6.3.8 RxGOOSE status........................6-6 6.3.9 RxGOOSE statistics .......................6-6 6.3.10 Digital counters........................6-6 6.3.11 Selector switches ........................6-7 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 7 High breakpoint ........................8-6 8.3.3 Low breakpoint........................8-6 Slopes and high set threshold............... 8-7 8.4.1 Description ..........................8-7 8.4.2 External faults on C-1......................8-7 8.4.3 External faults on C-2......................8-9 8.4.4 External faults on C-3......................8-9 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 8 Replace battery for SH/SL power supply ............. 10-14 10.9.2 Dispose of battery ......................10-15 10.10 Uninstall and clear files and data.............10-18 10.11 Repairs......................10-19 10.12 Storage ......................10-19 10.13 Disposal ......................10-20 A FLEXANALOG A.1 FlexAnalog items .....................A-1 OPERANDS viii B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 9 TABLE OF CONTENTS B RADIUS SERVER B.1 RADIUS server configuration ................. B-1 CONFIGURATION C COMMAND LINE C.1 Command line interface .................C-1 INTERFACE D MISCELLANEOUS D.1 Warranty ......................D-1 D.2 Revision history ....................D-1 ABBREVIATIONS INDEX B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 10 TABLE OF CONTENTS B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 11: Introduction

    Ensure that the control power applied to the device, the AC current, and voltage input match the ratings specified on the relay nameplate. Do not apply current or voltage in excess of the specified limits. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 12: For Further Assistance

    Fax: +1 905 927 5098 Worldwide e-mail: multilin.tech@ge.com Europe e-mail: multilin.tech.euro@ge.com Website: http://www.gegridsolutions.com/multilin When contacting GE by e-mail, optionally include a device information file, which is generated in the EnerVista software by clicking the Service Report button. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 13 CHAPTER 1: INTRODUCTION FOR FURTHER ASSISTANCE Figure 1-1: Generate service report B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 14 FOR FURTHER ASSISTANCE CHAPTER 1: INTRODUCTION B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 15: Product Description

    2.1.1 Overview The B30 Bus Differential System is part of the Universal Relay (UR) series of products. It is a microprocessor-based relay that provides protection and metering for a busbar with up to six feeders. Protection is provided by a low impedance percent differential element with features that make it immune to current transformer (CT) saturation.
  • Page 16 Modbus/TCP, TFTP, and PTP (according to IEEE Std. 1588-2008 or IEC 61588), and it allows access to the relay via any standard web browser (B30 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet port. The Ethernet port also supports the Parallel Redundancy Protocol (PRP) of IEC 62439-3 (clause 4, 2012) when purchased as an option.
  • Page 17 Table 2-2: Other device functions Function Function Function Breaker arcing current (I DNP 3.0 or IEC 60870-5-104 protocol Selector switch Breaker control Ethernet Global Data protocol Setting groups (6) Breaker flashover Event recorder Time synchronization over SNTP B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 18: Security

    The B30 supports password entry from a local or remote connection. Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry and the through the faceplate RS232 port. Remote access is defined as any access to settings or commands via any rear communications port.
  • Page 19 Default role except for menu writing CyberSentry Security Device Definition Settings |---------- Product Setup |--------------- Security (CyberSentry) |--------------- Supervisory See table notes See table notes |--------------- Display Properties |--------------- Clear Relay Records (settings) B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 20 |--------------- Direct Integers |---------- Transducer I/O |---------- Testing |---------- Front Panel Labels Designer |---------- Protection Summary Commands |---------- Virtual Inputs |---------- Clear Records |---------- Set Date and Time User Displays Targets Actual Values B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 21 RADIUS server when one is provided. If a RADIUS server is provided, but is unreachable over the network, server authentication requests are denied. In this situation, use local UR accounts to gain access to the UR system. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 22: Order Codes

    The order code is on the product label and indicates the product options applicable. The B30 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit. It consists of the following modules: power supply, CPU, CT/VT, contact input and output, transducer input and output, and inter-relay communications.
  • Page 23 Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED 820 nm, multimode, LED, 2 Channels 1300 nm, multimode, LED, 2 Channels 1300 nm, single-mode, ELED, 2 Channels 1300 nm, single-mode, Laser, 2 Channels B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 24 7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel 7W RS422, 2 Channels Table 2-5: B30 order codes for reduced-size vertical units - * * * - F ** - H ** - L **...
  • Page 25: Order Codes With Process Bus Modules

    G.703, 2 Channels RS422, 1 Channel 7W RS422, 2 Channels 2.3.2 Order codes with process bus modules Table 2-6: B30 order codes for horizontal units with process bus - * ** - * * * - F ** - H **...
  • Page 26 IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1300 nm, single-mode, Laser Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1550 nm, single-mode, Laser 2-12 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 27 G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel 7W RS422, 2 Channels Table 2-7: B30 order codes for reduced-size vertical units with process bus - * ** - * * * - F ** - H ** - L **...
  • Page 28: Replacement Modules

    Replacement modules can be ordered separately. When ordering a replacement CPU module or faceplate, provide the serial number of your existing unit. Not all replacement modules apply to the B30 relay. The modules specified in the order codes for the B30 are available as replacement modules for the B30.
  • Page 29 4 DCmA inputs, 4 DCmA outputs (only one 5A module is allowed) 8 RTD inputs 4 RTD inputs, 4 DCmA outputs (only one 5D module is allowed) 4 DCmA inputs, 4 RTD inputs 8 DCmA inputs B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 2-15...
  • Page 30 4 DCmA inputs, 4 DCmA outputs (only one 5A module is allowed) 8 RTD inputs 4 RTD inputs, 4 DCmA outputs (only one 5D module is allowed) 4 DCmA inputs, 4 RTD inputs 8 DCmA inputs 2-16 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 31: Signal Processing

    The UR samples its AC signals at 64 samples per cycle, that is, at 3840 Hz in 60 Hz systems, and 3200 Hz in 50 Hz systems. The sampling rate is dynamically adjusted to the actual system frequency by an accurate and fast frequency tracking system. The A/D converter has the following ranges of AC signals: B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 2-17...
  • Page 32 Measured analog values and binary signals can be captured in COMTRADE format with sampling rates from 8 to 64 samples per power cycle. Analog values can be captured with Data Logger, allowing much slower rates extended over long period of time. 2-18 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 33: Specifications

    > 2.0 × CT: ±1.5% of reading > 2.0 × CT rating Curve shapes: IEEE Moderately/Very/Extremely Inverse; IEC (and BS) A/B/C and Short Inverse; GE IAC Inverse, Short/Very/ Extremely Inverse; I t; FlexCurves™ (programmable); Definite Time (0.01 s base curve) Curve multiplier: Time Dial = 0.00 to 600.00 in steps of 0.01...
  • Page 34 Curve timing accuracy at >1.1 pickup: ±3.5% of operate time or ±1 cycle (whichever is greater) from pickup to operate Operate time: <30 ms at 1.10 pickup at 60 Hz AUXILIARY OVERVOLTAGE Pickup level: 0.004 to 3.000 pu in steps of 0.001 Dropout level: 97 to 98% of pickup 2-20 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 35 I / (k × I ) > 1.1 TRIP BUS (TRIP WITHOUT FLEXLOGIC) Number of elements: Number of inputs: Operate time: <2 ms at 60 Hz Timer accuracy: ±3% or 10 ms, whichever is greater B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 2-21...
  • Page 36: User-Programmable Elements

    LEDs on, one LED at a time off for 1 s USER-DEFINABLE DISPLAYS Number of displays: Lines of display: 2 × 20 alphanumeric characters Parameters: up to 5, any Modbus register addresses Invoking and scrolling: keypad, or any user-programmable condition, including pushbuttons 2-22 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 37: Monitoring

    DATA LOGGER Number of channels: 1 to 16 Parameters: any available analog actual value Sampling rate: 15 to 3600000 ms in steps of 1 Trigger: any FlexLogic operand Mode: continuous or triggered B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 2-23...
  • Page 38: Metering

    ±0.02 Hz (when current signal is used for frequency measurement) DEMAND Measurements: Phases A, B, and C present and maximum measured currents 3-Phase Power (P, Q, and S) present and maximum measured currents Accuracy: ±2.0% 2-24 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 39: Inputs

    0 to –1, 0 to +1, –1 to +1, 0 to 5, 0 to 10, 0 to 20, 4 to 20 (programmable) 379 Ω ±10% Input impedance: Conversion range: –1 to + 20 mA DC Accuracy: ±0.2% of full scale Type: Passive B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 2-25...
  • Page 40: Power Supply

    100 to 240 V at 50/60 Hz Minimum AC voltage: 88 V at 25 to 100 Hz Maximum AC voltage: 265 V at 25 to 100 Hz Voltage loss hold-up: 200 ms duration at maximum load 2-26 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 41: Outputs

    1 to 2.5 mA FORM-A CURRENT MONITOR Threshold current: approx. 80 to 100 mA FORM-C AND CRITICAL FAILURE RELAY Make and carry for 0.2 s: 30 A as per ANSI C37.90 Carry continuous: B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 2-27...
  • Page 42 1.6 A at L/R = 20 ms 0.8 A L/R = 40 ms CONTROL POWER EXTERNAL OUTPUT (FOR DRY CONTACT INPUT) Capacity: 100 mA DC at 48 V DC Isolation: ±300 Vpk DIRECT OUTPUTS Output points: 2-28 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 43: Communication Protocols

    SIMPLE NETWORK TIME PROTOCOL (SNTP) Clock synchronization error: <10 ms (typical) PRECISION TIME PROTOCOL (PTP) PTP IEEE Std 1588 2008 (version 2) Power Profile (PP) per IEEE Standard PC37.238TM2011 Slave-only ordinary clock Peer delay measurement mechanism B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 2-29...
  • Page 44: Inter-Relay Communications

    At extreme temperatures these values deviate based on component tolerance. On average, the output power decreases as the temperature is increased by a factor of 1 dB / 5 °C. 2-30 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 45: Cybersentry Security

    95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6 days) OTHER Altitude: 2000 m (maximum) Pollution degree: Overvoltage category: Ingress protection: IP20 front, IP10 back Noise: 0 dB B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 2-31...
  • Page 46: Type Tests

    Insulation: class 1, Pollution degree: 2, Over voltage cat II 1 Not tested by third party. 2.5.13 Production tests THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. 2-32 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 47: Approvals

    Normally, cleaning is not required. When dust has accumulated on the faceplate display, wipe with a dry cloth. To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 2-33...
  • Page 48 SPECIFICATIONS CHAPTER 2: PRODUCT DESCRIPTION 2-34 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 49: Installation

    For any issues, contact GE Grid Solutions as outlined in the For Further Assistance section in chapter 1. Check that you have the latest copy of the B30 Instruction Manual and the UR Family Communications Guide, for the applicable firmware version, at http://gegridsolutions.com/multilin/manuals/index.htm...
  • Page 50: Panel Cutouts

    Maintenance > Change Front Panel. 3.2.1 Horizontal units The B30 is available as a 19-inch rack horizontal mount unit with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 51: Vertical Units

    3.2.2 Vertical units The B30 is available as a reduced size (¾) vertical mount unit, with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 52 PANEL CUTOUTS CHAPTER 3: INSTALLATION Figure 3-4: Vertical dimensions (enhanced panel) B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 53 CHAPTER 3: INSTALLATION PANEL CUTOUTS Figure 3-5: Vertical and mounting dimensions (standard panel) For side-mounting B30 devices with the enhanced front panel, see the following documents available on the UR DVD and the GE Grid Solutions website: • GEK-113180 — UR-Series UR-V Side-Mounting Front Panel Assembly Instructions •...
  • Page 54 PANEL CUTOUTS CHAPTER 3: INSTALLATION For side-mounting B30 devices with the standard front panel, use the following figures. Figure 3-6: Vertical side-mounting installation (standard panel) B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 55 CHAPTER 3: INSTALLATION PANEL CUTOUTS Figure 3-7: Vertical side-mounting rear dimensions (standard panel) B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 56: Rear Terminal Layout

    (nearest to CPU module), indicated by an arrow marker on the terminal block. The figure shows an example of rear terminal assignments. Figure 3-8: Example of modules in F and H slots B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 57: Wiring

    CHAPTER 3: INSTALLATION WIRING 3.3 Wiring 3.3.1 Typical wiring Figure 3-9: Typical wiring diagram (T module shown for CPU) B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 58: Dielectric Strength

    The power supply module can be ordered for two possible voltage ranges, and the B30 can be ordered with or without a redundant power supply module option. Each range has a dedicated input connection for proper operation. The ranges are as follows (see the Specifications section of chapter 2 for details): •...
  • Page 59: Ct/Vt Modules

    CT input of standard CT/VT modules. However, the phase CT inputs and phase VT inputs are the same as those of regular CT/VT modules. These modules have enhanced diagnostics that can automatically detect CT/VT hardware failure and take the relay out of service. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 3-11...
  • Page 60 UR models. Substitute the tilde “~” symbol with the slot position of the module in the following figure. Figure 3-12: CT/VT module wiring 3-12 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 61: Process Bus Modules

    3.3.5 Process bus modules The B30 can be ordered with a process bus interface module. The module interfaces with the HardFiber Process Bus System, or HardFiber Brick, allowing bidirectional IEC 61850 fiber optic communications with up to eight HardFiber Bricks.
  • Page 62 Where a tilde “~” symbol appears, substitute the slot position of the module. Where a number sign “#” appears, substitute the contact number. 3-14 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 63 ~6a, ~6c 2 Inputs Fast Form-C ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs Fast Form-C ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 3-15...
  • Page 64 ~5a, ~5c 2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used 3-16 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 65 CHAPTER 3: INSTALLATION WIRING Figure 3-14: Contact input and output module wiring (Sheet 1 of 2) B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 3-17...
  • Page 66 CHAPTER 3: INSTALLATION Figure 3-15: Contact input and output module wiring (Sheet 2 of 2) For proper functionality, observe the polarity shown in the figures for all contact input and output connections. 3-18 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 67 The contact inputs with auto-burnish create a high current impulse when the threshold is reached to burn off this oxidation layer as a maintenance to the contacts. Afterwards the contact input current is reduced to a steady-state current. The impulse has a five-second delay after a contact input changes state. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 3-19...
  • Page 68: Transducer Inputs And Outputs

    Transducer output modules provide DC current outputs in several standard DCmA ranges. Software is provided to configure virtually any analog quantity used in the relay to drive the analog outputs. 3-20 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 69 (5A, 5C, 5D, 5E, and 5F) and channel arrangements that can be ordered for the relay. Where a tilde “~” symbol appears, substitute the slot position of the module. Figure 3-19: Transducer input/output module wiring The following figure show how to connect RTDs. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 3-21...
  • Page 70: Rs232 Faceplate Port

    EnerVista UR Setup software provided with the relay. Cabling for the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors. The baud rate for this port can be set, with a default of 115200 bps. 3-22 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 71: Cpu Communication Ports

    Figure 3-21: RS232 faceplate port connection 3.3.9 CPU communication ports 3.3.9.1 Overview In addition to the faceplate RS232 port, there is a rear RS485 communication port. The CPU modules do not require a surge ground connection. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 3-23...
  • Page 72 This common voltage is implied to be a power supply common. Some systems allow the shield (drain wire) to be used as common wire and to connect directly to the B30 COM terminal (#3); others function correctly only if the common wire is connected to the B30 COM terminal, but insulated from the shield.
  • Page 73: Irig-B

    IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices. The IRIG-B code allows time accuracies of up to 100 ns. Using the IRIG-B input, the B30 operates an internal oscillator with 1 µs resolution and accuracy.
  • Page 74: Direct Input And Output Communications

    UR-series relays with the following connections: UR1-Tx to UR2-Rx, UR2-Tx to UR3-Rx, UR3-Tx to UR4-Rx, and UR4-Tx to UR1-Rx. A maximum of 16 URs can be connected in a single ring. 3-26 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 75 UR1-Tx1 to UR2-Rx1, UR2-Tx1 to UR3-Rx1, UR3-Tx1 to UR4-Rx1, and UR4-Tx1 to UR1-Rx1 for the first ring; and UR1-Tx2 to UR4-Rx2, UR4-Tx2 to UR3-Rx2, UR3-Tx2 to UR2-Rx2, and UR2-Tx2 to UR1-Rx2 for the second ring. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 3-27...
  • Page 76 Those that apply depend on options purchased. The options are outlined in the Inter-Relay Communications section of the Order Code tables in Chapter 2. All of the fiber modules use ST type connectors. 3-28 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 77: Fiber: Led And Eled Transmitters

    The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser modules. Figure 3-30: 7x Laser fiber modules The following figure shows configuration for the 2I and 2J fiber-laser modules. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 3-29...
  • Page 78: Interface

    The following figure shows the typical pin interconnection between two G.703 interfaces. For the actual physical arrangement of these pins, see the Rear Terminal Layout section earlier in this chapter. All pin interconnections are to be maintained for a connection to a multiplexer. 3-30 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 79 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is inserted fully. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 3-31...
  • Page 80 (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 = OFF). The switch settings for the internal and loop timing modes are shown. 3-32 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 81 One source lies on the G.703 line side of the interface while the other lies on the differential Manchester side of the interface. Figure 3-37: G.703 dual loopback mode B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 3-33...
  • Page 82: Rs422 Interface

    (data module 1) connects to the clock inputs of the UR RS422 interface in the usual way. In 3-34 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 83 Figure 3-40: Timing configuration for RS422 two-channel, three-terminal application Data module 1 provides timing to the B30 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been omitted in the figure because they vary by manufacturer.
  • Page 84: Rs422 And Fiber Interface

    For the direct fiber channel, address power budget issues properly. When using a laser interface, attenuators can be necessary to ensure that you do not exceed maximum optical input power to the receiver. Figure 3-42: RS422 and fiber interface connection 3-36 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 85: And Fiber Interface

    Connection — as per all fiber optic connections, a Tx to Rx connection is required The UR-series C37.94 communication module can be connected directly to any compliant digital multiplexer that supports the IEEE C37.94 standard. The figure shows the concept. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 3-37...
  • Page 86 5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of B30 communication for two and three terminal applications.
  • Page 87 When the clips have locked into position, the module is inserted fully. Figure 3-47: IEEE C37.94 timing selection switch setting Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the following figure. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 3-39...
  • Page 88: C37.94Sm Interface

    Fiber optic cable length — Up to 11.4 km • Fiber optic connector — Type ST • Wavelength — 1300 ±40 nm • Connection — As per all fiber optic connections, a Tx to Rx connection is required 3-40 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 89 5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of B30 communication for two and three terminal applications.
  • Page 90 When the clips have locked into position, the module is inserted fully. Figure 3-50: C37.94SM timing selection switch setting Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the following figure. 3-42 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 91: Activate Relay

    Press the right arrow until the message displays. MESSAGE SECURITY Press the down arrow until the message displays. MESSAGE INSTALLATION Press the right arrow until the Not Programmed message displays. MESSAGE RELAY SETTINGS: B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 3-43...
  • Page 92: Install Software

    To communicate via the faceplate RS232 port, use a standard straight-through serial cable. Connect the DB-9 male end to the relay and the DB-9 or DB-25 female end to the computer COM2 port as described in the CPU Communication Ports section earlier in this chapter. 3-44 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 93: System Requirements

    This device (catalog number F485) connects to the computer using a straight-through serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the B30 rear communications port. The converter terminals (+, –, GND) are connected to the B30 communication module (+, –, COM) terminals. See the CPU Communication Ports section in chapter 3 for details.
  • Page 94: Install Software

    Click the Next button to begin the installation. The files are installed in the directory indicated, and the installation program automatically creates icons and adds an entry to the Windows start menu. 3-46 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 95: Add Device To Software

    3.7 Add device to software You connect remotely to the B30 through the rear RS485 or Ethernet port with a computer running the EnerVista UR Setup software. The B30 also can be accessed locally with a computer through the front panel RS232 port or the rear Ethernet port using the Quick Connect feature.
  • Page 96 From the Windows desktop, right-click the My Network Places icon and select Properties to open the network connections window. Or in Windows 7, access the Network and Sharing Center in the Control Panel. 3-48 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 97 Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button. Click the “Use the following IP address” box. Enter an IP address with the first three numbers the same as the IP address of the B30 relay and the last number different (in this example, 1.1.1.2).
  • Page 98 Minimum = 0ms, Maximum = 0ms, Average = 0 ms Pinging 1.1.1.1 with 32 bytes of data: verify the physical connection between the B30 and the computer, and double-check the programmed IP address in setting, then repeat step 2. Product Setup  Communications  Network  IP Address...
  • Page 99 If this computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been disconnected from the B30 relay. Start the Internet Explorer software. Select the UR device from the EnerVista Launchpad to start EnerVista UR Setup. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 3-51...
  • Page 100 Click the Quick Connect button to open the window. Select the Ethernet interface and enter the IP address assigned to the B30, then click the Connect button. The EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named “Quick Connect”...
  • Page 101: Configure Serial Connection

    For the RS232 connection, a computer with an RS232 port and a serial cable are required. To use the RS485 port at the back of the relay, a GE Grid Solutions F485 converter (or compatible RS232-to-RS485 converter) is required. See the F485 instruction manual for details.
  • Page 102: Configure Ethernet Connection

    SEL-2032. This option enables display of a terminal window to allow interaction with the other device. 11. Click the Read Order Code button to connect to the B30 and upload the order code to the software. If a communications error occurs, ensure that the EnerVista software serial communications values entered in the previous step correspond to the relay setting values, and also ensure that the same IP address is not assigned to multiple B30 ports.
  • Page 103 12. If using a gateway to connect to the device, select Yes from the drop-down list. 13. Click the Read Order Code button to connect to the B30 device and upload the order code. If the device was entered already, a message displays "Device ’x’ is also using IP address.." If a communications error occurs, ensure that the values entered in the previous steps correspond to the relay setting values, and also ensure that the same IP address is not assigned to multiple B30 ports.
  • Page 104: Configure Modem Connection

    ADD DEVICE TO SOFTWARE CHAPTER 3: INSTALLATION The device has been configured for Ethernet communications. Proceed to the Connect to the B30 section to begin communications. 3.7.4 Configure modem connection A modem connection allows a computer to communicate with a UR device over phone lines.
  • Page 105: Connect To The B30

    When unable to connect because of an "ACCESS VIOLATION," access Device Setup and refresh the order code for the device. When unable to connect, ensure that the same IP address is not assigned to multiple B30 ports, for example under Settings > Product Setup > Communications > Network.
  • Page 106: Use Quick Connect Via The Front Panel Rs232 Port

    Connect a nine-pin to nine-pin RS232 serial cable to the computer and the front panel RS232 port. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista DVD or online from http://www.gegridsolutions.com/multilin). See the software installation section if not already installed.
  • Page 107: Use Quick Connect Via A Rear Ethernet Port

    Connect" and displays them in the Online Window. Expand the sections to view data directly from the B30 device. Use the Device Setup button to change the site name. Each time that the EnerVista software is initialized, click the Quick Connect button to establish direct communications to the B30.
  • Page 108: Import Settings

    If required, change the Files of type drop-down list. Select the file to import. To apply the settings to a live device, drag-and-drop the device entry from the Offline Window area to its entry in the Online Window area. 3-60 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 109 CHAPTER 3: INSTALLATION IMPORT SETTINGS Individual settings also can be dragged and dropped between Online and Offline Window areas. The order codes much match. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 3-61...
  • Page 110 IMPORT SETTINGS CHAPTER 3: INSTALLATION 3-62 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 111: Interfaces

    The EnerVista UR Setup software is provided with every B30. This chapter outlines the EnerVista software interface features. The EnerVista UR Setup Help File also provides details for getting started and using the software interface.
  • Page 112: Event Viewing

    IP Address IP Subnet Mask IP Routing When a settings file is loaded to a B30 that is in-service, the following sequence occurs: The B30 takes itself out of service. The B30 issues a UNIT NOT PROGRAMMED major self-test error.
  • Page 113: File Support

    Settings list / offline window area Software windows, with common tool bar Settings file data view windows, with common tool bar Workspace area with data view tabs Status bar 10. Quick action hot links B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 114: Protection Summary Window

    4.1.6 Protection summary window The Protection Summary is a graphical user interface to manage elements, such as enabling and disabling them. Access it under Settings > Protection Summary. See the Settings chapter for information on use. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 115: Settings Templates

    CHAPTER 4: INTERFACES ENERVISTA SOFTWARE INTERFACE Figure 4-2: Protection Summary interface (B30 example shown) 4.1.7 Settings templates Settings file templates simplify the configuration and commissioning of multiple relays that protect similar assets. An example is a substation that has 10 similar feeders protected by 10 UR-series F60 relays.
  • Page 116 Figure 4-4: Settings template with all settings specified as locked Specify the settings to make viewable by clicking them. A setting available to view is displayed against a yellow background. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 117 To display only the settings available for editing: Select an installed device or a settings file from the left menu of the EnerVista UR Setup window. Apply the template by selecting the Template Mode > View In Template Mode option. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 118 Once the template has been applied, users are limited to edit the settings specified by the template, but all settings are shown. The effect of applying the template to the phase time overcurrent settings is shown as follows. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 119: Secure And Lock Flexlogic Equations

    4.1.8.1 Lock FlexLogic equations To lock individual entries of a FlexLogic equation: Right-click the settings file or online device and select the Template Mode > Create Template item to enable the settings template feature. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 120 The effect of applying the template to the FlexLogic entries is shown here. Figure 4-10: Locking FlexLogic entries through settings templates The FlexLogic entries are also shown as locked in the graphical view and on the front panel display. 4-10 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 121 Right-click the setting file in the offline window area and select the Edit Device Properties item. The window opens. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-11...
  • Page 122: Settings File Traceability

    When a settings file is transferred to a B30 device, the date, time, and serial number of the B30 are sent back to EnerVista UR Setup and added to the settings file on the local computer. This information can be compared with the B30 actual values at any later date to determine if security has been compromised.
  • Page 123 With respect to the figure, the traceability feature is used as follows. The transfer date of a settings file written to a B30 is logged in the relay and can be viewed in the EnerVista software or the front panel display. Likewise, the transfer date of a settings file saved to a local computer is logged in the EnerVista software.
  • Page 124 4.1.9.2 Online device traceability information The B30 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista online window as shown in the example.
  • Page 125: Front Panel Interface

    The front panel can be viewed and used in the EnerVista software, for example to view an error message displayed on the front panel. To view the front panel in EnerVista software: Click Actual Values > Front Panel. Figure 4-18: Front panel use in the software (C60 shown) B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-15...
  • Page 126: Front Panel Keypad

    MESSAGE arrow from a header display displays specific information for the category. Conversely, continually pressing the MESSAGE left arrow from a setting value or actual value display returns to the header display. 4-16 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 127: Changing Settings

    Each numerical setting has its own minimum, maximum, and increment value associated with it. These parameters define what values are acceptable for a setting. FLASH MESSAGE For example, select the SETTINGS  PRODUCT SETUP  DISPLAY PROPERTIES  FLASH TIME: 10.0 s MESSAGE TIME setting.  B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-17...
  • Page 128 Repeat step 2 for the remaining characters: r,e,a,k,e,r, ,#,1. Press to store the text. ENTER If you have any problem, press to view context sensitive help. Flash messages appear sequentially for several HELP 4-18 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 129: Faceplate

    The faceplate is hinged to allow easy access to the removable modules. There is also a removable dust cover that fits over the faceplate that must be removed in order to access the keypad panel. The following figure shows the horizontal arrangement of the faceplate panel. Figure 4-21: Standard horizontal faceplate B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-19...
  • Page 130: Led Indicators

    LED indicator or target message, once the condition has been cleared (these RESET latched conditions can also be reset via the menu). SETTINGS  INPUT/OUTPUTS  RESETTING keys are used by the breaker control feature. USER 4-20 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 131 Support for applying a customized label beside every LED is provided. Default labels are shipped in the label package of every B30, together with custom templates. The default labels can be replaced by user-printed labels. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 132 ORed to turn on or off the phase A, B, or C LEDs. • VOLTAGE — Indicates voltage was involved • CURRENT — Indicates current was involved • FREQUENCY — Indicates frequency was involved • OTHER — Indicates a composite function was involved 4-22 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 133 LED settings must be entered as shown in the User-programmable LEDs section of chapter 5. The LEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both panels as explained in the next section. Figure 4-26: LED panel 2 (default labels) B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-23...
  • Page 134: Custom Led Labeling

    Select the Front Panel Label Designer item from the Online Window or Offline Window area, for example under Settings > Front Panel Label Designer. If the option does not display, it means that the B30 does not have an enhanced front panel or that no customization is possible. The Online Window has the advantage of displaying the live fields as opposed to blank fields.
  • Page 135 Use the tool EXACTLY as outlined as follows, with the printed side containing the GE part number facing the user. The label package shipped with every B30 contains the three default labels, the custom label template sheet, and the label removal tool.
  • Page 136 Slide the label tool under the LED label until the tabs snap out as shown. This attaches the label tool to the LED label. Remove the tool and attached LED label as shown. 4-26 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 137 Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown. To remove the user-programmable pushbutton labels from the B30 enhanced front panel and insert the custom labels: Use the knife to lift the pushbutton label and slide the tail of the label tool underneath, as shown. Ensure that the bent tab points away from the relay.
  • Page 138: Breaker Control

    4.2.9 Breaker control The B30 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker, that can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually initiated from the faceplate keypad or automatically initiated from a FlexLogic operand.
  • Page 139: Change Passwords

    The information in this section refers to password security. For information on how to set the password for the first time or change CyberSentry passwords, see the previous chapter or the Settings > Product Setup > Security > CyberSentry section in the next chapter. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-29...
  • Page 140 When entering a settings or command password via EnerVista or any serial interface, the user must enter the corresponding connection password. If the connection is to the back of the B30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 141: Invalid Password Entry

    By default, when an incorrect Command or Setting password has been entered via the faceplate interface three times within five minutes, the FlexLogic operand is set to “On” and the B30 does not allow settings or LOCAL ACCESS DENIED command level access via the faceplate interface for five minutes.
  • Page 142: Flexlogic Design And Monitoring Using Engineer

    Works with all UR firmware versions The figure shows an example where several inputs are used to trigger an output. With the OR function, any one of the inputs can trigger the output. 4-32 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 143 This section explains how to use Engineer. It outlines the following topics: • Design logic • Send file to and from device • Monitor logic • View front panel • Generate connectivity report • Preferences B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-33...
  • Page 144: Design Logic

    Preparation — Under Settings > Inputs/Outputs > Virtual Outputs, virtual outputs 3 and 4 are named DLTrigger Top logic — Seven-minute timer trigger Bottom logic — Turn on LED 9 for 10 seconds when the trigger starts 4-34 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 145 This procedure uses input / output logic as an example. To create a logic diagram: In the Offline Window area, access Engineer for the device, then Logic Designer. If the device is not listed, right-click B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-35...
  • Page 146 Add the input blocks to the logic diagram. For example, click the I/O Tokens tab on the right, click the Input element, then click in the logic sheet to add it. Or drag-and-drop it. 4-36 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 147 Line option. The cursor needs to be at the connection point to end the line, not elsewhere on the block. Note that the outline color is no longer red on the blocks. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-37...
  • Page 148 The warning "input using disabled feature" means that input needs to be enabled. Double-click the block, click the View Associated Screen button, enable the setting, save, and recompile. The output and messages are explained in the next section. 4-38 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 149 'Do not update IID file when updating SCL files') are updated. If the CID file is not already there, it is generated. The location of these files is C:\ProgramData\GE Power Management\urpc, for example, in the Offline and Online folders.
  • Page 150 The same timer is used in more than one place in the editor. This means (TIMER_ID, SheetReference) either the circuit that the Timer belongs to has been branched, or the Timer has been duplicated. 4-40 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 151 Click the Ok button to save and exit from the window. In the logic diagram, select an element, then click in the drawing area to add it, click again to add a second box, and so on. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-41...
  • Page 152 Optimization Summary. Changes also display when the FlexLogic Equation Editor is accessed. The logic diagram does not change. In the example shown, no lines were saved to free up space. Figure 4-45: Code optimization results 4-42 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 153 Type in the second text string box, or select any of the 32 previous searches from the drop-down list. Click the Search button. Any results display. The search applies to all tabs, not just the active tab. Double-click a search result to view the item. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-43...
  • Page 154: Send File To And From Device

    When a window opens, select the device to which you want to send the file, then click the Send button and confirm. The order codes must match. The file is sent to the live device. Any errors can be viewed in the log file at the prompt. 4-44 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 155: Monitor Logic

    (green box outline). In this case, the battery is weak and needs to be replaced. This can be viewed as the Replace Battery message on the front panel of the device and in the EnerVista software under Actual Values > Front Panel > Front Panel or Display/Keypad. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-45...
  • Page 156: View Front Panel And Print Labels

    To save the report and labels, click File > Save As, enter a file name, and select the FPR, JPG, or PDF format. Use the instructions in the second tab of the window to add the labels to the physical device. 4-46 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 157: Generate Connectivity Report

    View > Toolbar > Advanced Actions — Active when in Logic Designer. Toggles a toolbar to nudge, rotate, flip, or change the order of an element. View > Show Unused Pins — Enable to display unconnected pins. Disable to eliminate unconnected pins from the view, for example when printing. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-47...
  • Page 158 File Information The text entered here displays at the bottom right of a diagram when printing, provided that the Show Title Block option is enabled. Note the option to change the logo from the GE logo to your company logo. Display The panel sets how the element boxes display.
  • Page 159 The software displays the color specified when an element is on. There is no color when the element is off. The software displays another color when the status cannot be determined and is unknown. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-49...
  • Page 160 Options display for filtering, such as recording timing for Virtual Inputs and Outputs, but not Communications Status. 4.4.6.4 COMTRADE waveforms Waveform files are viewable in the EnerVista software. The preferences are unrelated to Engineer and are outlined in the UR Family Communications Guide. 4-50 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 161: Toolbars

    When you re-launch the EnerVista software, communication is on by default. 4.4.7.2 Token Toolbox Drawing Tools Draw a line. Click and drag to draw. Draw multiple joined lines. Click and drag for each line. Double-click to finish. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-51...
  • Page 162 Remote inputs from other devices Input from another UR device. Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive and cannot be used simultaneously. Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive and cannot be used simultaneously. 4-52 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 163 Tag-In can is used to reference an existing Tag-Out. It joins another diagram to a previous diagram. Boolean Tokens These symbols are used to create FlexLogic Equations. Use them as intermediate logic for the Virtual Output equations. The display can vary from that shown here. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-53...
  • Page 164 Place a positive one shot and a negative one shot symbol in the Logic Designer diagram Place a timer in the Logic Designer diagram Elements These blocks configure properties of the element or use element operands as input to FlexLogic equations. 4-54 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 165 Set the width of the selected components to the same width as the reference component Same Height Set the height of the selected components to the same height as the reference component B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-55...
  • Page 166 Front, Back Moves current components to the absolute front or back of all viewable layers Forward, Backward Moves current components on layer higher or lower than its original layer hierarchy 4-56 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 167: Settings

     FAULT REPORTS  OSCILLOGRAPHY See page 5-100    DATA LOGGER See page 5-101    DEMAND See page 5-103    USER-PROGRAMMABLE See page 5-104   LEDS B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 168  SETTINGS  SETTING GROUP 1 See page 5-167   GROUPED ELEMENTS   SETTING GROUP 2     SETTING GROUP 3    SETTING GROUP 4   B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 169 See page 5-252 TEST MODE FORCING: Range: FlexLogic operand   See page 5-253  FORCE CONTACT See page 5-253   INPUTS  FORCE CONTACT See page 5-254    OUTPUTS B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 170: Overview

    FUNCTION setting — This setting programs the element to operate when selected as “Enabled.” The factory default is “Disabled.” Once “Enabled,” any element associated with the function becomes active and all options become available. • NAME setting — This setting is used to uniquely identify the element. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 171: Introduction To Ac Sources

    The same considerations apply to transformer winding 2. The protection elements require access to the net current for transformer protection, but some elements can need access to the individual currents from CT1 and CT2. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 172 “bank,” and all four are either current or voltage, as are channels 5, 6, 7, and 8. Channels 1, 2, 3 and 5, 6, 7 are arranged as phase A, B, and C respectively. Channels 4 and 8 are either another current or voltage. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 173: Product Setup

    To reset the unit after a lost password: Email GE customer service at multilin.tech@ge.com with the serial number and using a recognizable corporate email account. Customer service provides a code to reset the relay to the factory defaults.
  • Page 174  EVENTS: Disabled The B30 supports password entry from a local or remote connection. Local access is defined as access to settings or commands via the faceplate. This includes both keypad entry and the RS232 port. Remote access is defined as access to settings or commands via any rear communications port. This includes both Ethernet and RS485 connections.
  • Page 175 When entering a settings or command password via EnerVista or any serial interface, the user must enter the corresponding connection password. If the connection is to the back of the B30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 176 SETTINGS  PRODUCT SETUP  SECURITY  ACCESS SUPERVISION  ACCESS  ACCESS LEVEL See below   SUPERVISION  TIMEOUTS INVALID ATTEMPTS Range: 2 to 5 in steps of 1  BEFORE LOCKOUT: 3 5-10 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 177 INVALID ATTEMPTS BEFORE LOCKOUT The B30 provides a means to raise an alarm upon failed password entry. If password verification fails while accessing a password-protected level of the relay (either settings or commands), the FlexLogic operand is UNAUTHORIZED ACCESS asserted.
  • Page 178 The status of this timer updates every five seconds. 5.3.1.3 EnerVista security Enable the security management system The EnerVista security system allows an administrator to manage access privileges of multiple users of EnerVista. 5-12 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 179 If you force password entry by using this feature, ensure that you know the Administrator password. If you do not know the password and are locked out of the software, contact GE Grid Solutions for the default password of a UR device.
  • Page 180 The EnerVista security management system must be enabled (the Enable Security check box enabled) To modify user privileges: Select the Security > User Management item from the top menu to open the user management window. Locate the username in the User field. 5-14 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 181 This feature requires a CyberSentry software option. See the Order Codes section in chapter 2 for details. The EnerVista software provides the means to configure and authenticate the B30 access using either a server or the device. Access to functions depends on user role.
  • Page 182 When the "Device" button is selected, the B30 uses its local authentication database and not the RADIUS server to authenticate the user. In this case, it uses built-in roles (Administrator, Engineer, Supervisor, Operator, Observer, or Administrator and Supervisor when Device Authentication is disabled), as login accounts and the associated passwords are stored on the B30 device.
  • Page 183 Figure 5-3: Security panel when CyberSentry installed For the Device > Settings > Product Setup > Supervisory option, the panel looks like the following. Figure 5-4: Supervisory panel For the Security panel, the following settings are available. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-17...
  • Page 184 Administrator is to re-enable Device authentication when Device authentication is disabled. To re-enable Device authentication, the Supervisor unlocks the device for setting changes, and then the Administrator can re- enable Device authentication. 5-18 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 185 SETTINGS  PRODUCT SETUP  SECURITY  SECURITY LOGIN: Range: Administrator, Engineer, Supervisor,   None Operator, Factory (for factory use only), None  CHANGE LOCAL See page 5-20   PASSWORDS LOGOUT: Range: FlexLogic operand  B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-19...
  • Page 186 • Observer — This role has read-only access to all B30 settings. This role allows unlimited concurrent access but it has no download access to any files on the device. Observer is the default role if no authentication has been done to the device.
  • Page 187 In Device authentication mode, the Observer role does not have a password associated with it. In Server authentication mode the Observer role requires a password. If you are locked out of the software, contact GE Grid Solutions for the default password. When using CyberSentry, the default password is "ChangeMe1#".
  • Page 188 RS232 and RS485 connections. The default value is 1 minute. Self-tests SETTINGS  PRODUCT SETUP  SECURITY  SUPERVISORY  SELF TESTS  SELF TESTS  FAILED See below    AUTHENTICATE 5-22 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 189 Supervisor, Engineer, Operator, Observer) in the RADIUS server. If you do, the UR relay automatically provides the authentication from the device. In the EnerVista software, choose Server authentication and log in using the user name and password configured on the RADIUS server for Server authentication login. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-23...
  • Page 190 Clear Demand Records command (not applicable to all UR products) Clear Energy command (not applicable to all UR products) Clear Unauthorized Access command Clear Teleprotection Counters command (not applicable to all UR products) Clear All Relay Records command Role Log in 5-24 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 191: Display Properties

    Enumeration Description Role Log off In addition to supporting syslog, a B30 with CyberSentry also saves the security events in two local security files, these being SECURITY_EVENTS.CSV and SETTING_CHANGES.LOG. Details on these files and how to retrieve them are available in the EnerVista software under Maintenance >...
  • Page 192: Clear Relay Records

    Some customers prefer very low currents to display as zero, while others prefer the current to display even when the value reflects noise rather than the actual signal. The B30 applies a cut-off value to the magnitudes and angles of the measured currents.
  • Page 193: Communications

    Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user- programmable pushbuttons to clear specific records is a typical application for these commands. Since the B30 responds to rising edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.
  • Page 194 5.3.4.3 Ethernet network topology The B30 has three Ethernet ports. Each Ethernet port must belong to a different network or subnetwork. Configure the IP address and subnet to ensure that each port meets this requirement. Two subnets are different when the bitwise AND operation performed between their respective IP address and mask produces a different result.
  • Page 195 SCADA is provided through LAN2. P2 and P3 are connected to LAN2, where P2 is the primary channel and P3 is the redundant channel. In this configuration, P3 uses the IP and MAC addresses of P2. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-29...
  • Page 196 LAN2, to which port 2 (P2) is connected, and communications with SCADA on LAN3, to which port 3 (P3) is connected. There is no redundancy. Figure 5-7: Multiple LANS, no redundancy 5-30 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 197 IP addresses and mask. Configure the network IP and subnet settings before configuring the routing settings. To obtain a list of all port numbers used, for example for audit purposes, contact GE technical support with substantiating information, such as the serial number and order code of your device.
  • Page 198 2 is performed. The delay in switching back ensures that rebooted switching devices connected to the B30, which signal their ports as active prior to being completely functional, have time to completely initialize themselves and become active. Once port 2 is active again, port 3 returns to standby mode.
  • Page 199 PRODUCT SETUP 5.3.4.6 Parallel Redundancy Protocol (PRP) The B30 is provided with optional PRP capability. This feature is specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for details. The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation networks.
  • Page 200 The route destination and mask must match. This can be verified by checking that RtDestination and RtMask = RtDestination Example of good configuration: RtDestination = 10.1.1.0; Rt Mask = 255.255.255.0 Example of bad configuration: RtDestination = 10.1.1.1; Rt Mask = 255.255.255.0 5-34 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 201 The configuration before release 7.10 was as follows: • PRT1 IP ADDRESS = 10.1.1.2 PRT1 SUBNET IP MASK = 255.255.255.0 PRT1 GWY IP ADDRESS = 10.1.1.1 PRT2 IP ADDRESS = 10.1.2.2 PRT2 SUBNET IP MASK = 255.255.255.0 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-35...
  • Page 202 This allows the EnerVista UR Setup software to be used on the port. UR devices operate as Modbus slave devices only. For more information on the protocol, including the memory map table, see the UR Family Communications Guide. 5-36 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 203 0 disables Modbus over TCP/IP, meaning closes the Modbus TCP port. When the port number is changed to 0, the change takes effect when the B30 is restarted. When it is set to 0, use the front panel or serial port to communicate with the relay.
  • Page 204 MAX RETRIES: 10 DNP UNSOL RESPONSE Range: 0 to 65519 in steps of 1  DEST ADDRESS: 1 DNP CURRENT SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,  FACTOR: 1 100000 5-38 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 205 Range: 0 to 32 in steps of 1  CONTROL POINTS: 0 DNP TCP CONNECTION Range: 10 to 7200 s in steps of 1  TIMEOUT: 120 s DNP EVENT TIME BASE: Range: UTC, LOCAL  LOCAL B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-39...
  • Page 206 DNP ADDRESS unique address to each DNP slave. The B30 can specify a maximum of five clients for its DNP connections. These are IP addresses for the controllers to which the B30 can connect. The settings follow. SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP PROTOCOL  DNP NETWORK CLIENT ADDRESSES ...
  • Page 207 DNP TCP connection for greater than the time specified by this setting, the connection is aborted by the B30. This frees up the connection to be re-used by a client. Any change takes effect after cycling power to the relay.
  • Page 208 60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are ignored. 5.3.4.12 IEC 61850 protocol The B30 is provided with optional IEC 61850 communications. This feature is specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for details.
  • Page 209 The maximum number of simultaneous clients supported by the UR family is five. EnerVista setup for IEC 61850 The EnerVista UR Setup software provides the interface to configure B30 settings for the IEC 61850 protocol. This section describes this interface. The software also supports import/export and merging of IEC 61850 Substation Configuration Language (SCL) files as documented in the UR Family Communications Guide.
  • Page 210 Figure 5-11: IEC 61850 panel Opening the IEC 61850 window while online causes the UR Setup software to retrieve and import an SCL file from the B30. This System Configuration Description (SCD) file contains all the settings in the UR at the time of the file request, both those that are mapped into the IEC 61850 information model (that is, the "public"...
  • Page 211 When the Save button is clicked in the online IEC 61850 window, UR Setup software prepares a configured IED description (CID) file containing all the settings of the UR and sends the CID file to the B30. Upon receipt, the B30 checks the CID file for correctness, going out of service, then back into service when the CID file is accepted.
  • Page 212 Default: TEMPLATE The value entered sets the IED name used by IEC 61850 for the B30. An IED name unique within the network must be entered for proper operation. Valid characters are upper and lowercase letters, digits, and the underscore (_) character.
  • Page 213 Range: status-only, direct-with-normal-security, sbo-with-normal-security Default: sbo-with-normal-security This setting specifies the control service that clients must use to control the TEST MODE FUNCTION of the B30. An "on" control to <LDName>/LLN0.Mod changes TEST MODE FUNCTION to Disabled, an "on-blocked" control changes it to Forcible, and a "test/blocked"...
  • Page 214 Protection logical device has been set to instance name "Prot", the function-related name "Feeder1Prot" and the configuration revision "2016-03-07 08:46." The text is clipped on the right if the line is longer than the available width. The next paragraphs explain how to do this setup. 5-48 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 215 Figure 5-15: Menu for logical node If the insert option is selected, or the edit option is selected for other than the Master logical device, a logical device parameters edit dialog opens. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-49...
  • Page 216 Each logical device inst name is required to be unique within the device, and it cannot be blank. Also, if the corresponding functional ldName setting is blank, the concatenation of the IED name and the logical device 5-50 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 217 The UR increments the value of paramRev by one whenever one or multiple setting changes occurs in one Modbus write request by any means (front panel, Modbus, or MMS) other than by SCL file B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-51...
  • Page 218 Routable GOOSE (R-GOOSE) is supported in firmware release 7.4 and later. Routable GOOSE allows UR and other devices to be located in separate networks. Encryption/decryption of messages is performed by a separate gateway device. Messages are routed using a separate router, using IP addresses. Note the following behavior: 5-52 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 219 The UR does not implement the Fixed-Length encoded GOOSE messages option specified in IEC 61850-8-1:2011 clause A.3; the UR always uses the ASN.1 Basic encoding rules (as specified in ISO/IEC 8825-1) as specified in IEC 61850 edition 1.0 and as optional in IEC 61850 edition 2.0. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-53...
  • Page 220 TxGOOSE1 messages from other GOOSE messages. <LDName> is a syntactic variable that is set to the value of setting Master functional ldName if one or more characters have been entered to that setting, otherwise the value of setting IED NAME suffixed with "Master". 5-54 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 221 Network devices can forward a message with a higher priority value before a message with a lower priority value, which speeds delivery of high-priority messages in heavily loaded networks. The standard recommends that higher-priority messages, such as GOOSE, have priority values in the range of 4 to 7. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-55...
  • Page 222 Range: 1 to 60 s in steps of 1 s Default: 60 s This setting specifies the time interval between heartbeat messages, meaning messages that are sent periodically while no events are detected. 5-56 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 223 61850-90-5 R GOOSE service can be subscribed to. The UR accepts both the variable length encoded GOOSE messages specified IEC 61850 8 1:2004 and the Fixed-Length encoded GOOSE messages as specified in IEC 61850 8 1:2011 clause A.3. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-57...
  • Page 224 RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1 does not check the value received in the goID field. If the publisher is a UR 7.3x series device, this setting needs match the value of the publisher's TxGOOSE GoID setting. 5-58 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 225 <GoCBName> is the name of the publishing control block. The B30 translates the ACSI format required for this setting to the MMS format used in GOOSE messages: <LDName>/LLN0$GO$<GoCBName> If the publisher is a UR 7.3x or 7.40 series device, <LDName> is the value of the publisher's Master functional ldName setting if that setting is not empty, otherwise it is the value of the publisher's IED NAME suffixed with "Master".
  • Page 226 If the publisher is a UR 7.3x or 7.40 series device, set these settings to match the basic type of the members of the publisher's data set selected by the publisher's TxGOOSE datSet setting. 5-60 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 227 SCD (supported in version 7.40 and later). When the file format is SCD, the system lists all IEDs inside the SCD file and lets the user select the ones to add. The figure shows a selection being made by importing a CID file using the Add IED function. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-61...
  • Page 228 This setting selects the logic state for the RxGOOSE Boolean1 FlexLogic operand if the UR has just completed startup and the selected RxGOOSE has not yet received a message, or the selected RxGOOSE has lost its connectivity with the publisher. The following choices are available: 5-62 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 229 Range: None, RxGOOSE1, RxGOOSE2, and so on Default: None This setting selects the GOOSE message containing the value that drives the RxGOOSE DPS1 FlexLogic operand. If set to None, the RxGOOSE DPS1 FlexLogic operand assumes its default state. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-63...
  • Page 230 (supported in version 7.40 and later). When the file format is SCD, the system lists all IEDs inside the SCD file and lets the user select the ones to add. Figure 5-23: RxGOOSE Analog Inputs panel There are 32 RxGOOSE analog inputs. 5-64 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 231 Range: 0.000 to 1000000000.000 in steps of 0.001 Default: 1.000 This setting specifies the per-unit base value for other B30 features to use with the RxGOOSE Analog1 operand. A FlexElement for instance subtracts two quantities after converting their values to integers rescaled to a common base, the common base being the largest of the base values of the two quantities.
  • Page 232 RptEna attribute is false. Buffered and unbuffered reports Navigate to Settings > Product Setup > Communications > IEC 61850 > Reports > Buffered Reports or Unbuffered Reports. 5-66 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 233 Also, the control block can be configured to send integrity reports containing the present value of all members either on demand from the client or periodically. A TCP handshaking mechanism causes messages that are not read and acknowledged by the client to be retransmitted. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-67...
  • Page 234 Control blocks and data sets can be pre-configured by sending the B30 a CID file. See the UR Family Communications Guide for details. EnerVista UR Setup also can be used to select the data set members and to pre-configure the control blocks.
  • Page 235 This setting selects the data set whose members' status is reported in Unbuffered Report1 messages using the UR Setup software designator for the data set. The IEC 61850 name of the data sets are configured in the Datasets panel, as described later. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-69...
  • Page 236 DataSets Navigate to Settings > Product Setup > Communications > IEC 61850 > DataSets. 5-70 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 237 The DataSet name is not copied or pasted. In short, use this feature to copy a DataSet Member setting and paste it into another Member setting, a text file, or Word, as examples. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-71...
  • Page 238 Select the member from the drop-down list. Or right-click an entry to copy, paste, delete, or insert. Product setup Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup. 5-72 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 239 Deadband parameters of measured values related to the Energy metering are configured here. Real Time Clock Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup > Real Time Clock. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-73...
  • Page 240 However, a tabulation of the analog values and their associated deadband setting can be found in the UR Family Communications Guide. Figure 5-30: Deadband settings with .db suffix 5-74 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 241 Navigate to Settings > Communications > IEC 61850 > System Setup > Breakers > Breaker 1 to access the settings that configure the IEC 61850 protocol interface with the first breaker control and status monitoring element. The settings and functionality for the others are similar. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-75...
  • Page 242 SelectWithValue or Operate service with ctlVal true and with Check.Interlock-check true is requested of either BkrCSWI1.Pos or Bkr0XCBR1.Pos and the selected operand is not activated, a Negative Response (-Rsp) is issued with the REASON CODE of Blocked-by-interlocking. 5-76 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 243 This setting specifies the maximum time between an operate command to breaker 1 via BkrCSWI1.Pos until BkrCSWI1.Pos.stVal enters the commanded state. The command terminates if the commanded state is not reached in the set time. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-77...
  • Page 244 If a SelectWithValue or Operate service with ctlVal true and with Check.Interlock-check true is requested of DiscCSWI1.Pos or Disc0XSWI1.Pos and the selected operand is not activated, a Negative Response (-Rsp) is issued with the REASON CODE of Blocked-by-interlocking. 5-78 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 245 > System Setup section later. These signals force a disconnect switch trip or close control while the operand selected by setting XSWI1 ST.LOC OPERAND is not active. "sbo" here is select-before-operate. Enhanced security means that the B30 reports to the client the disconnect switch 1 position the end of the command sequence.
  • Page 246 Navigate to Settings > Product Setup > Communications > IEC 61850 > Settings for Commands to access the settings that configure the IEC 61850 protocol interface for record clear commands. 5-80 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 247 This setting selects the control model clients must use to successfully control the command CLEAR FAULT REPORTS. "sbo" here is select-before-operate. Enhanced security means that the B30 reports to the client the breaker 1 position at the end of the command sequence.
  • Page 248 Virtual Inputs are controllable FlexLogic operands that can be controlled via IEC 61850 commands to GGIO2, by DNP, by Modbus, and by the UR front panel. The settings related to these IEC 61850 commands are described here. 5-82 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 249 Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO4 > GGIO4.AnIn1 to access the settings for the first GGIO4 value. The settings and functionality for the others are similar. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-83...
  • Page 250 <LDName>/GGIO4.AnIn01.instMag.f. This setting is stored as an IEEE 754 / IEC 60559 floating point number. Because of the large range of this setting, not all possible values can be stored. Some values are rounded to the closest possible floating point number. 5-84 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 251 PRODUCT SETUP File transfer by IEC 61850 The B30 supports file transfer by IEC 61850. The approach is as follows, using the SISCO AX-S4 61850 client software as an example. In the AX-S4 61850 Explorer window, click the Tools menu and access the SISCO File Transfer Utility.
  • Page 252 NUMBER: 0 The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the B30 over a network. The B30 operates as a TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained from the B30 contains a list and description of all available files, for example event records and oscillography.
  • Page 253 COMMUNICATIONS  PROTOCOL connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the B30 maintains two sets of IEC 60870-5-104 data change buffers, ideally no more than two masters actively communicate with the B30 at one time.
  • Page 254 CHAPTER 5: SETTINGS The B30 can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to which the B30 can connect. A maximum of two simultaneous connections are supported at any given time.
  • Page 255 EXCH 1 DATA ITEM 1 to 20/50 from the B30 memory map can be configured to be included in an EGD exchange. The settings are the starting Modbus register address for the data item in decimal format. See the Modbus memory map in the UR Series Communications Guide for details.
  • Page 256 PTP, or SNTP, its time is overwritten by these three sources, if any of them is active. If the synchronization timeout occurs and none of IRIG-B, PTP, or SNTP is active, the B30 sets the invalid bit in the time stamp of a time-tagged message.
  • Page 257 Spontaneous transmission occurs as a response to cyclic Class 2 requests. If the B30 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in the control field of the response).
  • Page 258 FlexAnalog operands. The measurands sent are voltage, current, power, power factor, and frequency. If any other FlexAnalog is chosen, the B30 sends 0 instead of its value. Note that the power is transmitted in KW, not W. Measurands are transmitted as ASDU 3 or ASDU 9 (type identification value set to measurands I, respectively measurands II).
  • Page 259 Commands are received as General Command (Type Identification 20). The user can configure the action to perform when an ASDU command comes. A list of available mappings is provided on the B30. This includes 64 virtual inputs (see the following table). The ON and OFF for the same ASDU command can be mapped to different virtual inputs.
  • Page 260: Modbus User Map

    ADDRESS The UR Family Communications Guide outlines the Modbus memory map. The map is also viewable in a web browser; enter the IP address of the B30 in a web browser and click the option. 5.3.6 Real-time clock 5.3.6.1 Menu SETTINGS ...
  • Page 261 Setup for IRIG-B is illustrated in the Installation chapter. For the Other protocols, whenever a time synchronization message is received through any of the active protocols, the B30 clock updates. However, given that IEC 60870-5-103, IEC 60870-5-104, Modbus, and DNP are low-accuracy time synchronization methods, avoid their use for synchronization when better accuracy time protocols, such as IRIG-B and PTP, are active in the system.
  • Page 262 See the Order Codes section in chapter 2 for details. The B30 supports the Precision Time Protocol (PTP) specified in IEEE Std 1588 2008 using the Power Profile (PP) specified in IEEE Std C37.238 2011. This enables the relay to synchronize to the international time standard over an Ethernet network that implements PP.
  • Page 263 The B30 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the B30 can obtain clock time over an Ethernet network. The B30 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a dedicated product using a GPS receiver.
  • Page 264 B30 clock is closely synchronized with the SNTP/ NTP server. It takes up to two minutes for the B30 to signal an SNTP self-test error if the server is offline.
  • Page 265: User-Programmable Fault Report

    The user programmable record contains the following information: the user-programmed relay name, detailed firmware revision (x.xx, for example) and relay model (B30), the date and time of trigger, the name of pre-fault trigger (a specific FlexLogic operand), the name of fault trigger (a specific FlexLogic operand), the active setting group at pre-fault trigger, the active setting group at fault trigger, pre-fault values of all programmed analog channels (one cycle before pre-fault trigger), and fault values of all programmed analog channels (at the fault trigger).
  • Page 266: Oscillography

    Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of the relay, which is always 64 samples per cycle. That is, it has no effect on the fundamental calculations of the device. 5-100 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 267: Data Logger

     DATA LOGGER DATA LOGGER MODE: Range: Continuous, Trigger   Continuous DATA LOGGER TRIGGER: Range: FlexLogic operand  DATA LOGGER RATE: Range: 15 to 3600000 ms in steps of 1  60000 msec B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-101...
  • Page 268 Analog Input hardware modules installed. Upon startup, the relay automatically prepares the parameter list. A list of all possible analog metering actual value parameters is shown in 5-102 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 269: Demand

    90% of a steady-state value, just as the response time of an analog instrument. A steady state value applied for twice the response time indicates 99% of the value. Figure 5-41: Thermal demand characteristic B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-103...
  • Page 270: User-Programmable Leds

    When enabled, the LED test can be initiated from any digital input or user-programmable condition, such as a user- programmable pushbutton. The control operand is configured under the setting. The test covers all LED TEST CONTROL LEDs, including the LEDs of the optional user-programmable pushbuttons. 5-104 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 271 The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is executed. Figure 5-42: LED test sequence Application example 1 Assume one needs to check if any of the LEDs is “burned” through user-programmable pushbutton 1. Apply the following settings. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-105...
  • Page 272 LED column 4 — User-programmable LEDs 25 through 36 • LED column 5 — User-programmable LEDs 37 through 48 See the LED Indicators section in chapter 4 for information on the location of these indexed LEDs. 5-106 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 273: User-Programmable Self-Tests

    BATTERY FAIL Range: Disabled, Enabled  FUNCTION: Enabled SNTP FAIL Range: Disabled, Enabled  FUNCTION: Enabled IRIG-B FAIL Range: Disabled, Enabled  FUNCTION: Enabled PTP FAIL Range: Disabled, Enabled  FUNCTION: Enabled B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-107...
  • Page 274: Control Pushbuttons

    The location of the control pushbuttons are shown in the following figures. Figure 5-43: Control pushbuttons (enhanced faceplate) An additional four control pushbuttons are included on the standard faceplate when the B30 is ordered with the 12 user- programmable pushbutton option.
  • Page 275: User-Programmable Pushbuttons

     Disabled PUSHBTN 1 AUTORST Range: 0.2 to 600.0 s in steps of 0.1  DELAY: 1.0 s PUSHBTN 1 REMOTE: Range: FlexLogic operand  PUSHBTN 1 LOCAL: Range: FlexLogic operand  B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-109...
  • Page 276  EVENTS: Disabled The B30 is provided with this optional feature, specified as an option at the time of ordering. Using the order code for your device, see the order codes in chapter 2 for details. User-programmable pushbuttons provide an easy and error-free method of entering digital state (on, off) information. The number of available pushbuttons is dependent on the faceplate module ordered with the relay.
  • Page 277 — This setting specifies the top 20-character line of the user-programmable message and is intended to PUSHBTN 1 ID TEXT provide ID information of the pushbutton. See the User-definable Displays section for instructions on how to enter alphanumeric characters from the keypad. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-111...
  • Page 278 “High Priority” or “Normal.” MESSAGE — If this setting is enabled, each pushbutton state change is logged as an event into the event PUSHBUTTON 1 EVENTS recorder. The figures show the user-programmable pushbutton logic. 5-112 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 279 CHAPTER 5: SETTINGS PRODUCT SETUP Figure 5-48: User-programmable pushbutton logic (Sheet 1 of 2) B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-113...
  • Page 280: Flex State Parameters

    16 states are readable in a single Modbus register. The state bits can be configured so that all states of interest are available in a minimum number of Modbus registers. 5-114 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 281: User-Definable Displays

    Range: up to 20 alphanumeric characters  DISP 1 ITEM 1: Range: 0 to 65535 in steps of 1   DISP 1 ITEM 5: Range: 0 to 65535 in steps of 1  B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-115...
  • Page 282 If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the bottom line only. The units are only displayed on both lines if the units specified both the top and bottom line items are different. 5-116 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 283: Direct Inputs And Outputs

    DIRECT OUTPUT DEVICE ID messages. All UR-series IEDs in a ring need to have unique numbers assigned. The IED ID is used to identify the sender of the direct input and output message. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-117...
  • Page 284 DIRECT I/O DATA RATE setting applies to a B30 with dual-channel communication cards and allows crossing DIRECT I/O CHANNEL CROSSOVER over messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output network regardless of the physical media of the two communication channels.
  • Page 285 DIRECT I/O CH1 RING CONFIGURATION: “Yes” DIRECT I/O CH2 RING CONFIGURATION: “Yes” For UR-series IED 2: DIRECT OUTPUT DEVICE ID: “2” DIRECT I/O CH1 RING CONFIGURATION: “Yes” DIRECT I/O CH2 RING CONFIGURATION: “Yes” For UR-series IED 3: B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-119...
  • Page 286 Figure 5-53: Three-terminal line application A permissive pilot-aided scheme can be implemented in a two-ring configuration, shown as follows (IEDs 1 and 2 constitute a first ring, while IEDs 2 and 3 constitute a second ring). 5-120 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 287 In this application, apply the following settings. For UR-series IED 1: DIRECT OUTPUT DEVICE ID: “1” DIRECT I/O CH1 RING CONFIGURATION: “Yes” DIRECT I/O CH2 RING CONFIGURATION: “Yes” For UR-series IED 2: B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-121...
  • Page 288 EVENTS: Disabled The B30 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The monitoring function counts all incoming messages, including messages that failed the CRC check.
  • Page 289: Teleprotection

     EVENTS: Disabled The B30 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of unreturned messages.
  • Page 290: Installation

    5.4 Remote resources 5.4.1 Remote resources configuration When the B30 is ordered with a process card module as a part of HardFiber system, an additional Remote Resources menu tree is available in the EnerVista software to allow configuration of the HardFiber system.
  • Page 291 Bricks. Remote resources settings configure the point-to-point connection between specific fiber optic ports on the B30 process card and specific Brick. The relay is then configured to measure specific currents, voltages and contact inputs from those Bricks, and to control specific outputs.
  • Page 292: System Setup

    SETTINGS  SYSTEM SETUP  AC INPUTS  VOLTAGE BANK F5(S5)  VOLTAGE BANK F5 PHASE VT F5 Range: Wye, Delta   CONNECTION: Wye PHASE VT F5 Range: 25.0 to 240.0 V in steps of 0.1  SECONDARY: 66.4 V 5-126 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 293: Power System

    ), while Clarke transformation of the phase ANGLE REF signals is used for frequency metering and tracking (V = (2V ) / 3) for better performance during fault, FREQUENCY open pole, and VT and CT fail conditions. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-127...
  • Page 294: Signal Sources

    “Disabled” only in unusual circumstances; consult GE Grid Solutions for special variable- FREQUENCY TRACKING frequency applications. The frequency tracking feature functions only when the B30 is in the “Programmed” mode. If the B30 is “Not Programmed,” then metering values are available but can exhibit significant errors. 5.5.3 Signal sources SETTINGS ...
  • Page 295 This configuration can be used on a two-winding transformer, with one winding connected into a breaker-and-a-half system. The following figure shows the arrangement of sources used to provide the functions required in this application, and the CT/VT inputs that are used to provide the data. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-129...
  • Page 296: Breakers

    Range: Disabled, Enabled  CONTROL: Disabled BREAKER 1 NAME: Range: up to six alphanumeric characters  Bkr 1 BREAKER 1 MODE: Range: 3-Pole, 1-Pole  3-Pole BREAKER 1 OPEN: Range: FlexLogic operand  5-130 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 297 1. The number of breaker control elements depends on the number of CT/VT modules specified with the B30. The following settings are available for each breaker control element.
  • Page 298 — This setting specifies the interval required to maintain setting changes in effect after an MANUAL CLOSE RECAL1 TIME operator has initiated a manual close command to operate a circuit breaker. — Selects an operand indicating that breaker 1 is out-of-service. BREAKER 1 OUT OF SV 5-132 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 299 CHAPTER 5: SETTINGS SYSTEM SETUP Figure 5-59: Dual breaker control logic (Sheet 1 of 2) IEC 61850 functionality is permitted when the B30 is in “Programmed” mode and not in local control mode. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-133...
  • Page 300 IEC 61850 trip and close commands shown is one protection pass only. To maintain the close/ open command for a certain time, do so on the contact outputs using the "Seal-in" setting, in the Trip Output element, or in FlexLogic. 5-134 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 301: Disconnect Switches

    — This setting selects an operand that prevents opening of the disconnect switch. This setting can be SWITCH 1 BLK OPEN used for select-before-operate functionality or to block operation from a panel switch or from SCADA. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-135...
  • Page 302 This allows for non-simultaneous operation of the poles. IEC 61850 functionality is permitted when the B30 is in “Programmed” mode and not in local control mode. 5-136 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 303 CHAPTER 5: SETTINGS SYSTEM SETUP Figure 5-61: Disconnect switch logic B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-137...
  • Page 304: Flexcurves

    15.0 0.48 0.88 15.5 0.50 0.90 16.0 0.52 0.91 16.5 0.54 0.92 17.0 0.56 0.93 17.5 0.58 0.94 18.0 0.60 0.95 18.5 0.62 0.96 19.0 0.64 0.97 19.5 0.66 0.98 10.0 20.0 5-138 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 305 30 ms. At approximately four times pickup, the curve operating time is equal to the MRT and from then onwards the operating time remains at 200 ms. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-139...
  • Page 306 Configuring a composite curve with an increase in operating time at increased pickup multiples is not allowed. If this is attempted, the EnerVista software generates an error message and discards the proposed changes. 5.5.6.5 Standard recloser curves The following graphs display standard recloser curves available for the B30. 5-140 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 307 CHAPTER 5: SETTINGS SYSTEM SETUP Figure 5-65: Recloser curves GE101 to GE106 Figure 5-66: Recloser curves GE113, GE120, GE138, and GE142 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-141...
  • Page 308 SYSTEM SETUP CHAPTER 5: SETTINGS Figure 5-67: Recloser curves GE134, GE137, GE140, GE151, and GE201 Figure 5-68: Recloser curves GE131, GE141, GE152, and GE200 5-142 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 309 CHAPTER 5: SETTINGS SYSTEM SETUP Figure 5-69: Recloser curves GE133, GE161, GE162, GE163, GE164, and GE165 Figure 5-70: Recloser curves GE116, GE117, GE118, GE132, GE136, and GE139 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-143...
  • Page 310 SYSTEM SETUP CHAPTER 5: SETTINGS Figure 5-71: Recloser curves GE107, GE111, GE112, GE114, GE115, GE121, and GE122 Figure 5-72: Recloser curves GE119, GE135, and GE202 5-144 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 311: Bus

    If a given circuit cannot be connected to any other bus section different than the protected one, the FlexLogic constant "On" is recommended for the status signal. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-145...
  • Page 312: Flexlogic

    Figure 5-73: UR architecture overview The states of all digital signals used in the B30 are represented by flags (or FlexLogic operands, which are described later in this section). A digital “1” is represented by a set flag. Any external contact change-of-state can be used to block an element from operating, as an input to a control feature in a FlexLogic equation, or to operate a contact output.
  • Page 313 Counter 1 EQL The number of pulses counted is equal to the set number Lower than Counter 1 LO The number of pulses counted is below the set number Fixed Logic 1 Logic 0 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-147...
  • Page 314 Breaker 1 flashover element phase C has dropped out BKR 1 FLSHOVR DPO Breaker 1 flashover element has dropped out BKR 2 FLSHOVR Same set of operands as shown for BKR 1 FLSHOVR 5-148 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 315 BREAKER 1 ONE P OPEN Only one pole of breaker 1 is open BREAKER 1 OOS Breaker 1 is out of service BREAKER 2 to 6 Same set of operands as shown for BREAKER 1 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-149...
  • Page 316 ELEMENT: NEUTRAL OV1 PKP Neutral overvoltage element 1 has picked up Neutral overvoltage NEUTRAL OV1 DPO Neutral overvoltage element 1 has dropped out NEUTRAL OV1 OP Neutral overvoltage element 1 has operated 5-150 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 317 Phase B of phase undervoltage 1 has dropped out PHASE UV1 DPO C Phase C of phase undervoltage 1 has dropped out PHASE UV2 to 3 Same set of operands as shown for PHASE UV1 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-151...
  • Page 318 ↓ Teleprotection inputs/outputs TELEPRO INPUT 1-16 On Flag is set, Logic =1 TELEPRO INPUT 2-1 On Flag is set, Logic =1 ↓ ↓ TELEPRO INPUT 2-16 On Flag is set, Logic =1 5-152 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 319 Virt Op 1 Flag is set, logic=1 Virtual outputs Virt Op 2 Flag is set, logic=1 Virt Op 3 Flag is set, logic=1 ↓ ↓ Virt Op 96 Flag is set, logic=1 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-153...
  • Page 320 Communications source of the reset command RESET OP (OPERAND) Operand (assigned in the INPUTS/OUTPUTS  RESETTING menu) source of the reset command RESET OP (PUSHBUTTON) Reset key (pushbutton) source of the reset command 5-154 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 321 2 to 16 any input is ‘1’ 2 to 16 all inputs are ‘1’ 2 to 16 all inputs are ‘0’ NAND 2 to 16 any input is ‘0’ only one input is ‘1’ B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-155...
  • Page 322: Flexlogic Rules

    A timer operator (for example, "TIMER 1") or virtual output assignment (for example, " = Virt Op 1") can be used once only. If this rule is broken, a syntax error is declared. 5.6.3 FlexLogic evaluation Each equation is evaluated in the ascending order in which the parameters have been entered. 5-156 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 323: Flexlogic Example

    4, which is programmed in the contact output section to operate relay H1 (that is, contact output H1). Therefore, the required logic can be implemented with two FlexLogic equations with outputs of virtual output 3 and virtual output 4, shown as follows. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-157...
  • Page 324 It is generally easier to start at the output end of the equation and work back towards the input, as shown in the following steps. It is also recommended 5-158 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 325 It is now possible to check that this selection of parameters produces the required logic by converting the set of parameters into a logic diagram. The result of this process is shown in the figure, which is compared to the logic for virtual output 3 diagram as a check. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-159...
  • Page 326 Now check that the selection of parameters produce the required logic by converting the set of parameters into a logic diagram. The result is shown in the figure, which is compared to the logic for virtual output 4 diagram as a check. 5-160 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 327 Always test the logic after it is loaded into the relay, in the same way as has been used in the past. Testing can be simplified by placing an "END" operator within the overall set of FlexLogic equations. The equations are evaluated up B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-161...
  • Page 328: Flexlogic Equation Editor

    Range: Off, any analog actual value parameter  FLEXELEMENT 1 INPUT Range: SIGNED, ABSOLUTE  MODE: SIGNED FLEXELEMENT 1 COMP Range: LEVEL, DELTA  MODE: LEVEL FLEXELEMENT 1 Range: OVER, UNDER  DIRECTION: OVER 5-162 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 329 — This setting specifies the first (non-inverted) input to the FlexElement. Zero is assumed as the input if FLEXELEMENT 1 +IN this setting is set to “Off.” For proper operation of the element, at least one input must be selected. Otherwise, the element does not assert its output operands. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-163...
  • Page 330 Figure 5-82: FlexElement direction, pickup, and hysteresis In conjunction with the setting, the element can be programmed to provide two extra FLEXELEMENT 1 INPUT MODE characteristics, as shown in the following figure. 5-164 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 331 BUS DIFFERENTIAL RESTRAINING = maximum primary RMS value of the +IN and –IN inputs BASE CURRENT (CT primary for source currents, and bus reference primary current for bus differential currents) (Bus Diff Mag) B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-165...
  • Page 332: Non-Volatile Latches

    Autorecloser, until a deliberate interface action resets the latch. — This setting characterizes Latch 1 to be Set- or Reset-dominant. LATCH 1 TYPE — If asserted, the specified FlexLogic operands 'sets' Latch 1. LATCH 1 SET 5-166 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 333: Grouped Elements

    SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  SETTING GROUP 1  BUS DIFFERENTIAL See below     PHASE CURRENT See page 5-172    NEUTRAL CURRENT See page 5-184   B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-167...
  • Page 334: Bus Differential

    The biased bus differential function has a dual-slope operating characteristic (see figure below) operating in conjunction with saturation detection and a directional comparison principle (see the logic diagram in this section). 5-168 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 335 ). This setting determines the sensitivity of the relay for low current internal faults. The value chosen LOW BPNT needs to be high enough to accommodate the spurious differential current resulting from inaccuracy of the CTs operating B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-169...
  • Page 336 — This setting defines the drop-out time of the seal-in timer applied to the FlexLogic BUS ZONE 1 DIF SEAL-IN BUS 1 OP operand. More information on the bus zone differential settings can be found in the Application of Settings chapter. 5-170 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 337 CHAPTER 5: SETTINGS GROUPED ELEMENTS Figure 5-86: Bus zone 1 differential logic B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-171...
  • Page 338: Phase Current

     DIRECTIONAL 2 5.7.4.2 Inverse TOC curve characteristics The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I t standard curve shapes. This allows for simplified coordination with downstream devices.
  • Page 339 2.521 2.414 25.756 15.213 9.729 7.783 6.753 6.102 5.647 5.307 5.041 4.827 38.634 22.819 14.593 11.675 10.130 9.153 8.470 7.960 7.562 7.241 51.512 30.426 19.458 15.567 13.507 12.204 11.294 10.614 10.083 9.654 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-173...
  • Page 340 3.600 2.700 2.160 1.800 1.543 1.350 1.200 1.00 27.000 13.500 6.750 4.500 3.375 2.700 2.250 1.929 1.688 1.500 IEC Curve C 0.05 3.200 1.333 0.500 0.267 0.167 0.114 0.083 0.063 0.050 0.040 5-174 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 341 A to E = constants defined in the table = characteristic constant defined in the table = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”) RESET Table 5-28: GE type IAC inverse time curve constants IAC curve shape IAC Extreme Inverse 0.0040 0.6379...
  • Page 342 Multiplier Current ( I / I pickup (TDM) 10.0 0.01 0.44 0.25 0.11 0.06 0.04 0.03 0.02 0.02 0.01 0.01 0.10 4.44 2.50 1.11 0.63 0.40 0.28 0.20 0.16 0.12 0.10 5-176 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 343 = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed) RESET Recloser curves The B30 uses the FlexCurve feature to facilitate programming of 41 recloser curves. See the FlexCurves settings section earlier in this chapter for details. 5.7.4.3 Phase time overcurrent (ANSI 51P, IEC PTOC) SETTINGS ...
  • Page 344 (see the figure); the pickup level is calculated as Mvr times the setting. If the voltage restraint PHASE TOC1 PICKUP feature is disabled, the pickup level always remains at the setting value. 5-178 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 345 — Selects the signal source for the phase time overcurrent protection element. SIGNAL SOURCE — Selects how phase current input quantities are interpreted by the B30. Inputs can be selected as fundamental INPUT phasor magnitudes or total waveform RMS magnitudes as required by the application.
  • Page 346 PHASE IOC1 BLOCK A: Range: FlexLogic operand   PHASE IOC1 BLOCK C: Range: FlexLogic operand  PHASE IOC1 Range: Self-reset, Latched, Disabled  TARGET: Self-reset PHASE IOC1 Range: Disabled, Enabled  EVENTS: Disabled 5-180 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 347  DIRECTIONAL 1 FUNCTION: Disabled PHASE DIR 1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6  SOURCE: SRC 1 PHASE DIR 1 BLOCK: Range: FlexLogic operand  B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-181...
  • Page 348 (ECA) settings. 5-182 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 349 When set to "Yes," the directional element blocks the operation of any phase overcurrent element under directional control, when voltage memory expires. When set to "No," the directional element allows tripping of phase overcurrent elements under directional control. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-183...
  • Page 350: Neutral Current

    5.7.5.1 Menu SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEUTRAL CURRENT  NEUTRAL CURRENT  NEUTRAL TOC 1 See below      NEUTRAL TOC 6   5-184 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 351 — This setting selects the signal source for the neutral time overcurrent protection element. NEUTRAL TOC1 SIGNAL SOURCE — This setting selects how neutral current input quantities are interpreted by the B30. Inputs can be NEUTRAL TOC1 INPUT selected as fundamental phasor magnitudes or total waveform RMS magnitudes as required by the application.
  • Page 352 The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents resulting from: • System unbalances under heavy load conditions • Transformation errors of current transformers (CTs) during double-line and three-phase faults • Switch-off transients during double-line and three-phase faults 5-186 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 353: Ground Current

    SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  GROUND CURRENT  GROUND CURRENT  GROUND TOC1 See below      GROUND TOC6    GROUND IOC1 See page 5-189     GROUND IOC6   B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-187...
  • Page 354 — This setting selects the signal source for the ground time overcurrent protection element. GROUND TOC1 SIGNAL SOURCE — This setting selects how ground current input quantities are interpreted by the B30. Inputs can be GROUND TOC1 INPUT selected as fundamental phasor magnitudes or total waveform RMS magnitudes as required by the application.
  • Page 355 0.02 to 46 times the CT rating. This channel can be equipped with a standard or sensitive input. The conversion range of a sensitive channel is from 0.002 to 4.6 times the CT rating. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-189...
  • Page 356: Breaker Failure (Ansi 50Bf)

    BF1 USE TIMER 3: Range: Yes, No  BF1 TIMER 3 PICKUP Range: 0.000 to 65.535 s in steps of 0.001  DELAY: 0.000 s φ BF1 BKR POS1 A/3P: Range: FlexLogic operand  5-190 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 357 FlexLogic timer, set longer than any breaker failure timer, whose output operand is selected to block the breaker failure scheme. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-191...
  • Page 358 FlexLogic operands that initiate tripping required to clear the faulted zone. The trip output can be sealed-in for an adjustable period. • Target message indicating a failed breaker has been declared • Illumination of the faceplate Trip LED (and the Phase A, B, or C LED, if applicable) 5-192 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 359 Neutral current supervision is used only in the three phase scheme to provide increased sensitivity. This setting is valid only for three-pole tripping schemes. — If set to "Yes," the early path is operational. BF1 USE TIMER 1 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-193...
  • Page 360 In microprocessor relays this time is not significant. In B30 relays, which use a Fourier transform, the calculated current magnitude ramps-down to zero one power frequency cycle after the current is interrupted, and this lag needs to be included in the overall margin duration, as it occurs after current interruption.
  • Page 361 Upon operation of the breaker failure element for a single pole trip command, a three-pole trip command needs to be given via output operand BKR FAIL 1 TRIP Figure 5-98: Single-pole breaker failure initiate logic B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-195...
  • Page 362 GROUPED ELEMENTS CHAPTER 5: SETTINGS Figure 5-99: Single-pole breaker failure, timers logic 5-196 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 363 CHAPTER 5: SETTINGS GROUPED ELEMENTS Figure 5-100: Three-pole breaker failure, initiate logic B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-197...
  • Page 364 GROUPED ELEMENTS CHAPTER 5: SETTINGS Figure 5-101: Three-pole breaker failure, timers logic 5-198 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 365: Voltage Elements

    The undervoltage delay setting defines the family of curves shown as follows. Eq. 5-15 where T = operating time D = undervoltage delay setting (D = 0.00 operates instantaneously) V = secondary voltage applied to the relay = pickup level pickup B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-199...
  • Page 366 This can be applied for bus configurations of up to five feeders with the voltage signal available. If applied, use the undervoltage function to supervise the main differential output with an AND gate in the FlexLogic equation before driving the output contact. 5-200 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 367 Range: 0.00 to 600.00 s in steps of 0.01  DELAY: 1.00 s PHASE OV1 BLOCK: Range: FlexLogic Operand  PHASE OV1 Range: Self-reset, Latched, Disabled  TARGET: Self-reset PHASE OV1 Range: Disabled, Enabled  EVENTS: Disabled B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-201...
  • Page 368 Range: 0.00 to 600.00 s in steps of 0.01  DELAY: 1.00 s NEUTRAL OV1 BLOCK: Range: FlexLogic operand  NEUTRAL OV1 TARGET: Range: Self-reset, Latched, Disabled  Self-reset NEUTRAL OV1 EVENTS: Range: Disabled, Enabled  Disabled 5-202 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 369 Range: Disabled, Enabled  Disabled The B30 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM is the per-unit (pu) base used when setting the SETUP ...
  • Page 370: Control Elements

    The trip bus element allows aggregating outputs of protection and control elements without using FlexLogic and assigning them a simple and effective manner. Each trip bus can be assigned for either trip or alarm actions. Simple trip conditioning such as latch, delay, and seal-in delay are available. 5-204 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 371 TRIP BUS 1 RESET RESET OP operand is pre-wired to the reset gate of the latch, As such, a reset command from the front panel interface or via communications resets the trip bus output. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-205...
  • Page 372: Setting Groups

    Prevents the active setting group from changing when the selected FlexLogic operand is "On." This SETTING GROUPS BLK — can be useful in applications where it is undesirable to change the settings under certain conditions, such as during a control sequence. 5-206 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 373: Selector Switch

    RANGE: 7 SELECTOR 1 TIME-OUT: Range: 3.0 to 60.0 s in steps of 0.1  5.0 s SELECTOR 1 STEP-UP: Range: FlexLogic operand  SELECTOR 1 STEP-UP Range: Time-out, Acknowledge  MODE: Time-out B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-207...
  • Page 374 (“Acknowledge” mode). When the new position is applied, the relay displays the SELECTOR SWITCH 1: POSITION Z IN USE message. Typically, a user-programmable pushbutton is configured as the stepping up control input. 5-208 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 375 (that is, the three-bit input is not available (0,0,0) or out of range), then the selector switch output is set to position 0 (no output operand selected) and an alarm is established ( SELECTOR 1 PWR ALARM B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-209...
  • Page 376 The selector position pre-selected via the three-bit control input has not been confirmed before the time The following figures illustrate the operation of the selector switch. In these diagrams, “T” represents a time-out setting. 5-210 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 377 CHAPTER 5: SETTINGS CONTROL ELEMENTS Figure 5-110: Time-out mode B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-211...
  • Page 378 1 through 3. The pre-selected setting group is to be applied automatically after five seconds of inactivity of the control inputs. When the relay powers up, it is to synchronize the setting group to the three-bit control input. 5-212 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 379 SETTINGS  PRODUCT menu: SETUP  USER-PROGRAMMABLE PUSHBUTTONS  USER PUSHBUTTON 1 : “Self-reset” PUSHBUTTON 1 FUNCTION : “0.10 s” PUSHBUTTON 1 DROP-OUT TIME The figure shows the logic for the selector switch. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-213...
  • Page 380: Digital Elements

    Range: Disabled, Enabled  PICKUP LED: Enabled DIG ELEM 1 BLOCK: Range: FlexLogic operand  DIGITAL ELEMENT 1 Range: Self-reset, Latched, Disabled  TARGET: Self-reset DIGITAL ELEMENT 1 Range: Disabled, Enabled  EVENTS: Disabled 5-214 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 381 In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact that is open when the breaker is open (see figure). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must include the breaker position. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-215...
  • Page 382 Using the contact input settings, this input is given an ID name, for example, “Cont Ip 1," and is set “On” when the breaker is closed. The settings to use digital element 1 to monitor the breaker trip circuit are indicated (EnerVista example shown). 5-216 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 383: Digital Counters

     COUNTER 1 COUNTER 1 Range: Disabled, Enabled  FUNCTION: Disabled  COUNTER 1 NAME: Range: up to 12 alphanumeric characters  Counter 1 COUNTER 1 UNITS: Range: up to six alphanumeric characters  B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-217...
  • Page 384 If control power is interrupted, the accumulated and frozen values are saved into non-volatile memory during the power-down operation. 5-218 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 385: Monitoring Elements

     BREAKER RESTRIKE 1 See page 5-228     BREAKER RESTRIKE 6    CT TROUBLE ZONE 1 See page 5-230    CT TROUBLE ZONE 2   B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-219...
  • Page 386 In three-pole tripping applications, configure the same operand to initiate arcing current calculations for poles A, B, and C of the breaker. In single-pole tripping applications, configure per-pole tripping operands to initiate the calculations for the poles that are actually tripped. 5-220 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 387 -cycle) and AMP MAX (kA) values of the last event. — This setting specifies the maximum symmetrical interruption rating of the circuit breaker. BKR 1 INTERUPTION RATING Figure 5-117: Arcing current measurement B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-221...
  • Page 388 CONTROL ELEMENTS CHAPTER 5: SETTINGS Figure 5-118: Breaker arcing current logic 5-222 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 389 (contact input indicating the breaker status is off), and no flashover current is flowing. A contact showing the breaker status must be provided to the relay. The voltage difference is not considered as a condition for open breaker in this part of the logic. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-223...
  • Page 390 This application does not require detection of breaker status via a 52a contact, as it uses a voltage difference larger than setting. However, monitoring the breaker contact ensures scheme stability. BRK 1 FLSHOVR DIFF V PKP 5-224 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 391 (all line breakers open), to well above the maximum line (feeder) load (line/feeder connected to load). B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-225...
  • Page 392 A six-cycle time delay applies after the selected FlexLogic operand resets. — This setting specifies the time delay to operate after a pickup condition is detected. BRK FLSHOVR PKP DELAY 5-226 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 393 CHAPTER 5: SETTINGS CONTROL ELEMENTS Figure 5-119: Breaker flashover logic B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-227...
  • Page 394 The user can add counters and other logic to facilitate the decision making process as to the appropriate actions upon detecting a single restrike or a series of consecutive restrikes. 5-228 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 395 1/8th of the power cycle. — Enables/disables high-frequency (HF) pattern detection when breaker restrike occurs. BREAKER RESTRIKE 1 HF DETECT High-frequency pattern is typical for capacitor bank, cables, and long transmission lines applications. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-229...
  • Page 396 CT TROUBLE ZONE 1 DELAY setting, CT Trouble is declared for the given phase by setting the appropriate FlexLogic output operand. 5-230 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 397 Range: 0 to 1000 min. in steps of 1  RESET TIME: 20 min THERM PROT 1 RESET: Range: FlexLogic operand  THERM PROT 1 BLOCK: Range: FlexLogic operand  THERMAL PROTECTION 1 Range: Self-reset, Latched, Disabled  TARGET: Self-reset B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-231...
  • Page 398 The reset time of the thermal overload protection element is also time delayed using following formula: Eq. 5-18 where τ = thermal protection trip time constant = a minimum reset time setting 5-232 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 399 IEC255-8 cold curve or hot curve equations op(In) is the reset time calculated at index n as per the reset time equation rst(In) B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-233...
  • Page 400: Inputs/Outputs

    The figure shows the logic for the thermal overload protection element. Figure 5-125: Thermal overload protection logic 5.9 Inputs/outputs 5.9.1 Contact inputs SETTINGS  INPUTS/OUTPUTS  CONTACT INPUTS  CONTACT INPUTS   CONTACT INPUT H5a   5-234 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 401 The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user-settable debounce time in order for the B30 to validate the new contact state. In the following figure, the debounce time is set at 2.5 ms;...
  • Page 402: Virtual Inputs

    VIRTUAL INPUT 1 Range: Disabled, Enabled  FUNCTION: Disabled  VIRTUAL INPUT 1 ID: Range: up to 20 alphanumeric characters  Virt Ip 1 VIRTUAL INPUT 1 Range: Self-Reset, Latched  TYPE: Latched 5-236 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 403: Contact Outputs

    Range: FlexLogic operand  CONTACT OUTPUT H1 Range: Disabled, Enabled  EVENTS: Enabled A contact inputs and outputs are digital signals associated with connections to hard-wired contacts. Wet and dry contacts are supported. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-237...
  • Page 404 On power up, the relay reads positions of the latching contacts from the hardware before executing any other functions of the relay (such as protection and control features or FlexLogic). 5-238 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 405 The relay is to be controlled from virtual outputs: VO1 to operate and VO2 to reset. Program the Latching Outputs by making the following changes in the SETTINGS  INPUTS/OUTPUTS  CONTACT menus (assuming an H4L module): OUTPUTS  CONTACT OUTPUT H1a CONTACT OUTPUT H1c B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-239...
  • Page 406 Write the following FlexLogic equation (EnerVista example shown). Program the Latching Outputs by making the following changes in the SETTINGS  INPUTS/OUTPUTS  CONTACT menu (assuming an H4L module): OUTPUTS  CONTACT OUTPUT H1a 5-240 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 407: Virtual Outputs

    DIRECT INPUT 1 Range: 0 to 16  DEVICE ID: 0 DIRECT INPUT 1 Range: 0 to 32  BIT NUMBER: DIRECT INPUT 1 Range: On, Off, Latest/On, Latest/Off  DEFAULT: Off B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-241...
  • Page 408 UR-series chassis. The problem is solved by adding an extra UR-series IED, such as the C30, to satisfy the additional inputs/outputs and programmable logic requirements. The figure shows that two IEDs are connected via single-channel digital communication cards. 5-242 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 409 OP" UR IED 1: : "2" DIRECT INPUT 7 DEVICE ID : "3" DIRECT INPUT 7 BIT NUMBER : select "On" for security, select "Off" for dependability DIRECT INPUT 7 DEFAULT STATE B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-243...
  • Page 410 : "2" (this is a message from IED 2) DIRECT INPUT 5 BIT NUMBER : "2" DIRECT INPUT 6 DEVICE ID : "4" (effectively, this is a message from IED 3) DIRECT INPUT 6 BIT NUMBER UR IED 3: 5-244 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 411: Teleprotection

    The teleprotection function must be enabled to utilize the inputs. 5.9.7.2 Teleprotection inputs SETTINGS  INPUTS/OUTPUTS  TELEPROTECTION  TELEPROT INPUTS  TELEPROT INPUTS TELEPROT INPUT 1-1 Range: Off, On, Latest/Off, Latest/On  DEFAULT: Off   B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-245...
  • Page 412 (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end). On three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of channel failure between any pair of relays. 5-246 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 413: Transducer Inputs/Outputs

    VALUE: 0.000 The B30 is provided with optional DCmA capability. This feature is specified as an option at the time of ordering. See the Order Codes section in chapter 2 for details. Hardware and software are provided to receive signals from external transducers and to convert these signals into a digital format for use as required.
  • Page 414: Rtd Inputs

    FlexElements, the operate level is scaled to a base of 100°C. For example, a trip level of 150°C is achieved by setting the operate level at 1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output contact directly. 5-248 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 415: Dcma Outputs

    DCMA OUTPUT H1 Range: –90.000 to 90.000 pu in steps of 0.001  MIN VAL: 0.000 pu DCMA OUTPUT H1 Range: –90.000 to 90.000 pu in steps of 0.001  MAX VAL: 1.000 pu B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-249...
  • Page 416 — This setting allows selection of the output range. Each DCmA channel can be set independently DCMA OUTPUT H1 RANGE to work with different ranges. The three most commonly used output ranges are available. 5-250 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 417 The voltage is to be monitored in the range from 70% to 110% of nominal. The minimum and maximum positive-sequence voltages to be monitored are: Eq. 5-26 The base unit for voltage (see the FlexElements section in this chapter for additional details) is: Eq. 5-27 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-251...
  • Page 418: Testing

     FUNCTION: Disabled The B30 provides a test facility to verify the functionality of contact inputs and outputs, some communication functions and the phasor measurement unit (where applicable), using simulated conditions. The test mode can be in any of three states: Disabled, Isolated, or Forcible.
  • Page 419: Test Mode Forcing

      When in Forcible mode, the operand selected by the setting dictates further response of the B30 to TEST MODE FORCING testing conditions, as described in the following two sections. The test mode state is indicated on the relay faceplate by a combination of the Test Mode LED indicator, the In-Service LED indicator, and by the critical fail relay, as shown in the following table.
  • Page 420: Force Contact Outputs

    While the selected operand is Off, the output behaves as it does when in service. On restart, the setting and the force contact input and force contact output settings revert to TEST MODE FORCING their default states. 5-254 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 421: Actual Values

      RxGOOSE See page 6-6   STATUS  RxGOOSE See page 6-6   STATISTICS  DIGITAL COUNTERS See page 6-6    SELECTOR SWITCHES See page 6-7   B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 422  TRANSDUCER I/O See page 6-21    RTD INPUTS  ACTUAL VALUES  USER PROGRAMMABLE See page 6-21   RECORDS  FAULT REPORTS  EVENT RECORDS See page 6-22    B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 423: Front Panel

    The front panel can be viewed and used in the EnerVista software, for example to view an error message displayed on the front panel. To view the front panel in EnerVista software: Click Actual Values > Front Panel. Figure 6-1: Front panel use in the software (C60 shown) B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 424: Status

    Range: On, Off  STATUS: Off The B30 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time of ordering. See the Order Codes section of chapter 2 for details. 6.3.4 RxGOOSE DPS inputs ACTUAL VALUES ...
  • Page 425: Teleprotection Inputs

    CHAPTER 6: ACTUAL VALUES STATUS The B30 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time of ordering. See the Order Codes section of chapter 2 for details. 6.3.5 Teleprotection inputs ACTUAL VALUES ...
  • Page 426: Rxgoose Status

     Offline The B30 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time of ordering. See the Order Codes section of chapter 2 for details. actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE All RxGOOSE Online Input.
  • Page 427: Selector Switches

     No Signal Pdelay), Synchronized PORT 3 PTP STATE: Range: Disabled, No Signal, Calibrating, Synch’d (No  No Signal Pdelay), Synchronized PTP - IRIG-B DELTA: Range: -500,000,000 to +500,000,000 ns  500000000 ns B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 428: Direct Inputs

    The UNRETURNED MSG COUNT CRC FAIL values can be cleared using the command. COUNT CLEAR DIRECT I/O COUNTERS values represent the state of each direct input. DIRECT INPUT 1 DIRECT INPUT (32) B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 429: Direct Devices Status

    STATUS: n/a CHANNEL 2 LOST Range: 1 to 65535 in steps of 1  PACKETS: VALIDITY OF CHANNEL Range: n/a, FAIL, OK  CONFIGURATION: FAIL The status information for two channels is shown here. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 430: Remaining Connection Status

    Range: 0 to 4G, blank if PRP disabled  Mismatches Port B: Range: 0 to 4G, blank if PRP disabled  Total Errors: Range: 0 to 4G, blank if PRP disabled  6-10 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 431: Metering

    CHAPTER 6: ACTUAL VALUES METERING The B30 is provided with optional PRP capability. This feature is specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for details. is a counter for total messages received (either from DANPs or from SANs) on Port A.
  • Page 432 6.4.1.2 UR convention for measuring phase angles All phasors calculated by URs and used for protection, control and metering functions are rotating phasors that maintain the correct phase angle relationships with each other at all times. 6-12 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 433 For display and oscillography purposes the phase angles of symmetrical components are referenced to a common reference as described in the previous sub-section. WYE-connected instrument transformers • ABC phase rotation: • ACB phase rotation: The above equations apply to currents as well. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 6-13...
  • Page 434 * The power system voltages are phase-referenced – for simplicity – to V and V , respectively. This, however, is a relative matter. It is important to remember that the B30 displays are always referenced as specified under SETTINGS  SYSTEM SETUP  POWER SYSTEM  FREQUENCY AND PHASE REFERENCE The example above is illustrated in the following figure.
  • Page 435: Bus Zone

    6.4.3.2 Phase current metering ACTUAL VALUES  METERING  SOURCE SRC 1  PHASE CURRENT  PHASE CURRENT SRC 1 RMS Ia: 0.000   SRC 1 b: 0.000 c: 0.000 A B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 6-15...
  • Page 436 SRC 1 RMS Vag:   SRC 1 0.00 V SRC 1 RMS Vbg:  0.00 V SRC 1 RMS Vcg:  0.00 V SRC 1 PHASOR Vag:  0.000 V 0.0° 6-16 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 437 SRC 1 REAL POWER  φa: 0.000 W SRC 1 REAL POWER  φb: 0.000 W SRC 1 REAL POWER  φc: 0.000 W SRC 1 REACTIVE PWR  3φ: 0.000 var B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 6-17...
  • Page 438 S = V x Î x Î x Î Eq. 6-1 When VTs are configured in delta, the B30 does not calculate power in each phase and three-phase power is measured as S = V x Î x Î Eq. 6-2...
  • Page 439 These parameters can be monitored to reduce supplier demand penalties or for statistical metering purposes. Demand calculations are based on the measurement type selected in the SETTINGS  PRODUCT SETUP B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 6-19...
  • Page 440: Tracking Frequency

    +IN and –IN inputs. FREQUENCY = 1 Hz BASE PHASE ANGLE ϕ = 360 degrees (see the UR angle referencing convention) BASE POWER FACTOR = 1.00 BASE RTDs BASE = 100°C 6-20 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 441: Rxgoose Analogs

     0.000 The B30 is provided with optional GOOSE communications capability. This feature is specified as a software option at the time of ordering. See the Order Codes section of chapter 2 for details. The RxGOOSE Analog values display in this menu. The RxGOOSE Analog values are received via IEC 61850 GOOSE messages sent from other devices.
  • Page 442: Event Records

    The event records are also viewable in the software and in a web browser. The figure shows the event records in the software. To view them in a web browser, enter the IP address of the device. Figure 6-5: Event records viewed in EnerVista software 6-22 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 443: Oscillography

    BKR 1 ACC ARCING AMP  φC: 0.00 kA2-cyc BKR 1 OPERATING TIME  φA: 0 ms BKR 1 OPERATING TIME  φB: 0 ms BKR 1 OPERATING TIME  φC: 0 ms B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 6-23...
  • Page 444: Product Information

    Range: YYYY/MM/DD HH:MM:SS  OPERATING TIME: Range: operating time in HH:MM:SS  0:00:00 CT/ VT ADVANCED DIAG Range: Yes, No  ACTIVE: No LAST SETTING CHANGE: Range: YYYY/MM/DD HH:MM:SS  1970/01/01 23:11:19 6-24 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 445: Firmware Revisions

    Range: YYYY/MM/DD HH:MM:SS  2016/09/15 16:41:32 Date and time when the FPGA was built. The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been installed. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 6-25...
  • Page 446 PRODUCT INFORMATION CHAPTER 6: ACTUAL VALUES 6-26 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 447: Commands And Targets

    The commands menu contains relay directives intended for operations personnel. All commands can be protected from unauthorized access via the command password; see the Security section of chapter 5 for details. The following flash message appears after successfully command entry. COMMAND EXECUTED B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 448: Virtual Inputs

    This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a command setting to “Yes” and pressing the key. After clearing data, the command setting automatically reverts to ENTER “No.” B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 449: Set Date And Time

    PERFORM LAMP TEST — This command causes the relay to scan the backplane for the hardware modules and update the UPDATE ORDER CODE order code to match. If an update occurs, the following message displays. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 450: Targets Menu

    Although the diagnostic information is cleared before the B30 is shipped from the factory, the user can want to clear the diagnostic information for themselves under certain circumstances. For example, you clear diagnostic information after replacement of hardware.
  • Page 451: Target Messages

    A target enables the EnerVista UR Setup software to monitor automatically and display the status of any active target messages of all the devices inserted into that site. Each B30 element with a TARGET setting has a target message that when activated by its element is displayed in sequence with any other currently active target messages in the menu.
  • Page 452 Contact Factory (xxx) • Latched target message: Yes. • Description of problem: One or more installed hardware modules is not compatible with the B30 order code. • How often the test is performed: Module dependent. • What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed module (for example, F8L).
  • Page 453 Description of problem: A bad IRIG-B input signal has been detected. • How often the test is performed: Monitored whenever an IRIG-B signal is received. • What to do: Ensure the following: – The IRIG-B cable is properly connected. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 454 How often the test is performed: On any setting changes, when new settings were written to device. • What to do: Verify that the setting change was legitimate and essential for proper functioning of the protection and control system. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 455 Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C). • How often the test is performed: Every hour. • What to do: Remove the B30 from service and install in a location that meets operating temperature standards. UNEXPECTED RESTART: Press “RESET” key •...
  • Page 456 Description of problem: There is a problem with the Compact Flash memory in the CPU module. • How often the test is performed: On relay power-up and afterwards once every 24 hours. 7-10 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 457 AC bank crosschecking setting to none, until the Process Bus Failure clears. Once the problem AC bank has been identified, the values from each of the two Bricks can be examined individually by temporarily mapping each to an AC bank with a single origin. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 7-11...
  • Page 458 Brick output failing to respond to an output command can only be detected while the command is active, and so in this case the target is latched. A latched target can be unlatched by pressing the faceplate reset key if the command has ended, however the output can still be non-functional. 7-12 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 459: Application Of Settings

    It is also assumed that the CTs have been selected without considering a B30 application, but the UR settings are to be calculated for proper relay application. The CT data used in this example are kept to a minimum and in a generic form. The CT data does not reflect any particular notation or national standards.
  • Page 460: Sample Busbar And Data

    Table 8-2: Basic CT data Ratio (Ω) Leads (m) CTsec CT-1 600:5 0.34 CT-2 600:5 0.34 CT-3 1200:5 0.64 CT-4 1000:5 0.54 CT-5, CT-6 1000:5 0.54 CT-7, CT-8 1200:5 0.64 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 461: Zoning And Dynamic Bus Replica

    To provide the bus differential zoning as shown in the figures, eight currents need to be measured. Consequently, the protection cannot be accomplished by one B30. However, as each bus has not more than six connections, two B30s can be used.
  • Page 462: South Bus Zone

    FlexLogic “On” constant for the status • CT-7 currents are configured as SRC 5 and used as the source 1E of the bus differential zone 1 together with the FlexLogic “On” constant for the status B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 463: Biased Characteristic Breakpoints

    CT The total burden resistance depends on both the fault type and connection of the CTs. For single-line-to-ground faults and CTs connected in Wye, the burden resistance is calculated as: Eq. 8-2 where B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 464: High Breakpoint

    Assuming 0.003 Ω/m lead resistance and approximating the B30 input resistance for the 5A input CTs as 0.2 VA / (5 A) 0.008 Ω, the limits of the linear operation of the CTs have been calculated and presented in the Limits of Linear Operations of the CTs table.
  • Page 465: Slopes And High Set Threshold

    ), where ω is radian system frequency (2πf). If the above condition is violated, CT time-to-saturate for a full DC saturation can be estimated as follows. The CT saturation factor K capability curve is defined as Eq. 8-5 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 466 • Method 1 — Download the "CT Time-to-Saturate Estimator.xlsm" spreadsheet from the GE Multilin web site, located under Support > Support Documents > B30 Bus Differential System. Enter the required system and CT parameters to obtain the CT time-to-saturate. •...
  • Page 467: External Faults On C-2

    8.4.4 External faults on C-3 The following table presents the results of analysis of an external fault on circuit C-3 (C-3 is connected to the North bus; C- 4 and C-5 are connected to the South bus). B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 468: External Faults On C-4

    DC components and can generate a spurious differential signal for both the North and South bus relays depending on the bus configuration. The saturation does not occur before 9.45 ms and is detected by the Saturation Detector. 8-10 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 469: Bus Differential Settings

    HIGH BPNT 8.96 None of the CTs saturate for AC currents below 8.96 pu. The DC component, however, can saturate some CTs even for currents below 8.96 pu. The B30 copes with saturation using the current directional principle. HIGH SET 5.94...
  • Page 470: Enhancing Relay Performance

    CTs in any particular bus configuration. 8-12 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 471: Theory Of Operation

    9.1.1 Bus differential protection The figure shows that input currents defining (through the dynamic bus replica) the bus differential zone are received by the B30 from current transformers (CTs) associated with the power system. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 472 The output logic (Block 11) combines the differential, directional, and saturation flags into the biased differential operation flag. The applied logic enhances performance of the relay while keeping an excellent balance between dependability/ speed and security. See the Output Logic and Examples section. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 473: Dynamic Bus Replica

    This mechanism is referred to as a dynamic bus replica. The dynamic bus zone is programmed as a number of ‘source-status’ pairs. The Sources feature of the B30 is a convenient and flexible mechanism for associating input currents and voltages with protection and control elements.
  • Page 474: Ct Ratio Matching

    9.2.2 CT ratio matching The B30 allows for using CTs with various rated secondary currents and transformation ratios. Scaling to a common base is performed internally by the relay. The maximum allowable ratio mismatch is 32:1. For proper setting of the differential characteristic, it is imperative to understand the common base used by the relay.
  • Page 475: Differential Principle

    Figure 9-3: Biased operating characteristic The higher slope used by the B30 acts as an actual percentage bias regardless of the value of the restraining signal. This is so because the boundary of the operating characteristic in the higher slope region is a straight line intersecting the origin of the ‘differential - restraining’...
  • Page 476: Differential And Restraining Currents

    LOW BPNT 9.3.3 Enhanced security To enhance the performance of the B30, the differential characteristic is divided into two regions having diverse operating modes, as shown in following figure. The first region applies to comparatively low differential currents and has been introduced to deal with CT saturation on low-current external faults.
  • Page 477: Directional Principle

    The B30 operates in the 2-out-of-2 mode in the first region of the differential characteristic. Both differential and directional principles (Differential Principle and Directional Principle) must confirm an internal fault in order for the biased differential element to operate.
  • Page 478 Figure 9-6: Directional principle operation during internal faults The B30 implementation calculates the maximum angle for the considered currents and compares it against a fixed threshold of 90°. The flag indicating whether the directional protection principle is satisfied is available as the FlexLogic operand BUS 1(2) DIR.
  • Page 479: Saturation Detector

    9.5.1 CT saturation detection The saturation detector of the B30 takes advantage of the fact that any CT operates correctly for a short period of time, even under very large primary currents that would subsequently cause a very deep saturation. As a result, in the case of an external fault, the differential current stays very low during the initial period of linear operation of the CTs while the restraining signal develops rapidly.
  • Page 480: Output Logic And Examples

    For high differential signals, the directional principle is included only if demanded by the saturation detector (dynamic 1- out-of-2 / 2-out-of-2 mode). Typically, the directional principle is slower, and by avoiding using it when possible, the B30 gains speed.
  • Page 481: Internal And External Fault Example

    The first of the following figures presents the bus currents and the most important logic signals for the case of an external fault. Despite very fast and severe CT saturation, the B30 remains stable. The second figure presents the same signals but for the case of an internal fault. The B30 trips in 10 ms (fast form-C output contact).
  • Page 482 OUTPUT LOGIC AND EXAMPLES CHAPTER 9: THEORY OF OPERATION Figure 9-10: External fault example 9-12 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 483 CHAPTER 9: THEORY OF OPERATION OUTPUT LOGIC AND EXAMPLES Figure 9-11: Internal fault example B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 9-13...
  • Page 484 OUTPUT LOGIC AND EXAMPLES CHAPTER 9: THEORY OF OPERATION 9-14 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 485: Maintenance

    UR Family Communications Guide for the entries. The upper part of the window displays values. The lower part of the window is for factory service use. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 10-1...
  • Page 486 Float — A numbering system with no fixed number of digits before or after the decimal point. An example is 0.000000. Binary — A numbering system using 0 and 1. An example is 0000-0000-0000-0000. Entries are not saved when closing the window. 10-2 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 487: General Maintenance

    GENERAL MAINTENANCE 10.2 General maintenance The B30 requires minimal maintenance. As a microprocessor-based relay, its characteristics do not change over time. Expected service life is 20 years for UR devices manufactured June 2014 or later when applied in a controlled indoors environment and electrical conditions within specification.
  • Page 488: Cybersentry Security Event Files

    15 = Role Log in 10.3.1.2 Setting changes file The SETTING_CHANGES.LOG file stores all the setting changes. A total of 1024 events are stored in a circular buffer in non- volatile memory. 10-4 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 489: Compare Settings

    Comparison Report: Sequential File 1, File 2 Layout — When disabled (default), the report shows only what differs, as shown in the previous figure. When enabled, the report indicates differences by device. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 10-5...
  • Page 490: Back Up And Restore Settings

    LED operands are not modeled. If the block setting of the Phase IOC is configured with LED operands, its displays as TBD in IID and CID files, the web interface, or in an MMS client. 10-6 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 491 Hqve this option enabled when you want to keep the IID file from the UR device instead of from another tool. The location of the file is C:\ProgramData\GE Power Management\urpc\Offline, for example.
  • Page 492: Restore Settings

    IID type backup was created either using the EnerVista UR Setup software in online mode or by using any of the supported file transfer protocols. Note that TFTP cannot be used here, as TFTP "put" mode is disabled for security reasons. 10-8 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 493 Manually copy the remaining settings, outlined as follows. To restore settings from an IID file using EnerVista software: In Windows, make a copy the IID file with a cid extension. Connect to the device in the Online Window area. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 10-9...
  • Page 494: Upgrade Software

    UR 7.4 can be used to access multiple UR devices that have version 7.4x, 7.2x, and 6.0x firmware installed. Existing installations do not need to be uninstalled before upgrade. You can also downgrade the software; use the same procedure. 10-10 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 495: Upgrade Firmware

    If upgrading both EnerVista software and B30 firmware, upgrade the software first. The firmware of the B30 device can be upgraded, locally or remotely, using the EnerVista software. Upgrades are possible for the same release (such as 7.01 to 7.02) and from one firmware version to another (such as 7.2 to 7.3).
  • Page 496: Replace Module

    To avoid damage to the equipment, use proper electrostatic discharge protection (for example, a static strap) when coming in contact with modules while the relay is energized. 10-12 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 497 Open the enhanced faceplate to the left once the thumb screw has been removed. This allows for easy access of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the B30. Figure 10-10: Modules inside relay with front cover open (enhanced faceplate) The standard faceplate can be opened to the left once the black plastic sliding latch on the right side has been pushed up, as shown below.
  • Page 498: Battery

    Replace the battery with the identical make and model. For example, do not use a rechargeable battery. Observe the + and - polarity of the battery and replace it with the same polarity as marked on the battery holder. 10-14 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 499: Dispose Of Battery

    Batteriet er forsynet med indgraveret symboler for hvad batteriet indeholder: kadmium (Cd), bly (Pb) og kviksølv (Hg). Europæiske brugere af elektrisk udstyr skal aflevere kasserede produkter til genbrug eller til leverandøren. Yderligere oplysninger findes på webstedet www.recyclethis.info. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 10-15...
  • Page 500 (Cd), ólom (Pb) vagy higany (Hg) tartalomra utaló betűjelzés. A hulladék akkumulátor leadható a termék forgalmazójánál új akkumulátor vásárlásakor, vagy a kijelölt elektronikai hulladékudvarokban. További információ a www.recyclethis.info oldalon. 10-16 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 501 (Cd), chumbo (Pb), ou o mercúrio (hg). Para uma reciclagem apropriada envie a bateria para o seu fornecedor ou para um ponto de recolha designado. Para mais informação veja: www.recyclethis.info. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 10-17...
  • Page 502: Uninstall And Clear Files And Data

    +86-21-2401-3208 India +91 80 41314617 From GE Part Number 1604-0021-A1, GE Publication Number GEK-113574. 10.10 Uninstall and clear files and data The unit can be decommissioned by turning off power to the unit and disconnecting the wires to it. Files can be cleared after uninstalling the EnerVista software or UR device, for example to comply with data security regulations.
  • Page 503: Repairs

    Customers are responsible for shipping costs to the factory, regardless of whether the unit is under warranty. • Fax a copy of the shipping information to the GE Grid Solutions service department in Canada at +1 905 927 5098. Use the detailed return procedure outlined at https://www.gegridsolutions.com/multilin/support/ret_proc.htm...
  • Page 504: Disposal

    Other than the battery, there are no special requirements for disposal of the unit at the end its service life. For customers located in the European Union, dispose of the battery as outlined earlier. To prevent non-intended use of the unit, remove the modules, dismantle the unit, and recycle the metal when possible. 10-20 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 505: A.1 Flexanalog Items

    SRC 1 Ic RMS Amps Source 1 phase C current RMS 6150 SRC 1 In RMS Amps Source 1 neutral current RMS 6152 SRC 1 Ia Mag Amps Source 1 phase A current magnitude B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 506 SRC 3 In RMS Amps Source 3 neutral current RMS 6280 SRC 3 Ia Mag Amps Source 3 phase A current magnitude 6282 SRC 3 Ia Angle Degrees Source 3 phase A current angle B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 507 SRC 5 Ia Mag Amps Source 5 phase A current magnitude 6410 SRC 5 Ia Angle Degrees Source 5 phase A current angle 6411 SRC 5 Ib Mag Amps Source 5 phase B current magnitude B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 508 SRC 1 Vbg Mag Volts Source 1 phase BG voltage magnitude 6667 SRC 1 Vbg Angle Degrees Source 1 phase BG voltage angle 6668 SRC 1 Vcg Mag Volts Source 1 phase CG voltage magnitude B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 509 SRC 2 V_2 Mag Volts Source 2 negative-sequence voltage magnitude 6763 SRC 2 V_2 Angle Degrees Source 2 negative-sequence voltage angle 6784 SRC 3 Vag RMS Volts Source 3 phase AG voltage RMS B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 510 6878 SRC 4 Vx RMS Volts Source 4 auxiliary voltage RMS 6880 SRC 4 Vx Mag Volts Source 4 auxiliary voltage magnitude 6882 SRC 4 Vx Angle Degrees Source 4 auxiliary voltage angle B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 511 SRC 6 Vca RMS Volts Source 6 phase CA voltage RMS 6997 SRC 6 Vab Mag Volts Source 6 phase AB voltage magnitude 6999 SRC 6 Vab Angle Degrees Source 6 phase AB voltage angle B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 512 7227 SRC 2 Phase C PF Source 2 phase C power factor 7232 SRC 3 P Watts Source 3 three-phase real power 7234 SRC 3 Pa Watts Source 3 phase A real power B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 513 SRC 5 Phase B PF Source 5 phase B power factor 7323 SRC 5 Phase C PF Source 5 phase C power factor 7328 SRC 6 P Watts Source 6 three-phase real power B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 514 Source 5 frequency 7562 SRC 6 Frequency Source 6 frequency 7718 SRC 3 Demand Watt Watts Source 3 real power demand 7720 SRC 3 Demand var Vars Source 3 reactive power demand A-10 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 515 Bus 1 Rest C Ang Degrees Bus restraint current phase C angle 9493 Bus Max CT Primary Amps Bus maximum CT primary 9504 Bus 2 Diff A Mag Amps Bus differential IA magnitude B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL A-11...
  • Page 516 Brk 3 Op Time Breaker 3 operating time 12086 Brk 3 Arc Amp A kA2-cyc Breaker 3 arcing amp phase A 12088 Brk 3 Arc Amp B kA2-cyc Breaker 3 arcing amp phase B A-12 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 517 RTD input 15 actual value 13567 RTD Ip 16 RTD input 16 actual value 13568 RTD Ip 17 RTD input 17 actual value 13569 RTD Ip 18 RTD input 18 actual value B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL A-13...
  • Page 518 39182 FlexElement 8 Value FlexElement 8 actual value 45584 RxGOOSE Analog 1 RxGOOSE analog input 1 45586 RxGOOSE Analog 2 RxGOOSE analog input 2 45588 RxGOOSE Analog 3 RxGOOSE analog input 3 A-14 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 519 63626 Bus 1 M_Ir C Bus M_Ir C 63628 Bus 1 d_Ir A Bus d_Ir A 63630 Bus 1 d_Ir B Bus d_Ir B 63632 Bus 1 d_Ir C Bus d_Ir C B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL A-15...
  • Page 520 FLEXANALOG ITEMS APPENDIX A: FLEXANALOG OPERANDS A-16 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 521: B.1 Radius Server Configuration

    UR device for successful authentication, and the shortname is a short, optional alias that can be used in place of the IP address. client 10.0.0.2/24 { secret = testing123 shortname = private-network-1 In the <Path_to_Radius>\etc\raddb folder, create a file called dictionary.ge and add the following content. # ########################################################## GE VSAs ############################################################ VENDOR...
  • Page 522 8.2. Access Settings > Product Setup > Security. Configure the IP address and ports for the RADIUS server. Leave the GE vendor ID field at the default of 2910. Update the RADIUS shared secret as specified in the clients.conf file.
  • Page 523: C.1 Command Line Interface

    • <device> is the UR device name, as displayed in the Device Name field of the Device Setup window and listed in the Online Window. Use quotes with spaces, such as "B30 Belfort". • "-s" can be used with any command to suppress error messages •...
  • Page 524 For non-CyberSentry devices — Set <authentication type> to "traditional". Note that <authentication type> defaults to "traditional" if not specified. Set <account> to "COMMANDS" or "SETTINGS". If not specified, the SETTINGS account is used. Example: SetupCLI URPC login -d "C30 Melbourne" -A traditional -a SETTINGS -w 1password1 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 525 SetupCLI <Application> getsettings -d <device> -f <File> [-s] Read settings from device <device> and save them to the .urs file <File>. The <File> must not already exist. The default path to the output file is C:\Users\Public\Documents\GE Power Management\URPC\Data Example: SetupCLI URPC getsettings -d C30 -f "C30 Markham.urs"...
  • Page 526 SetupCLI URPC getsettings -d demoDevice -f devicefile.urs SetupCLI URPC compare -f existingfile.urs -r devicefile.urs -o output.txt The output is similar to the following: Comparing settings file aaa.urs : C:\Users\Public\Documents\GE Power Management\URPC\Data\ with bbb.urs : C:\Users\Public\Documents\GE Power Management\URPC\Data\ Setting Name (Group,Module,Item) Value...
  • Page 527 SetupCLI URPC getsettings -d DEV@SETUP_CLI -f "example file.urs" SetupCLI URPC logout -d DEV@SETUP_CLI SetupCLI URPC exit DEV@SETUP_CLI has to be used as the device name in the commands followed by the 'adddevice' command. B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 528 COMMAND LINE INTERFACE APPENDIX C: COMMAND LINE INTERFACE B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 529: D.1 Warranty

    D.1 Warranty For products shipped as of 1 October 2013, GE Grid Solutions warrants most of its GE manufactured products for 10 years. For warranty details including any limitations and disclaimers, see the GE Grid Solutions Terms and Conditions at https://www.gegridsolutions.com/multilin/warranty.htm...
  • Page 530 8 December 2016 16-3319 1601-0109-AE1 7.41x 31 January 2017 17-3427 Table D-2: Major changes for B30 manual version AE1 (English) Page Description General revision Added routable GOOSE content in chapters 2 and 5 3-36 Updated RS422 and Fiber Interface Connection figure for the clock channels (from 7a and 7b to 1a and 1b)
  • Page 531 Description Added Engineer content Updated IEC 61850 content Updated FlexAnalog table for most UR products Table D-3: Major changes for B30 manual version AC1 (English) Page Description General revision. Added online help and updated generic online help. Deleted EAC logo from title page and deleted EAC certification from Approvals specifications because document not...
  • Page 532 Added Software Upgrade section to the Maintenance chapter Moved communications appendices B through F to new UR Series Communications Guide for UR 7.3x AB1 Updated product warranty from 24 months to 10 years B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 533 Contact Output FREQ Frequency Communication Frequency-Shift Keying COMM Communications File Transfer Protocol COMP Compensated, Comparison FlexElement™ CONN Connection Forward CONT Continuous, Contact CO-ORD Coordination Generator Central Processing Unit GDOI Group Domain of Interpretation B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 534 Permissive Under-reaching Transfer Trip Manual / Manually Pulse Width Modulated Maximum Power Model Implementation Conformance Minimum, Minutes QUAD Quadrilateral Man Machine Interface Manufacturing Message Specification Rate, Reverse Minimum Response Time Registration Authority Message Reach Characteristic Angle B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 535 Transport Selector Time Undercurrent Time Undervoltage TX (Tx) Transmit, Transmitter Under Undercurrent Utility Communications Architecture User Datagram Protocol Underwriters Laboratories UNBAL Unbalance Universal Relay Universal Recloser Control .URS Filename extension for settings files Undervoltage B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 536 ABBREVIATIONS B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 537 ....................5-220 latching outputs ................5-239 specifications ..................2-21 zoning ....................... 8-3 Approvals ....................2-33 Architecture, relay ................5-146 Arcing current ..................5-220 Attempt to contact RADIUS server failed message ..7-10 Audit list of port numbers ...............5-31 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 538 ................... 5-235 import preferences ................. 10-7 FlexLogic operands ..............5-153 Circuit monitoring applications ..........5-215 settings ....................5-234 Cleaning ....................2-33 specifications ..................2-25 thresholds ..................5-235 wet and dry connections .............. 3-19 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 539 ................7-2 actual values ..................6-23 error messages ..................7-7 clearing ..................5-26, 7-2 FlexLogic operands ...............5-153 settings ....................5-101 settings ....................5-241 Data, reading values ................6-1 specifications ..................2-26 Dataset member is empty message ........5-54 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 540 ................6-25 create logic diagram ..............4-32 Firmware upgrade or downgrade .......... 10-11 Error messages ................. 4-40 Firmware version does not match EnerVista ....10-11 Warning messages ................. 4-41 Flash memory ..............10-18, 10-19 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 541 URs ..........2-8 specifications ..................2-27 self-test errors ................... 7-11 Frequency metering Heartbeat messages ............5-53, 5-56 actual values ..................6-20 HTTP ......................5-85 specifications ..................2-24 port, close .................... 5-85 Frequency tracking ................6-20 Humidity specifications ..............2-31 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 542 RTD input specifications ............... 2-26 LEDs RTD inputs ................... 3-20 clear ..................... 5-241 virtual ....................5-236 custom labels ..................4-24 explained ....................4-20 In Service ....................3-43 settings ....................5-106 Trouble ....................3-43 Link power budget ................2-30 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 543 .................10-1 actual values ..................6-24 Model information, view ..............6-24 update ......................7-3 Model number ..................3-1 Oscillatory transient testing specifications ......2-32 Modem connection ................3-56 Modification file number ..............6-25 Module failure error ..............7-6, 7-7 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 544 ................4-30, 5-9, 5-10 Power supply settings templates ................4-7 description ................... 3-10 wrong entry ..................4-31 removal to replace battery ............10-14 Permissive functions ...............5-199 specifications ..................2-26 Per-unit quantity ..................5-4 viii B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 545 .............. 3-34 with fiber interface ................3-36 RS485 RADIUS server description ................... 3-24 authentication ..................5-15 settings ....................5-28 setup ......................B-1 specifications ..................2-29 RAM required ..................3-45 RTD FlexAnalogs .................. A-13 Reactive power ..................6-17 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 546 ..............5-107 update or downgrade ..............10-10 Serial number ..............3-1, 4-11, 6-24 Source frequency ................6-20 Serial ports Source transfer schemes ............. 5-199 settings ....................5-28 specifications ..................2-29 Server authentication ............... 5-15 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 547 ....................7-3 setting not working ...............5-215 LEDs ......................7-3 unit not programmed error ............5-124 self-test error messages ..............7-5 TxGOOSE settings ................5-252, 5-253 actual values ..................6-11 settings ....................5-53 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 548 ..................2-22 User-programmable pushbuttons FlexLogic operands ...............5-155 logic diagrams .................5-113 XOR gate explained ................4-53 settings ....................5-109 specifications ..................2-23 User-programmable self-test settings .........5-107 Yellow caution icon in Offline Window ........4-39 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...
  • Page 549 INDEX Zero-sequence core balance ............3-12 Zoning ......................8-3 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL xiii...
  • Page 550 INDEX B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL...

Table of Contents