GE C60 Instruction Manual page 537

Breaker protection system ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 37 of 66)
ADDR
REGISTER NAME
Neutral Overvoltage (Read/Write Grouped Setting) (3 modules)
7F00
Neutral Overvoltage 1 Function
7F01
Neutral Overvoltage 1 Signal Source
7F02
Neutral Overvoltage 1 Pickup
7F03
Neutral Overvoltage 1 Pickup Delay
7F04
Neutral Overvoltage 1 Reset Delay
7F05
Neutral Overvoltage 1 Block
7F07
Neutral Overvoltage 1 Target
7F08
Neutral Overvoltage 1 Events
7F09
Neutral Overvoltage 1 Curves
7F0A
Reserved (7 items)
7F11
...Repeated for Neutral Overvoltage 2
7F22
...Repeated for Neutral Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting) (2 modules)
7F60
Auxiliary Undervoltage 1 Function
7F61
Auxiliary Undervoltage 1 Signal Source
7F62
Auxiliary Undervoltage 1 Pickup
7F63
Auxiliary Undervoltage 1 Delay
7F64
Auxiliary Undervoltage 1 Curve
7F65
Auxiliary Undervoltage 1 Minimum Voltage
7F66
Auxiliary Undervoltage 1 Block
7F68
Auxiliary Undervoltage 1 Target
7F69
Auxiliary Undervoltage 1 Events
7F6A
Reserved (7 items)
7F71
...Repeated for Auxiliary Undervoltage 2
Auxiliary Overvoltage (Read/Write Grouped Setting) (2 modules)
7FA0
Auxiliary Overvoltage 1 Function
7FA1
Auxiliary Overvoltage 1 Signal Source
7FA2
Auxiliary Overvoltage 1 Pickup
7FA3
Auxiliary Overvoltage 1 Pickup Delay
7FA4
Auxiliary Overvoltage 1 Reset Delay
7FA5
Auxiliary Overvoltage 1 Block
7FA7
Auxiliary Overvoltage 1 Target
7FA8
Auxiliary Overvoltage 1 Events
7FA9
Reserved (8 items)
7FB1
...Repeated for Auxiliary Overvoltage 2
Frequency (Read Only)
8000
Tracking Frequency
Temp Monitor Actual Values (Read Only Non-Volatile)
81C0
Reserved Register T1
81C1
Reserved Register T2
81C2
Reserved Register T3
81C4
Reserved Register T4
81C6
Reserved Register T5
81C8
Reserved Register T6
81CA
Reserved Register T7
81CC
Reserved Register T8
EGD Fast Production Status (Read Only Non-Volatile and Read Only)
83E0
EGD Fast Producer Exchange 1 Signature
83E1
EGD Fast Producer Exchange 1 Configuration Time
83E3
EGD Fast Producer Exchange 1 Size
EGD Slow Production Status (Read Only Non-Volatile and Read Only) (2 modules)
83F0
EGD Slow Producer Exchange 1 Signature
GE Multilin
RANGE
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 3
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 600
0 to 1
0 to 3
0 to 4294967295
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 65535
2 to 90
-55 to 125
-55 to 125
-2147483647 to
2147483647
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65535
0 to 4294967295
0 to 65535
0 to 65535
C60 Breaker Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F116
0 (Definite Time)
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
---
1
F111
0 (Definite Time)
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
Hz
0.01
F001
C
1
F002
C
1
F002
---
1
F004
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F001
---
---
F003
---
1
F001
---
1
F001
DEFAULT
0 (Disabled)
0 (SRC 1)
300
100
B
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
700
100
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
300
100
100
0
0 (Self-reset)
0 (Disabled)
0
0
-55
125
0
0
0
0
0
0
0
0
0
0
B-45

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents