GE C60 Instruction Manual page 532

Breaker protection system ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 32 of 66)
ADDR
REGISTER NAME
5D0A
Ground Time Overcurrent 1 Events
5D0B
Reserved (6 items)
5D11
...Repeated for Ground Time Overcurrent 2
5D22
...Repeated for Ground Time Overcurrent 3
5D33
...Repeated for Ground Time Overcurrent 4
B
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (8 modules)
5DA0
Ground Instantaneous Overcurrent 1 Function
5DA1
Ground Instantaneous Overcurrent 1 Signal Source
5DA2
Ground Instantaneous Overcurrent 1 Pickup
5DA3
Ground Instantaneous Overcurrent 1 Delay
5DA4
Ground Instantaneous Overcurrent 1 Reset Delay
5DA5
Ground Instantaneous Overcurrent 1 Block
5DA7
Ground Instantaneous Overcurrent 1 Target
5DA8
Ground Instantaneous Overcurrent 1 Events
5DA9
Reserved (8 items)
5DB1
...Repeated for Ground Instantaneous Overcurrent 2
5DC2
...Repeated for Ground Instantaneous Overcurrent 3
5DD3
...Repeated for Ground Instantaneous Overcurrent 4
5DE4
...Repeated for Ground Instantaneous Overcurrent 5
5DF5
...Repeated for Ground Instantaneous Overcurrent 6
5E06
...Repeated for Ground Instantaneous Overcurrent 7
5E17
...Repeated for Ground Instantaneous Overcurrent 8
Setting Groups (Read/Write Setting)
5F70
Setting Group for Modbus Comms (0 means group 1)
5F71
Setting Groups Block
5F73
FlexLogic Operands to Activate Groups 2 through 6 (5
items)
5F7D
Setting Group Function
5F7E
Setting Group Events
Setting Groups (Read Only)
5F7F
Current Setting Group
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
5F94
Setting Group 2 Name
5F9C
Setting Group 3 Name
5FA4
Setting Group 4 Name
5FAC
Setting Group 5 Name
5FB4
Setting Group 6 Name
Open Pole Detect (Read/Write Grouped Setting)
6040
Open Pole Detect Function
6041
Open Pole Detect Block
6043
Open Pole Detect A Aux Co
6045
Open Pole Detect B Aux Co
6047
Open Pole Detect C Aux Co
6049
Open Pole Detect Current Source
604A
Open Pole Detect Current Pickup
604B
Open Pole Detect Voltage Source
604C
Open Pole Detect Voltage Input
604D
Open Pole Detect Pickup Delay
604E
Open Pole Detect Reset Delay
604F
Open Pole Detect Target
6050
Open Pole Detect Events
6051
Open Pole Detect Broken Co
B-40
RANGE
0 to 1
0 to 1
0 to 1
0 to 5
0 to 30
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 5
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
0 to 5
---
---
---
---
---
---
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 5
0.05 to 20
0 to 5
0 to 1
0 to 65.535
0 to 65.535
0 to 2
0 to 1
0 to 1
C60 Breaker Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F001
---
1
F300
---
1
F300
---
1
F102
---
1
F102
---
1
F001
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F167
pu
0.01
F001
---
1
F167
---
1
F102
s
0.001
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F102
DEFAULT
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
0
0
0
0 (Disabled)
0 (Disabled)
0
(none)
(none)
(none)
(none)
(none)
(none)
0 (Disabled)
0
0
0
0
0 (SRC 1)
20
0 (SRC 1)
0 (Disabled)
60
100
0 (Self-reset)
0 (Disabled)
0 (Disabled)
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading