6 ACTUAL VALUES
The metered frequency values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was pro-
grammed by the user for the associated source (see
is measured via software-implemented zero-crossing detection of an AC signal. The signal is either a
SOURCE FREQUENCY
Clarke transformation of three-phase voltages or currents, auxiliary voltage, or ground current as per source configuration
(see the
SYSTEM SETUP
final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and
transients.
PATH: ACTUAL VALUES
METERING
SYNCHROCHECK 1
MESSAGE
MESSAGE
If a synchrocheck function setting is "Disabled", the corresponding actual values menu item is not displayed.
PATH: ACTUAL VALUES
METERING
TRACKING FREQUENCY
The tracking frequency is displayed here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE
System section of chapter 5 for details.
PATH: ACTUAL VALUES
METERING
FLEXELEMENT 1
The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
Table 6–2: FLEXELEMENT BASE UNITS (Sheet 1 of 2)
BREAKER ACC ARCING AMPS
(Brk X Acc Arc Amp A, B, and C)
BREAKER ARCING AMPS
(Brk X Arc Amp A, B, and C)
DCmA
FAULT LOCATION
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
GE Multilin
SETTINGS
settings). The signal used for frequency estimation is low-pass filtered. The
POWER SYSTEM
SYNCHROCHECK
SYNCHROCHECK 1 DELTA
VOLT:
0.000 V
SYNCHROCHECK 1 DELTA
PHASE:
0.0°
SYNCHROCHECK 1 DELTA
FREQ:
0.00 Hz
TRACKING FREQUENCY
TRACKING FREQUENCY:
60.00 Hz
setting in the
SETTINGS
FLEXELEMENTS
FLEXELEMENT 1
OpSig: 0.000 pu
2
× cycle
BASE = 2000 kA
2
× cycle
BASE = 1 kA
BASE = maximum value of the
under the +IN and –IN inputs.
BASE = Line Length as specified in Fault Report
f
= 1 Hz
BASE
ϕ
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
C60 Breaker Protection System
SYSTEM SETUP
SIGNAL SOURCES
SYNCHROCHECK 1(4)
SYSTEM SETUP
POWER SYSTEM
FLEXELEMENT 1(8)
setting for the two transducers configured
DCMA INPUT MAX
6.3 METERING
).
6.3.3 SYNCHROCHECK
6.3.4 TRACKING FREQUENCY
menu. See the Power
6.3.5 FLEXELEMENTS
6-21
6