6.3 METERING
Table 6–2: FLEXELEMENT BASE UNITS (Sheet 2 of 2)
SOURCE ENERGY
(Positive and Negative Watthours,
Positive and Negative Varhours)
SOURCE POWER
SOURCE VOLTAGE
SYNCHROCHECK
(Max Delta Volts)
PATH: ACTUAL VALUES
 IEC 61850
 GOOSE ANALOGS
The C60 Breaker Protection System is provided with optional IEC 61850 communications capability. This
feature is specified as a software option at the time of ordering. See the Order Codes section of chapter 2
for details.
6
The IEC 61850 GGIO3 analog input data points are displayed in this menu. The GGIO3 analog data values are received
via IEC 61850 GOOSE messages sent from other devices.
PATH: ACTUAL VALUES
 SENSITIVE
 DIRECTIONAL POWER
The effective operating quantities of the sensitive directional power elements are displayed here. The display may be useful
to calibrate the feature by compensating the angular errors of the CTs and VTs with the use of the
settings.
6-22
E
= 10000 MWh or MVAh, respectively
BASE
P
= maximum value of V
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
V
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
BASE


METERING
IEC 61850 GOOSE ANALOGS
ANALOG INPUT
0.000
ANALOG INPUT
MESSAGE
0.000
ANALOG INPUT
MESSAGE
0.000
ANALOG INPUT 32
MESSAGE
0.000


METERING

SENSITIVE DIRECTIONAL POWER

DIRECTIONAL POWER 1
3Φ: 0.000 W
DIRECTIONAL POWER 2
MESSAGE
3Φ: 0.000 W
C60 Breaker Protection System
× I
for the +IN and –IN inputs
BASE
BASE

6.3.6 IEC 61580 GOOSE ANALOG VALUES

1
2
3
6.3.7 SENSITIVE DIRECTIONAL POWER
6 ACTUAL VALUES
and
RCA
CALIBRATION
GE Multilin