B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 54 of 63)
ADDR
REGISTER NAME
C466
Clear Channel Tests Status Operand
C46C
Clear Unauthorized Access Operand
C472
Reserved (13 items)
Direct Input/Output Settings (Read/Write Setting)
C500
Direct Input Default States (8 items)
B
C508
Direct Input Default States (8 items)
C510
Direct Output x 1 Operand (8 items)
C520
Direct Output x 2 Operand (8 items)
Reset (Read/Write Setting)
C750
FlexLogic operand which initiates a reset
Control Pushbuttons (Read/Write Setting) (7 modules)
C760
Control Pushbutton 1 Function
C761
Control Pushbutton 1 Events
C762
...Repeated for Control Pushbutton 2
C764
...Repeated for Control Pushbutton 3
C766
...Repeated for Control Pushbutton 4
C768
...Repeated for Control Pushbutton 5
C76A
...Repeated for Control Pushbutton 6
C76C
...Repeated for Control Pushbutton 7
Force Contact Inputs/Outputs (Read/Write Settings)
C7A0
Force Contact Input x State (96 items)
C800
Force Contact Output x State (64 items)
87L Channel Tests (Read/Write)
C840
Local Loopback Function
C841
Local Loopback Channel
C842
Remote Loopback Function
C843
Remote Loopback Channel
C844
Remote Diagnostics Transmit
Remote Devices (Read/Write Setting) (16 modules)
CB00
Remote Device 1 GSSE/GOOSE Application ID (GOID)
CB21
Remote Device 1 GOOSE Ethernet APPID
CB22
Remote Device 1 GOOSE Dataset
CB23
Remote Device 1 in PMU Scheme
CB24
Reserved
CB25
...Repeated for Device 2
CB4A
...Repeated for Device 3
CB6F
...Repeated for Device 4
CB94
...Repeated for Device 5
CBB9
...Repeated for Device 6
CBDE
...Repeated for Device 7
CC03
...Repeated for Device 8
CC28
...Repeated for Device 9
CC4D
...Repeated for Device 10
CC72
...Repeated for Device 11
CC97
...Repeated for Device 12
CCBC
...Repeated for Device 13
CCE1
...Repeated for Device 14
CD06
...Repeated for Device 15
CD2B
...Repeated for Device 16
Remote Inputs (Read/Write Setting) (32 modules)
CFA0
Remote Input 1 Device
CFA1
Remote Input 1 Bit Pair
CFA2
Remote Input 1 Default State
B-62
RANGE
0 to 4294967295
0 to 4294967295
---
0 to 1
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
0 to 2
0 to 3
0 to 1
1 to 2
0 to 1
1 to 2
0 to 2
---
0 to 16383
0 to 16
0 to 1
0 to 3
1 to 32
0 to 96
0 to 3
L30 Line Current Differential System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F300
---
1
F300
---
---
F001
---
1
F108
---
1
F108
---
1
F300
---
1
F300
---
1
F300
---
1
F102
---
1
F102
---
1
F144
---
1
F131
---
1
F126
---
1
F001
---
1
F126
---
1
F001
---
1
F223
---
---
F209
"Remote Device
---
1
F001
---
1
F184
---
1
F126
---
1
F626
---
1
F001
---
1
F156
---
1
F086
DEFAULT
0
0
0
0 (Off)
0 (Off)
0
0
0
0 (Disabled)
0 (Disabled)
0 (Disabled)
0 (Disabled)
0 (No)
1
0 (No)
1
0 (NO TEST)
1"
0
0 (Fixed)
0 (No)
0 (None)
1
0 (None)
0 (Off)
GE Multilin