GE L30 Instruction Manual page 539

Line current differential system ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 21 of 63)
ADDR
REGISTER NAME
Passwords (Read/Write Setting)
400A
Setting Password Setting
Passwords (Read/Write)
4014
Command Password Entry
401E
Setting Password Entry
Passwords (Read Only)
4028
Command Password Status
4029
Setting Password Status
Passwords (Read/Write Setting)
402A
Command Password Access Timeout
402B
Setting Password Access Timeout
402C
Invalid Password Attempts (before lockout)
402D
Password Lockout Duration
Passwords (Read/Write)
402E
Password Access Events
Passwords (Read/Write Setting)
402F
Local Setting Auth
4031
Remote Setting Auth
4033
Access Auth Timeout
User Display Invoke (Read/Write Setting)
4040
Invoke and Scroll Through User Display Menu Operand
LED Test (Read/Write Setting)
4048
LED Test Function
4049
LED Test Control
Preferences (Read/Write Setting)
404F
Language
4050
Flash Message Time
4051
Default Message Timeout
4052
Default Message Intensity
4053
Screen Saver Feature
4054
Screen Saver Wait Time
4055
Current Cutoff Level
4056
Voltage Cutoff Level
87L Channel Status (Read Only)
4059
Channel 1 Local Loopback Status
405A
Channel 1 Loop Delay
405B
Channel 1 Number of Lost Packets
405C
Channel 1 Remote Loopback Status
405D
Channel 1 Status
405E
Channel 2 Local Loopback Status
405F
Channel 2 Loop Delay
4060
Channel 2 Number of Lost Packets
4061
Channel 2 Remote Loopback Status
4062
Channel 2 Status
4063
Channel PFLL Status
4064
87L Network Status
87L Channel Status (Read/Write Command)
4065
Channel Status Clear
87L Power System (Read/Write Setting)
4068
Block GPS Time Reference
406A
Channel Asymmetry Compensation
406C
Charging Current Compensation
406D
Local Relay ID
406E
Maximum Channel Asymmetry
GE Multilin
RANGE
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
5 to 480
5 to 480
2 to 5
5 to 60
0 to 1
1 to 4294967295
0 to 4294967295
5 to 480
0 to 4294967295
0 to 1
0 to 4294967295
0 to 5
0.5 to 10
10 to 900
0 to 3
0 to 1
1 to 65535
0.002 to 0.02
0.1 to 1
0 to 2
0 to 200
0 to 65535
0 to 2
0 to 2
0 to 2
0 to 200
0 to 65535
0 to 2
0 to 2
0 to 2
0 to 2
0 to 1
0 to 4294967295
0 to 4294967295
0 to 1
0 to 255
0 to 10
L30 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F202
---
1
F202
---
1
F202
---
1
F102
---
1
F102
min
1
F001
min
1
F001
---
1
F001
min
1
F001
---
1
F102
---
1
F300
---
1
F300
min
1
F001
---
1
F300
---
1
F102
---
1
F300
---
1
F531
s
0.1
F001
s
1
F001
---
1
F101
---
1
F102
min
1
F001
pu
0.001
F001
V
0.1
F001
---
1
F134
ms
0.1
F001
---
1
F001
---
1
F134
---
1
F134
---
1
F134
ms
0.1
F001
---
1
F001
---
1
F134
---
1
F134
---
1
F134
---
1
F134
---
1
F126
---
1
F300
---
1
F300
---
1
F102
---
1
F001
ms
0.1
F001
DEFAULT
(none)
(none)
(none)
B
0 (Disabled)
0 (Disabled)
5
30
3
5
0 (Disabled)
1
1
30
0
0 (Disabled)
0
0 (English)
10
300
0 (25%)
0 (Disabled)
30
20
10
2 (n/a)
0
0
2 (n/a)
1 (OK)
2 (n/a)
0
0
2 (n/a)
2 (n/a)
1 (OK)
2 (n/a)
0 (No)
0
0
0 (Disabled)
0
15
B-29