Siemens SIMATIC NETS7-1200 Operating Instructions Manual page 55

Telecontrol cp 1242-7
Hide thumbs Also See for SIMATIC NETS7-1200:
Table of Contents

Advertisement

Parameter
Declaration
ERROR
OUTPUT
STATUS
OUTPUT
The codes BUSY, DONE and ERROR
The codes of DONE and ERROR are relevant only when BUSY = 0.
BUSY
DONE
ERROR
0
0
0
You will find all other code combinations of DONE and ERROR in the following table.
The codes DONE, ERROR and STATUS
The following table shows the condition codes formed based on DONE, ERROR and
STATUS that must be evaluated by the user program.
DONE
ERROR
STATUS
1
0
0000
0
0
7000
0
0
7001
0
0
7002
0
1
8086
0
1
80E1
0
1
80E4
0
1
80E6
0
1
80E7
0
1
80E8
0
1
80E9
CP 1242-7
Operating Instructions, 09/2011, C79000-G8976-C247-02
Data type
Possible values
BOOL
0: -
1: Error
WORD
Meaning
No job being executed
Meaning
Job executed without errors
H
No job processing active (first instruction call)
H
Job processing started (first instruction call)
H
Job processing already active (renewed instruction call when BUSY = 1)
H
Illegal value for ID
H
Timeout:
H
Increase the value of the "Transmit timeout" in the configuration of the CP 1242-7 or
Check the connection partner.
Unknown ID:
H
First call TC_CON.
No query in progress (instruction call not started)
H
Data to be sent not completely transferred:
H
Repeat the job.
Remote partner cannot be reached.
H
Connection establishment by remote partner:
H
Check the connection partner. If necessary, terminate the connection with TC_DISCON
and establish it again with TC_CON.
5.4 Configuring the telecontrol instructions
Description
Error code
For the meaning in conjunction with the
parameters DONE and STATUS, refer to
Codes of the instruction.
Status code
For the meaning in conjunction with the
parameters DONE and ERROR, refer to
Codes of the instruction.
Configuration