Notes on operation
4.6 Calling a TeleService connection
Requirement for switching the connection
The request for connection establishment is triggered by the engineering station. To switch
the connection to the remote station, a telecontrol server or a TeleService gateway is
required. See also section Requirements for operation (Page 12).
Procedure for connection establishment for TeleService
Follow the steps below to establish a TeleService connection to the remote station via GPRS
from the engineering station:
1. Select the CPU of the remote station in the STEP 7 project.
2. Select the "Online" > "Online & Diagnostics" menu.
3. Choose the entry "TeleService via GPRS" in the "Type of interface" drop-down list.
4. Choose the entry "TeleService via GPRS" in the "PG/PC interface" drop-down list.
5. Click on the
6. Make the necessary entries in this dialog.
Note
No TeleService connection establishment using "Online" > "Go online"
If you attempt to establish a TeleService connection by selecting the CPU and then selecting
the menu or shortcut menu command "Online" > "Connect online", STEP 7 will automatically
attempt to connect via Ethernet. Reason: In STEP 7, the last connection path used to
download the project data is stored.
TeleService only from one STEP 7 project
You can only operate TeleService on an engineering Station from within a single STEP 7
project. TeleService from more than one STEP 7 project at any one time is not possible.
Terminating a TeleService connection
On completion of the TeleService session, terminate the TeleService connection again using
the "Go offline" button. The connection is terminated after approximately 5 minutes.
Loading only in offline mode
Loading software and blocks with TeleService via GPRS by calling the function "Load to
device" only works when no TeleService connection is established.
40
The "Online access" dialog opens.
icon next to the "PG/PC interface" drop-down list.
The "Establish remote connection" dialog box opens.
You will find information on the necessary entries in the tooltips of the STEP 7 online
help.