Honeywell UDC2500 Product Manual page 50

Universal digital controller
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

Configuration
Function Prompt
Lower Display
BAUD
TX_DLY
WS_FLT
SDENAB
SHDTIM
SDMODE
Selection or Range of
Setting
Upper Display
4800
9600
19200
38400
1 to 500 milliseconds
FP B
FPBB
FP L
FPLB
DIS
EnAB
0 to 255 Sample Periods
LAST
UDC2500 Universal Digital Limit ControllerProduct Manual
Parameter
Definition
BAUD RATE is the transmission speed in bits per
second.
4800 BAUD
9600 BAUD
19200 BAUD
38400 BAUD
TX DELAY—Configurable response-delay timer
allows you to force the UDC to delay its response
for a time period of from 1 to 500 milliseconds
compatible with the host system
hardware/software. This parameter is also used for
the IR communications link.
Defines word/byte order of floating point data for
communications. Byte values:
0
1
seeeeeee emmmmmmm mmmmmmmm mmmmmmmm
Where:
s = sign, e = exponent, m = mantissa bit
0
1
1
0
3
2
2
3
SHED ENABLE—Disables/enables shed
functionaliy.
SHED TIME—The number that represents how
many sample periods there will be before the
controller sheds from communications. Each
period equals 1/3 seconds; 0 equals No shed.
Note: If ComSTA is set to MODBUS and if
SHEDENAB is set to DISABL, Shed Time will not
be configurable.
SHED CONTROLLER MODE AND OUTPUT
LEVEL—Determines the mode of local control you
want when the controller is shed from the
communications link.
LAST—SAME MODE AND OUTPUT—The
controller will return to the same mode (manual or
automatic) at the same output level that it had
before shed.
2
3
2
3
3
2
1
0
0
1
40