<Figure 9> Correction of refrigerant piping length
MXZ-SM120TAM-U1
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0
<Figure 10> Correction of refrigerant piping length
■ Method for obtaining the piping equivalent length
Piping equivalent length = piping length to the farthest indoor unit + 0.3 × number of bends in the piping (m)
5-5-3. Correction of heating capacity for frost and defrosting
If heating capacity has been reduced due to frost formation or defrosting, multiply the capacity by the appropriate correc-
tion factor from the following table to obtain the actual heating capacity.
Correction factor diagram
Outdoor Intake temperature [°F(°C)WB]
Correction factor
OCH800A_29
50
100
150
200
Piping equivalent length (ft)
50
100
150
200
Piping equivalent length (ft)
43(6)
37(4)
1.00
0.98
250
300
350
250
300
350
36(2)
32(0)
28(−2)
25(−4)
21(−6)
0.89
0.88
0.89
0.90
0.95
400
450
500
400
450
500
18(−8)
14(−10)
5(−15)
−4(−20)
0.95
0.95
0.95
0.95
−13(−25)
0.95