Mitsubishi Electric MXZ-SM72TAM-U1 Service Manual page 135

Hide thumbs Also See for MXZ-SM72TAM-U1:
Table of Contents

Advertisement

5. Complete the function settings
• When the settings are completed, press the [SELECT] button to send the setting data from the remote controller to
the indoor units.
When the transmission is successfully completed, the screen will return to the function setting screen.
Function setting
Ref. address
Sending data
F1
F2
SELECT
MENU
RETURN
HOLD
Notes:
• Make the above settings only on Mr. Slim units as necessary.
• The above function settings are not available for the CITY MULTI units.
• Refer to the indoor unit Installation Manual for information about initial settings, mode numbers, and setting numbers
for the indoor
units.
• Be sure to write down the settings for all functions if any of the initial settings has been changed after the completion
of installation work.
13-5-2. PAR-FL32MA
Functions can be selected with the wireless remote controller. Function selection using wireless remote controller is avail-
able only for refrigerant system with wireless function. Refrigerant address cannot be specified by the wireless remote
controller.
An example of function selection flow
ON/OFF button
Temperature
setting buttons
Check button
Hour button
Minute button
Operating instructions
CHECK
1. Press the
• Press the TEMP
• Direct the wireless remote controller toward the receiver of the indoor unit and press the
OCH800A_135
F3
F4
ON
OFF
CHECK
TEMP
ON/OFF
FAN
AUTO STOP
AUTO START
MODE
VANE
CHECK LOUVER
h
TEST RUN
min
RESET
SET
CLOCK
button twice continuously. →
button once to set the address number to ˝50˝.
An example of a function selection flow is shown below. It shows how to turn off the function
that raises the set temperature by 4 degrees during heating operation. (Mode 24: 2)
Function setting
Mode
Raising the set temperature by 4 degrees
CHECK
1. Press the
button twice continuously.
will appear and ˝00˝ will blink. (Self-diagnosis mode)
CHECK
Enter the the address ˝50˝ during self-diagnosis mode, then press
2. Enter the unit No. ˝01˝ (since ˝01˝ is assigned to the target unit).
(Enter the address during self-diagnosis mode, then press the
Note: You cannot specify the refrigerant address.
3. Enter the mode No. ˝24˝ (function that raises set temperature by 4 degrees
during heating operation).
(Enter the address during self-diagnosis mode, then press the
4. Enter the setting No. ˝02˝ (OFF).
(Enter the address during self-diagnosis mode, then press the
NO
Finished
YES
7. End the function selection.
(End check mode.)
Note:
When you switch the mode to function selection mode with a wireless remote controller, the unit
ends function selection mode automatically if nothing is input for 10 minutes or longer.
appears and ˝00˝ blinks.
CHECK
Mode No.
Setting
Setting No. Target unit No.
24
01
OFF
02
h
button.
min
button.)
5. NO
h
button.)
h
button.)
h
button.
6. YES
Change
unit No.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mxz-sm96tam-u1Mxz-sm120tam-u1

Table of Contents