Mitsubishi Electric MXZ-SM72TAM-U1 Service Manual page 108

Hide thumbs Also See for MXZ-SM72TAM-U1:
Table of Contents

Advertisement

SW1
Contents
setting
No. 12345678
47
11110100 State of LEV
control
48
00001100 State of compres-
sor frequency
control 1
49
10001100 State of compres-
sor frequency
control 2
50
01001100 Protection input
51
11001100 The second
current value
when micropro-
cessor of power
board abnormality
is detected
52
00101100 Heatsink tem-
perature when
microprocessor of
power board
abnormality is
detected
53
10101100 Outdoor LEV-A
opening pulse
54
01101100 Outdoor LEV-A
opening pulse
abnormality delay
55
11101100 Outdoor LEV-A
opening pulse
abnormality
56
00011100 Outdoor LEV-B
opening pulse
57
10011100 Outdoor LEV-B
opening pulse
abnormality delay
58
01011100 Outdoor LEV-B
opening pulse
abnormality
59
11011100 63LS (Low
pressure)
60
00111100 63LS abnormality
delay
61
10111100 63 LS abnormality
62
01111100 TH2 (HIC pipe)
63
11111100 TH2 (HIC)
abnormality delay
64
00000010 TH2 (HIC)
abnormality
65
10000010 Operational
frequency
66
01000010 Target frequency 0–255 (Hz)
67
11000010 Outdoor fan
control step
number
68
00100010 Indoor LEV
Opening pulse
(No. 1 to 30 units)
69
10100010 High pressure
sensor (Pd)
OCH800A_108
1
2
3
Cooling/
Cooling:
Cooling/
Heating:
SHd de-
Heating:
Td over heat
crease
Min.Sj
prevention
prevention
correction
depends on
Td
Note: Display active LEV control
Condensing
Compressor
temperature
temperature
limit control
control
Note: Display active compressor frequency control
(High pressure and overheating control: only when connected to Ecodan)
Heat sink
Secondary
Input current
over heat
current
control
prevention
control
control
Note: Display active compressor frequency control
(High pressure and overheating control: only when connected to Ecodan)
63LS
HIC abnor-
abnormality
mality
Note: Display detected microprocessor protection or abnormality
0–999.9 (Arms)
Note: Display data at time of abnormality
−99.9–999.9 (°F)
Note: Display data at time of abnormality
0–2000 (pulse)
Note: Display of data at time of abnormality and abnormality delay
−99.9–999.9 (psig)
Note: Display of data from sensor
−99.9–999.9 (psig)
Display of data at time of abnormality and abnormality delay
−99.9–999.9 (°F)
Note: Display of data from thermistor
−99.9–999.9 (°F)
Note: Display of data at time of abnormality and abnormality delay
0–255 (Hz)
Note: Display of actual operating frequency
Note: Display of target frequency
0–15
Note: Display of number of outdoor fan control steps (target)
0–2000 (pulse)
Notes:
•Address and display data are alternately displayed every second.
•Pressing SWP2 changes the displayed unit in ascending order; it returns to No. 1 after No. 30.
−99.9–999.9 (psig)
Note: Display of detected data of outdoor unit sensors and thermistors
LED1, 2
4
5
6
Cooling/
Heating:
Heating:
Heating:
LEV opening
LEV opening
Min.Sj
correction
correction
correction
depends on
depends on
depends on
Pd
Td
Shd
Discharge
Pd abnormali-
Pd Back up
temp.
ty control
control
(heating)
(heating)
(heating)
backup
control
Unbalance
Frequency
Low pressure
control of
restrain of
decrease
3-phase
receipt
prevention
power supply
voltage
change
Frozen
4-way valve
Delay caused
protection
disconnection
by closed
abnormality
valve in
cooling mode
7
8
Cooling:
Correction of
high com-
pression ratio
prevention
Freeze
prevention
control at the
beginning of
SHd
Hz-up inhibit
High pressure
control at the
and overheat-
beginning of
ing control
SHd
TH6 abnor-
Power
mality
module
abnormality