Overview of Alarms
249153
<location>Cooling system: The water flow too low
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The drive converter cooling system signals that the water flow is too low.
- after the ON command, the feedback signal has not been received within the selected
starting time (p0260).
- in operation, the feedback signal has failed for longer than the permitted failure time
(p0263).
See also: p0260, p0263, r0267
Remedy:
- check the wiring between the cooling system and the input terminal (terminal module).
- check the external control unit for the cooling system.
249154
<location>Cooling system: Water has leaked
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The leakage water monitoring function has responded.
See also: r0267
Remedy:
- check the cooling system for leaks in the cooling circuit.
- check the wiring of the input terminal (terminal module) used to monitor the leakage
water.
249155
<location>Cooling system: Power stack adapter, firmware version too
old
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
The firmware version in the power stack adapter (PSA) is too old and does not support any
water cooling.
Remedy:
Upgrade the firmware version.
249156
<location>Cooling system: Cooling water temperature, fault threshold
exceeded
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The cooling water intake temperature has exceeded the permanently set fault threshold.
Remedy:
Check the cooling system and the ambient conditions.
249170
<location>Cooling system: Alarm occurred
Reaction:
NONE
Acknowledge:
NONE
Cause:
The cooling system signals a general alarm.
Remedy:
- check the wiring between the cooling system and the input terminal (terminal module).
- check the external control unit for the cooling system.
249171
<location>Cooling system: Conductivity has exceeded the alarm
threshold
Reaction:
NONE
Acknowledge:
NONE
Cause:
The conductivity of the cooling water has exceeded the selected alarm threshold
(p0269[1]).
See also: p0266
Remedy:
Check the device to de-ionize the cooling water.
249172
<location>Cooling system: Conductivity actual value is not valid
Reaction:
NONE
Acknowledge:
NONE
2-816