Diagnostics

4.1 Diagnostics via LEDs

4.1
Diagnostics via LEDs
4.1.1

Control Units

4.1.1.1

Description of the LED states of a CU320-2

The various states of the Control Units CU320-2 DP and CU320-2 PN during power-up and
during operation are displayed using LEDs on the Control Unit. The duration of the individual
statuses varies.
Table 4- 1
LED
RDY
DP/PN
OPT
● If an error occurs, the booting procedure is terminated and the cause is indicated
accordingly via the LEDs.
● Once the unit has successfully booted up, all the LEDs are switched off briefly.
● Once the unit has booted up, the LEDs are controlled via the loaded software.
Control Unit 320-2 DP while powering up
Table 4- 2
Red flashing
light 2 Hz
Red flashing
light 2 Hz
306
LEDs
Function
Ready
PROFIdrive cyclic operation via PROFIBUS (DP) or PROFINET (PN)
OPTION
Load software
LED
RDY
DP
Red
Orange
Red
Red
Red
Red
Flashing
light 2 Hz
Red
Orange
flashing
light
Red
Off
State
OPT
Orange
Reset
Off
BIOS loaded –
Off
BIOS error
Off
File error
Off
FW loading
Off
FW loaded
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
Comment
Hardware reset
RDY LED lights up red, all other LEDs light
up orange
Error occurred while loading the BIOS
Memory card not inserted or faulty
Software on memory card not present
or corrupted
RDY LED lights up red, PN LED flashes
orange without fixed frequency