Siemens Sinamics s120 Commissioning Manual page 159

With starter
Hide thumbs Also See for Sinamics s120:
Table of Contents

Advertisement

Procedure
14.
p1036[0] =
r0019.14 (DO 1)
15.
p1070[0] =
r1050 (DO 63)
16.
Press "FN" and "P". The display indicates 41, press "O", the display jumps to 31.
17.
Start the motor data identification with "I". The drive switches off again after approx. 5 sec., the display goes back
to 41.
18.
After pressing "O", 31 is displayed again. The drive is now ready. The drive is switched on by pressing "I", the mo-
tor accelerates by pressing the "↑" key.
19.
Save all param-
eters
These parameters offer more setting options than specified here. For further setting options see the
1)
SINAMICS S120/S150 List Manual.
[CDS] Parameter depends on command data sets (CDS). Data set 0 is preset.
[DDS] Parameter depends on drive data sets (DDS). Data set 0 is preset.
[MDS] Parameter depends on motor data sets (MDS). Data set 0 is preset.
BI binector input
BO binector output
CI connector input
CO connector output
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
BI: Motor potentiometer setpoint lower [CDS]
Sets the signal source to reduce the setpoint for the motorized potentiometer
Interconnection with r0019.14 of the drive object Control Unit (DO 1)
Effect: Signal, motorized potentiometer lower setpoint from BOP
CI: Main setpoint [CDS]
Sets the signal source for speed setpoint 1 of the speed controller.
Interconnection with r1050.00 to the separate drive object (DO 63)
Effect: Motorized potentiometer supplies the speed setpoint
Press the P key for approx. 5 sec until the display flashes.
3.8 First commissioning vector control AC drive blocksize format
Description
Commissioning
Factory
setting
0
0
159