Logic Output Function

The inverter has a built-in logic output feature. Select any two operands out of all
intelligent output options except LOG1~LOG3 and their operator out of AND, OR, or
XOR (exclusive OR). The terminal symbol for the new output is [LOG]. Use C021,
or
to route the logical result to terminal [11], [12] or the relay terminals.
C026
Intelligent outputs used as
internal inputs:
RUN, FA1, FA2... or
all other output
signals
RUN, FA1, FA2... or
all other output
signals
Option
Terminal
Code
Symbol
LOG1
Logic Output
33
Function
LOG2
34
35
LOG3
11, 12, AL0 – AL2
Valid for inputs:
C141~C150
Required settings
Notes:
C142/C145/C148
Operand A
C143/C146/C149
Operand B
Function Name
State
ON
OFF
[LOG1]/[LOG2]/[LOG3]
Operator
(C144/C147/C150)
AND, OR, XOR
Input Status
A
B
0
0
0
1
1
0
1
1
Description
when the Boolean operation specified by
/C145/C147
has a logical "1" result
when the Boolean operation specified by
/C145/C147
has a logical "0" result
Example for terminal [11] (default output
configuration shown – see
Inverter output
terminal circuit
CM2
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see
Inverter logic
circuit board
AL0
AL1
Power
supply
See I/O specs on
page 4-6
4−75
C022
[LOG] Output State
AND
OR
XOR
0
0
0
0
1
1
0
1
1
1
1
0
C144
C144
page
3-90):
LOG1~3
11
RY
page 4-52 and
3-90):
LOG1~3
AL2
Load