Hitachi WJ200 Series Instruction Manual page 127

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

3−46
Func.
Code
Restart mode on over voltage
b008
/ over current trip
Number of retry on over
b010
voltage / over current trip
Retry wait time on over
b011
voltage / over current trip
"b" Function
Name
Select inverter restart method,
Five option codes:
00...Alarm output after trip, no
01...Restart at 0Hz
03...Resume previous freq.
04...Resume operation after
Range is 1 to 3 times
Range is 0.3 to 100 sec.
Description
automatic restart
02...Resume
operation
after
frequency
matching
after active freq. matching,
then decelerate to stop and
display trip info
active freq. matching
Run
Defaults
Mode
Lnitial data
Units
Edit
00
3
times
1.0
sec

Advertisement

Table of Contents
loading

Table of Contents