Hitachi WJ200 Series Instruction Manual page 276

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Option
Terminal
Code
Symbol
FBV
Feedback Value
31
Check
11, 12, AL0 – AL2
Valid for inputs:
Required settings
A076, C052,
Notes:
• The [FBV] is designed for implementing two-stage
control. The PV high limit and PV low limit
parameters,
C052
and C053, do not function as
process alarm thresholds. Terminal [FBV] does
not provide a PID alarm function.
• The example circuit for terminal [11] drives a relay
coil. Note the use of a diode to prevent the
negative-going turn-off spike generated by the coil
from damaging the inverter's output transistor.
Function Name
State
ON
OFF
C053
Description
• Transitions to ON when the inverter is in RUN
Mode and the PID Process Variable (PV) is less
than the Feedback Low Limit (C053)
• Transitions to OFF when the PID Feedback Value
(PV) exceeds the PID High Limit (C052)
• Transitions to OFF when the inverter goes from
Run Mode to Stop Mode
Example for terminal [11] (default output
configuration shown – see
Inverter output
terminal circuit
CM2
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see
Inverter logic
circuit board
AL0
Power
supply
See I/O specs on
page 4-6
4−73
page
3-90):
FBV
11
RY
page 4-52 and
3-90):
FBV
AL1
AL2
Load